Professional Documents
Culture Documents
Abstract---The voltage instability is a serious issue in the model characterized by nonlinear differential and algebraic
modern power systems with rapid voltage droop due to equations which include generator dynamics, OLTC
stressed system with increased loading. Many techniques have transformers, SVC, etc, through transient stability
been given to predict the voltage collapse and maintain the simulations [4]. Although stability studies, in general,
voltage stability of a power system. The Voltage stability index
require a dynamic model of the power system, in this paper
(VSI) is a feature for solving voltage stability problems. In this
paper, a new index is proposed and the performance of the analysis of voltage behaviour has been approached using
new index with other indices is discussed. The effectiveness of both static and dynamic techniques, which have been
the proposed method is demonstrated through numerical widely used for voltage stability analysis [1]. An accurate
studies on IEEE 30 bus system, using several scenarios of load knowledge of how close the actual system‟s operating point
increase. The process known as continuation load flow is used. is from the voltage stability limit (nose point) which is a
The proposed voltage stability index is based on the difference measure of the voltage stability margin is crucial to
between the present bus voltage level and the voltage at the operators. Therefore, to find voltage stability indices have
nose point where the Jacobian becomes singular for the same become an important task for many stability studies. These
load condition. A stable system may suffer voltage collapse
indices provide reliable information about proximity to
when a contingency occurs. This paper analyses these cases. A
new sensitivity factor between reactive power injection and system voltage instability. The voltage stability index
improvement to the voltage stability margin is discussed. proposed here and its comparison with existing methods
Keywords- voltage stability, continuation load flow, voltage will be highlighted in this paper, through results obtained
stability index, nose point. from simulating on IEEE 30 bus system.
1
2) Modal analysis: Gao et al. [6] proposed a method that to bus R of voltage ER through an equivalent reactance X as
computes the smallest Eigen value and associated shown in Fig.1.
eigenvectors of the reduced Jacobian matrix of the power From the equivalent system,
system based on the steady state system model. The Eigen
Es ER
values are associated with the modes of voltage and PR = sin δ (4)
X
reactive power variation. If all the Eigen values are
positive, the system is considered to be voltage stable. If E s E R cos δ−E 2R
one of the Eigen values is negative or zero, the system is QR = (5)
𝑋
considered to be voltage unstable. A zero Eigen value of the
reduced Jacobian matrix means that the system is on the Where PR, QR load connected to bus R
border of voltage instability. The corresponding system
Jacobian matrix becomes singular. The potential voltage ES is the infinite bus voltage and
collapse situation of a stable system can be predicted
X is equivalent reactance
through the evaluation of the minimum positive Eigen
values. The magnitude of minimum Eigen value provides a Take PR, QR equations for evaluating the Voltage margin,
measure to know how close the system is to voltage Put ER=V at maximum loading point (nose point).
collapse. By using the bus participation factor, the weakest
bus can be determined, which is the greatest contributing 𝑑𝑄 E s cos δ−2V
= =0
factor for a system to reach voltage collapse situation. The 𝑑𝑉 𝑋
reduced Jacobian matrix is as given below 𝐸𝑆
𝑉= cos 𝛿 (6)
2
Δ Q = JR Δ V
JR= [J4 - J3J1-1J2] (2) 𝑉2
𝑄= (7)
𝑋
Δ V= JR-1 Δ Q 𝑄
Bus participation factors: 𝑋= (8)
(4𝑄 2 +𝑃 2 )
JR= ξ Λ η
𝑄
𝑃𝑘𝑖 = 𝜉𝑘𝑖 ∗ 𝜂𝑖𝑘 (3) 𝑉𝐿 = (9)
(4𝑄 2 +𝑃 2 )
Where
JR = Reduced Jacobian matrix
Voltage Margin = ER - VL
K = bus number
Where VL is voltage at bus R at nose point
i = Eigen value number
ER is the present bus voltage
ξ = right Eigen vector matrix of JR
Λ = diagonal Eigen value matrix of JR 4) P-V and Q-V curves:
η = left Eigen vector matrix of JR The P-V curves are the commonly used graphs for
The most vulnerable bus K is that for which P ki is predicting voltage security. They are used to determine the
maximum. loading margin of a power system. The power system load
is gradually increased and, at each increment, it is necessary
3) The Proposed Method: In this study, Voltage margin to recomputed power flows until the nose of the PV curve
method is employed as indicator to solve the Voltage is reached. The margin between the voltage at collapse
stability problem. Where the Voltage margin is minimum point and the current operating voltage is used as voltage
that bus is considered as weak bus and the voltage margin stability criterion [7].
is a measure to know how close the system is to voltage
collapse. Voltage margin of a bus is computed using the
equivalent system representation at that bus.
