You are on page 1of 4

2002 Student Conference on Research and Development Proceedings, Shah Alam Malaysia

9C”l

Novel Fast Voltage Stability Index (FVSI) for Voltage Stability Analysis
in Power Transmission System
Ismail Musirin’ and Titik Khawa Abdul Rahman’
Faculty of Electrical Engineering
Universiti Teknologi U4RA
40450 Shah Alam. Selangor
MALAYSIA
e-mail:’ismailbm@elect.itm.edu.mv, 2khawa@engr.uitm.edu.my

Abstract - since a couple of decades ago voltage P-V and Q-V curves, modal analysis [2], artificial
stability assessment has received an increasing attention neural networks [ 5 ] , neuro-fuzzy networks (61, reduced
due to the complexity of power system. With the Jacobian determinant, energy function methods [7]and
increase in power demand and limited power sources sensitivity analysis [SI. The P-V and Q-V curves leads
has caused the system to operate at its maximum to proximity to voltage collapse while the others
capacity. Therefore, a study that is able to determine the developed voltage stability indices as indicators. These
maximum capacity limit before voltage collapse must indices are derived referred either to a bus or a line.
be carried out so that necessary precaution can be taken Line stability indices [3,4] can be used to evaluate the
to avoid system capacity violation. on-line voltage stability condition since they can be
This paper presents a novel Fast Voltage Stability evaluated without having to tum off the generators.
Index (FVSI) simplified from a predeveloped voltage This paper presents the development of a novel fast
stability index referred to a line initiated from the voltage stability index (FVSI) referred to a line which is
voltage quadratic equation at the sending end of a capable in determining the point of voltage collapse,
representation of a 2-bus system. The line index in the maximum permissible load, weak bus in the system and
inter-connected system in which the value that is closed the most critical line in an inter-connected system. The
to 1.00 indicates that the line has reached its instability trend of voltage and index profiles were studied by
limit which could cause sudden voltage drop to the increasing the reactive power loading in stages until the
corresponding bus caused by the reactive load variation. load flow solution fails to give any results. FVSI was
The formulated index was tested on the IEEE reliability calculated for each line in the system as reactive load
test system in order to venfy the performance of the increased. The calculated FVSI could be used in
proposed indicator. Results showed that the proposed determining the weakest bus, line criticalness and
technique is indicative in predicting the occurrence of maximum loadability. Verification was conducted by
system collapse and hence necessary action can be re-evaluating the line indices using other techniques
taken to avoid such incident. described in references [3] and [4] and the results are in
close agreement.
Keywords: Voltage stability analysis, voltage collapse,
line index. maximum permissible load 2. VOLTAGE STABILITY INDEX
FORMULATION
1. INTRODUCTION
Voltage stability analysis can be conducted on a
The increase in power demand has forced the power system by evaluating the voltage stability index referred
system network to operate closed to its stability limit. to a line. In this research, the voltage stability index
This phenomenon is continuously becoming an issue referred to a line was formulated from the 2-bus
which requires a voltage stability analysis to be representation of a system. The value of line index
properly conducted especially at the planning stage. which is closed to unity indicates that the respective
According to Cutsem [I], voltage stability is defined as line is closed to its stability limit. To venfy the
the characteristic for a power system to remain in a state effectiveness of the proposed FVSI as a stability
of equilibrium’ at normal operating conditions and to indicator, comparisons were made with the indices
restore an acceptable state of equilibrium after a proposed by M Moghawemi [3] and A Mohamed [4].
disturbance. It is generally categorized into two
categories namely the dynamic and static. The static 2.1 Proposed Fast Voltage Stability Index (FVSI)
voltage stability analysis is widely accepted in the The voltage stability index developed in this paper is
foregoing papers although the dynamic voltage derived by first obtaining the current equation through a
instability has been the one that causes a lot of line in a 2 bus system.
intermptions. The reason being is that, the dynamic
analysis dealt with the non-linear load and rather
difficult to model them. Static voltage stability analysis
is conducted by assuming the system is operating in the
& I! 1.Y P qbW
R tjX
steady state [IO]. Several methods have been proposed Fig. 1. 2-bus model representation
in conducting the voltage stability analysis such as the
0-7803-7565-3/02/$17.00 02002 IEEE. 265
The representation of a 2-bus model is illustrated in Fig.
1. From the figure;

