Professional Documents
Culture Documents
Abstract—Salient pole synchronous generator is one of harmonic synchronous generator related to harmonic distortion level
sources that causes various power system harmonic problem produced by load. Parallel resonance contributed by network
especially related to neutral. This paper aims to study the capacitance in cable, inverter, and household with inductance
characteristics of third harmonic voltage and current from in transformer and cable has resulted higher voltage distortion.
generator when connected to balanced load via cable, generator While series resonance would cause higher current distortion
load connection with different generator neutral grounding when large number of power inverters are connected in the
resistor and generator load connection shunted by zig-zag system [3].
transformer. Lab scale experiments have been conducted to vary
all parameters related to cable capacitor and generator neutral Electrical parameters of the subsea cable such as cable
grounding resistor under various combined resistive and capacitance affect the frequency response characteristics for the
inductive load. Cable capacitance which depends on cable length, same length of different types of subsea cables, although its
size and number of parallel cable, combined with load impedance influence is not as large as the cable length [4]. The influence
determines the third harmonic current magnitude. The presence of subsea cable shunt capacitance on harmonic distortion due to
of cable capacitance that interact with generator inductance parallel resonance is investigated in detail by [5].
resulted to series harmonic resonance at 9th and 15th harmonic
order that causes high 9th and 15th harmonic current flowing Triplen harmonic current from synchronous generator
between generator and cable capacitor. Generator neutral return to its neutral via cable capacitance and has caused the
grounding resistor can effectively reduce the third harmonic in neutral grounding resistor to experience high temperature when
the phase and neutral. However care should be taken not to use connected to distribution grid [6]. Various transformer winding
very high generator neutral grounding resistor that can also configuration of distributed generation interconnection
restrict earth fault current that may pose problem to the transformer and neutral grounding reactor sizing have positive
sensitivity of earth fault protection system. Zig-zag transformer or negative impact on the triplen harmonic current [7]. Triplen
efficiently divert third harmonic current from generator to enter harmonic current is one of the causes contributed to neutral
the load but high circulating third harmonic current between grounding resistor failure apart from lightning, storms,
generator and zig-zag transformer may pose heating problem to earthquakes, extreme temperature changes, vibration etc. [8].
the equipments.
Simulation conducted by [9] has shown that zig-zag
Keywords-Third harmonic voltage; third harmonic current;
transformer is very effective to reduce triplen harmonic current
synchronous generator; cable capacitance; grounding from utility entering the load.
The objective of this paper is to study the influence of cable
I. INTRODUCTION capacitance, generator neutral grounding resistor and zig-zag
Harmonic becomes important when their presence in power transformer on third harmonic voltage and current produced by
system can cause problem to equipment functionality. Some of low voltage synchronous generator directly connected to
these problems related to harmonic voltage and the other to balanced load. In varying the parameters, lab experiment was
harmonic current or both. The advancement of electronic conducted and the methodology is described in section II. The
industry resulted in devices that are sensitive to the voltage and experimental results is presented and discussed in Section III.
current inputs. Finally the conclusion and recommendation is tabled in
section IV. The term generator will be used to represent salient
Generally, harmonic study does not go beyond
pole synchronous generator in the remaining text of this paper.
50th harmonic since above that level their existence is
negligible due to high impedance posed by the power system II. METHODOLOGY
network at that frequency. Third harmonic is the first harmonic
number of triplen harmonic which are 3rd, 9th, 15th, etc. series. The simulated results on the influence of cable length,
number of parallel cable, cable size and neutral grounding
Large round rotor synchronous generator in a thermal resistor size on the magnitude of third harmonic current have
power plant has been reported to produce harmonic even under been reported by [10]. Lab scale experiment are conducted in
no load condition [1]. Experiment carried out by [2] revealed three parts namely, generator directly connected to balanced
that under various load condition, voltage regulation of load via cable, generator directly connected to balanced load
Voltage (V)
Common neutral connection is made for generator with neutral 8
a' phase
grounding resistor and load. Combined resistive and inductive 6
loads are varied for every generator grounding resistor value. 4 b' phase
381
phase angle magnitude. Fig. 4 shows the third harmonic current
Third Harmonic Current magnitude at generator, cable capacitor and load terminals for
50 1.99μF cable capacitance.
40 The harmonic current spectrum when generator directly
Current(mA)
50 12
Voltage (V)
40 10
a' phase 8 a' phase
30
20 b' phase 6 b' phase
c' phase 4
10 c' phase
2
0 Neutral 0 Neutral
0.66uF 1.33uF 1.99uF 2.65uF 686+j120 686+j240 120+j960 686+j686 686+j1200
Load=686+j686 Cable capacitance=1.99uF
Capacitor terminal Generator terminal
10
Current(mA)
10
a' phase 8 a' phase
8
6 b' phase 6 b' phase
4 4
c' phase c' phase
2 2
0 Neutral 0 Neutral
0.66uF 1.33uF 1.99uF 2.65uF 686+j120 686+j240 120+j960 686+j686 686+j1200
Load=686+j686 Cable capacitance=1.99uF
Load terminal Capacitor terminal
Fig. 2. Third harmonic current at generator, cable capacitor and load terminals
for combined resistive and inductive load 686+j686
Third Harmonic Voltage
The combined resistive and inductive load is varied for 16
different fixed capacitance value in the second part of the 14
experiment. The third harmonic voltage magnitude at 12
Voltage (V)
382
Third Harmonic Current Harmonic Current Spectrum
60 60.00
50 50.00
Current(mA)
Current(mA)
40 40.00
30.00
30 a' phase
20.00 'a' phase
20 b' phase
10.00 'b' phase
10 c' phase
0.00 'c' phase
0 Neutral 0 3 6 9 12 15 18 21 24 27 30 33 36 39 42 45 48
686+j120 686+j240 120+j960 686+j686 686+j1200
Harmonic number
Cable capacitance=1.99uF Load=686+j686 Capacitance=0.66uF
Generator terminal Capacitor terminal
Fig. 5. Harmonic current spectrum for 9th and 15th harmonic resonance
Third Harmonic Current
80
70 B. Generator Neutral Grounding Resistor
60
Current(mA)
50
The generator neutral grounding resistor is varied for
40 a' phase various combined resistive and inductive load. The third
30 b' phase
harmonic voltage at generator terminal is almost constant for
20 all generator neutral grounding resistor values. However, at
10 c' phase
load terminal, the third harmonic voltage decrease as the
0 Neutral
neutral grounding resistor values increase as shown in Fig. 6
686+j120 686+j240 120+j960 686+j686 686+j1200
for combined resistive and inductive load of 686+j686 . This
Cable capacitance=1.99uF
Capacitor terminal
is due to voltage drop at neutral grounding resistor since the
third harmonic current is present in the neutral. The magnitude
reduction of third harmonic voltage is influenced by the
Third Harmonic Current neutral grounding resistance because the neutral third
harmonic current is small.