Fig.2:
Fig.1: Equivalent system at Bus K PV curve of a load bus in the power system
The system external to bus R supplying a load of P R+jQR is With Q-V curve, it is possible for the operators, to know is
represented by an infinite bus of voltage E S<δS connected the conditional reactive power that can be supplied by the
2
weakest bus before reaching minimum voltage limit. The
reactive power margin is the MVAR distance from the
operating point to the bottom of the Q-V curve. The Q-V
curve can be used as an index for voltage instability. The
point where dQ/dV is zero is the point of voltage stability
limit [3].
3
Figure: 6 shows that bus 22 exhibits the highest Lj index, Table.2: Continuation load flow with shunt capacitor at
which indicates that it is the most vulnerable bus in the bus22
system. The L-index and the voltage at bus 22 (critical bus)
S.NO. Loading Voltage Power Eigen L-index Voltage
are plotted as a function of loading factor. factor K V(pu) PL(MW) values margin
0.14
0.12
0.1
0.08 4 1.3 0.7919 39 0.3671 0.2627 0.3447
0.06
0.04
0.02 5 1.5 0.7114 45 0.2982 0.4057 0.2642
0
18 19 20 21 22 23 24 25 26 27 28 29 30
Bus 6 1.6 0.6563 48 0.2442 0.5238 0.2090
0.016
0.014
0.012
definition given below: 0.01
𝑉2 0.008
𝑋𝑐 0.004
0.002
0
1
𝑋𝑐 =
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
𝜔𝑐
1
Capacitor 𝐶= (11) Fig.9: Voltage sensitivity curve
(2𝜋𝑓 𝑋𝑐 )
e) Contingency case:
1
0.9
0.8
PV curve with Stable operating systems can suffer voltage instability
shunt capacitor
0.7 under contingencies.
Voltage (pu)
PV curve
0.6 without shunt
0.5 capacitor
0.4 Fig.10. shows two cases where the system remains stable
0.3
0.2
and unstable after it suffers a contingency of generation trip
0.1 out and a line outage. When the load is 1.5 times the base
0
0 0.5 1 1.5 2
load, the system which is stable before contingency
Load factor K experiences voltage instability after the contingency. When
the load factor is 1.3. Voltage stability is maintained both
before and after contingency.
4
This shows that a voltage stable system under normal
conditions can become unstable under contingency
0.9 condition.
0.8 PV curve
PV curve with without
0.7
contingency contingency IV. SUPERIOURTY OF THE PROPOSED
0.6
METHOD
V (pu)
0.5
0.4
0.3
1. The Voltage margin computation at each bus is done
0.2 using the locally available signals V, P, Q at that bus
0.1
0
only. All the existing methods used to study voltage
0 0.5 1 1.5 2
stability require complete data of the network.
Loading factor K
2. The system operator can readily use this method to
evaluate the vulnerability of each bus for voltage
Fig.10: PV curves with & without Contingency
collapse using online data which is available to him.
Table.3: Continuation load flow at contingency case at 3. The voltage margin computed by this method will
Bus8 and line 15-23 provide the system operator with useful information
about how much load can be added to the bus before
S. Loading Voltag Power Eigen L-index Voltage
NO factor K e PL(M values margin the system suffers voltage instability.
V(pu) W)
4. Unlike other methods using the Eigen value of the
1 1 0.8160 30 0.3988 0.2254 0.3688
system Jacobian or the L-index which compares the
2 1.1 0.7855 33 0.3759 0.2436 0.3383 present bus voltage with the open circuit voltage to
3 1.2 0.7510 36 0.3486 0.3316 0.3038 arrive at the voltage stability index, the proposed
4 1.3 0.7109 39 0.3146 0.4067 0.2637
method gives the magnitude of the bus voltage at
which the system looses the voltage stability.
5 1.5 0.5921 45 0.1936 0.6888 0.1449
0.4
is identified as the weakest bus in the system. “Sensitivity
0.3
0.2
Index of Voltage margin to Reactive power injection”, is
0.1 calculated. The authors conclude that the proposed method
0 to calculate voltage margin is faster and more elegant.
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35
time (sec)
Fig.11: Time domain analysis for contingency cases The authors gratefully thank Dr.M.Ramamoorty,
Distinguished Professor, for his continuous guidance and
For this time domain analysis[10], the following involvement in the project. The first author is fortunate to
assumptions are made, work under him, who is an inspiring creative researcher par
excellence. We are with feelings from the bottom of hearts
1. All P and Q are kept constant at load bus. express our indebtedness. It is a rewarding experience and
2. Except slack bus, all other generators have we look forward in future also seeking his help and to share
blocked their governors. his ideas to sincerely try to implement. The first author is
3. All electrical transients are neglected. happy to record her sincere thanks for the encouragement
4. Generator bus voltages are held constant. and support extended by Dr.K.Anuradha, Head of the EEE
Department and Prof.C.D.Naidu, Principal of the Institute.
5
REFERENCES