VI, V2 = voltage at the sending and receiving


buses Fig. 2. One-line diagram of transmission line
P,,QI = active and reactive powers at the
sending bus The line stability index can be reproduced as;
P2, Q2 = active and reactive powers at the
receiving bus
SI, S2 = apparent powers on the sending and where:
receiving buses x = line reactance
6 = 61-62 Qr = reactive power at the receiving end
= angle difference between the V, = sending end voltage
sending and receiving buses 8 = line impedance angle
6 = the angle difference between the supply
By taking the sending bus (bus 1) as the reference (i.e. voltage and the receiving voltage
6, = 0 and S, = 6), then the general current equation can
be written as; 2.3. Line Stability Factor
I = Y,LO-V,LB (1) A Mohamed et d. [4] derived four line stability
R+JX factors based on a power transmission concept in a
where; R is the line resistance and X is the line single line. An index was extracted in order to verify
reactance. since this index is the most suitable one. The
formulation begins with the power equation in a power
system. Fig. 3 illustrates a single line of a power
transmission concept.
The roots for V2 will be;
1

To-obtain real roots for V,, the discriminant is set


greater than or equal to ‘0’; i.e;
(3) -, Z=R+IX

4Z’QlX Fig. 3. Single line of power transmission concept


<I
(V,)’(RsinJ +Xcos6)’ - (4) The line stability factor for this model can be
The angle difference 6 is normally very small then, reproduced as;
Sir0,RsinJ -0 o n d X c o s 6 - X
Taking the symbols ’i’ as the sending bus and ‘j’as
the receiving bus. Hence, the fast voltage stability
;[I;[
LQP=4 - -P’ + Q
’ 1)

LQP must be kept less than 1.00 to maintain a


(7)

index FVSI can be defined by; stable system.


(5)
3. VOLTAGE STABILITY ANALYSIS
where: Z =line impedance Many methods were proposed in the literature in
X = line reactance conducting the voltage stability analysis such as the use
Q; = reactive power at the receiving end of P-V curves, Q-V curves, modal analysis, minimum
Vi = sending end voltage singular value, sensitivity analysis and artificial
intelligence. The results from the voltage stability
The line that exhibits FVSI closed to 1.00 implies analysis enabled us to identify the closeness of system
that it is approaching its instability point. If FVSI goes to its instability point, the line which is responsible for
beyond 1.00, one of the buses to the connected to the the voltage instability condition to the whole system
line will experience a sudden voltage drop leading to and the weakest bus that is closed to its maximum
system collapse. allowable load. Voltage stability analysis could be
conducted on-line or off-line, but the off-line studies is
2.2 Line Stability Index preferable in this research since it is less risky. Off-line
The line stability index symbolized by L, proposed voltage stability analysis is normally conducted at the
by M Moghawemi et d. [3] is formulated based on a planning stage capable to give early indication of the
power transmission concept in a single line. A single system load status. The most critical or weakest bus in
line in an interconnected network is illustrated in Fig. the system could be predetermined and the
2. corresponding line responsible for the possible violation
could also be pre-identified, thus necessary precaution
could be taken in avoiding such incidents.

266
4. AC POWER FLOW observed that bus 3 has a maximum injected load of
3.45 P.u.. Buses 15 a d 3 0 indicate 1.60 p.n. and 0.345
AC power flow plays an important role in the VSA p.u. as the maximum permissible reactive load
especially in the planning of future power system respectively. Further increase in the reactive power
expansion as well as to run existing system in the loading above these limits would cause the indices
optimum possible way. Results from the power flow exceed 1.00 and could cause voltage instability to the
computation are the voltages and angles on the system whole system.
. bus, power flow and line losses. Other properties like
current flows and voltage drops could also be included
in the load flow program. Calculation of voltage FVSI vs reactive load variations
stability index could be incorporated in the load flow (IEEE 30-bus)
program resulting a complete voltage stability analysis
process.
4 d
5. RESULT AND DISCUSSION I p- 0.6

0.4 1 L,
A test was conducted on the 30-bus IEEE reliability
test system and the single line diagram is illustrated in
Fig. 4. This system has six generator (PV) buses and
twenty-four load (PQ)buses with 41 interconnected
branches. Three load buses were randomly chosen in
I] metlvr load

order to investigate the effect of reactive power.loading Fig. 5. FVSI versus load variation at bus 3
on FVSI values which in turn identifies the most critical
line with respect to a bus. Reactive load at buses 3, 15 Results for verification conduaed by re-evaluating
and 30 were gradually increased from the base case the same test using I+,,,, and LQP are tabulated in Table
until their maximum allowable load or maximum 1. From the table, it is observed that the results are very
loadabilitywhich is the the maximum load that couldbe closed in agreement
injected to a load bus before the power flow solution
diverges.
I I 7
FVSI vs reactive load variation
(IEEEJO-bus)

1 -__
0 0.5
I reac&load
Line18 - - - + - - L i n e 2 2
--CLine 20 -Line 30
Fig. 6. FVSI versus load variation at bus 15

The voltage profile against reactive load variation is


(2 illustrated in Fig. 8. From the figure, it is observed that
bus voltages decay accordingly as the reactive power
Fig. 4. Single line diagram for IEEE 30-bus loading increased. The curve for bus 30 stops at a
reliability test system reactive loading of 0.345 p,u. with voltage at this point
is 0.527 p.u.. Similarly, the minimum voltage for bus 3
FVSI were evaluated for each line in the system for is 0.709 p,u. while for bus 15 it is at 0.638 P.U.. Since
every load increase. The line exhibited the largest index bus 30 can only withstand maximum injected load of
with respect to a load increase will be determined as the 0.345 p.u. which is the lowest compared to the rest,
most critical line. Any further increase on the load will therefore it is identified as the weakest bus. Conversely,
cause the line to have an index value greater than 1.00 bus 3 is the most secure bus since the maximum
resulting in the entire system instability permissible load is the largest. The determination of the
The graphs appeared in Fig. 5 through 7 illustrate the weakest bus is based on the maximum permissible load
corresponding FVSI profiles against load variations at before voltage collapse.
bus 3, 15 and 30. The highest index from the individual
graph indicates the most critical line referred to bus 3,
15 and 30. For instance, line 4 is the most critical line
with respect to bus 3 since its FVSI value is the highest.
Evaluation on bus 15 indicates that line 18 IS the most
critical line whilst line 38 is the most critical one
referred to bus 30. On the x-axis of the graphs, it is

267
7. REFERENCES
FVSI vs reactive load variation
(IEEE 30-bus)
[I] V T Cutsem and C Vournas, “Voltage Stability of
Electric Power Systems,” Kluwer academic
publishers, Boston, USA, pp 378, 1998.
[2] F D Galiana and Z C Cheng, ‘‘ Analysis of the
Load Behaviour near Jacobian Singularity,” IEEE
Transaction on Power System, Vol. I, pp 1529-
~~

1542, Nov 1992.


[3] M Moghavemmi, and F M Omar, “Technique for
Contingency Monitoring and Voltage Collapse
+Line38 reactive load
Prediction,” IEE Proceeding on Generation,
+Line 39 Transmission and Distribution, Vol. 145, No. 6,
Fig. 7. FVSI versus load variation at bus 30 pp634 - 640,1998.
Bus v o l t y e y.lm lo& r d o n
141 A Mobamed, G B Jasmon and S Yusoff, “A Static
(IEEE 30-bus) Voltage Collapse Indicator Using Line Stability
1.1 Factors,” Journal oflndustrial Technology, Vol. I,
N0.l. Pt C, pp 73-85, 1989.
[5] A El-Keib and X Ma, “Application of Artificial
Neural Networks in Voltage Stability Assessment,”
IEEE Transaction on Power System, Vol. 10, No. 4,
pp 1890 - 1896, Nov 1995.
[6] C Liu, C Chang and M Su, “Neuro-Fuzzy
0, i Networks for Voltage Security Monitoring Based
II on Synchronous Pharos Measurements,” IEEE
w

.*- Transaction an Power System, Vo1.13, No. 2, May


IIO 0.11 1Y L I I.* Id4 1.11
0- 111 &U I.“ II9 XI 1u 141

*.d 1998.
+.-, *.-U -+._I [7] C DeMarco and T Overbye, “An Energy Based
Security Measure for Assessing Vulnerability to
Fig. 8. Voltage profiles against load variation Voltage Collapse,” IEEE Transaction on Power
System, Vo1.5,No. 2, pp419-427,May 1990.
[8] N Flatabo and H Dommel, ‘Voltage Stability
Condition in a Power Transmission System
Calculated by Sensitivity Methods,” IEEE
Transaction on Power System, Vo1.5, pp 1286 -
1293, Nov 1990.
191 E Vaheedi, Y Mansour and D Sun, “Large Scale
Voltage Stability Constrained Optimal Planning
and Voltage Stability Applications Using Existing
OPF/Optimal VAR Planning Tools,” IEEE
Table 1: Re-evaluation of line index using FVSI, L,,,,, Transaction on Power System. Vo1.5, Feb 1999.
and LQP [I011 Musirin and T K Abdul Rahman, “On-Line
Voltage Stability Index for Voltage Collapse
Prediction. in Power System,” presented at Brunei
6. CONCLUSION International Conference on Engineering and
Technology 2001 (BICETZOOl), Brunei. October
A rigorous investigation on the effect of reactive 2001.
power loading was canied out and tests were performed
on the IEEE 30-bus reliability test system. Results
showed that the proposed index is capable at
determining the point of voltage instability, critical line
referred to a bus and the weakest bus in the system.
Voltage instability point is indicated by the FVSI value
closed to 1.00. Verification that was performed by re-
evaluating the line indices using L,and LQP
demonstrated a close agreement between the indices
thus making the proposed index is comparable as an
early warning tool to voltage collapse.

268

You might also like