40
35
The phase and neutral third harmonic current at generator
30 and load terminals decrease as the neutral grounding resistor
Current(mA)
8.00
a' phase
6.00
Harmonic Current Spectrum 4.00 b' phase
Harmonic number
Load=686+j120 Capacitance=2.65uF
Capacitor terminal
383
times phase current magnitude. In Fig. 9, almost all third
Third harmonic voltage harmonic current for phase and neutral from generator flow
14.00 through zig-zag transformer and very small amount flow to the
12.00 load for all combined resistive and inductive load. This is
10.00 because zig-zag transformer provides the least impedance to
Voltage (V)
4.00
Voltage (V)
Fig. 6. Third harmonic voltage at generator and load terminals for combined
a' phase
resistive and inductive load 686+j686 3.00
b' phase
2.00
c' phase
1.00
Neutral
Third harmonic current 0.00
686+j686 686+j1200 686+j4800 4800+j686
18.00
16.00 Generator terminal
14.00
Current (mA)
12.00
10.00
a' phase
8.00 Third harmonic voltage
6.00 b' phase
4.00 6.00
c' phase
2.00
0.00 5.00
Neutral
0 80 120 240 480 960 4.00
Voltage (V)
a' phase
Neutral Grounding Resistor value (ohm) 3.00
Generator Terminal b' phase
2.00
c' phase
1.00
Neutral
Third harmonic current 0.00
686+j686 686+j1200 686+j4800 4800+j686
18.00
16.00 Zig-zag transformer terminal
14.00
Current (mA)
12.00
10.00
a' phase
8.00 Third harmonic voltage
6.00 b' phase
4.00 6.00
c' phase
2.00
5.00
0.00 Neutral
0 80 120 240 480 960 4.00
Voltage (V)
a' phase
Neutral Grounding Resistor value (ohm) 3.00
Load Terminal b' phase
2.00
c' phase
1.00
Fig. 7. Third harmonic current at generator and load terminals for combined Neutral
resistive and inductive load 686+j686 0.00
686+j686 686+j1200 686+j4800 4800+j686
Load Terminal
C. Generator Shunted by Zig-zag Transformer
The third harmonic voltage at generator, zig-zag Fig. 8. Third harmonic voltage at generator, zig-zag transformer and load
transformer and load terminals are quite constant for every terminals for combined resistive and inductive load
combined resistive and inductive load as shown in Fig. 8.
Higher load impedance phase angle magnitude yield higher
voltage magnitude at generator, zig-zag transformer and load
terminals.
Almost zero sequence in nature, the phase neutral current
sum at neutral hence resulting neutral current almost three
384
Generator neutral grounding resistor provides additional
Third harmonic current impedance in the neutral and their resultant impedance with
350.00 combined resistive and inductive load determines the
300.00 magnitude of third harmonic current. Practically, generator
250.00 neutral grounding resistor can be used to reduce third harmonic
Current (mA)
200.00
current from generator.
a' phase
150.00 b' phase Zig-zag transformer exhibits low impedance earth path for
100.00 c' phase third harmonic current to return to generator neutral. It diverts
50.00 the generator third harmonic current from flowing to the load
Neutral
0.00 but very high third harmonic current circulating between
686+j686 686+j1200 686+j4800 4800+j686 generator and zig-zag transformer. This may pose heating
problem to generator, zig-zag transformer and generator neutral
Generator terminal
grounding resistor.
ACKNOWLEDGMENT
Third harmonic current The authors would like to thank Universiti Teknologi
350.00 PETRONAS (UTP) in particular Research & Innovation Office
300.00 (RIO) in providing Short Term Internal Research Fund
250.00 (STIRF) for this study.
Current (mA)
8.00 electrical submersible pump systems", IEEE Trans. Ind. Appl., vol. 46,
no. 2, pp.575 -583 2010.
6.00
[5] X. Liang, W. M. Jackson, “Influence of Subsea Cables on Offshore
4.00 Power Distribution Systems”, IEEE Transactions On Industry
Applications, Vol. 45, No. 6, pp. 2136-2144 November/December 2009.
2.00
[6] M. F. Abdullah, N. H. Hamid, Z. Baharudin, M. F. I. Khamis, N. S. R.
0.00 Hashim, S. Yusof, “Investigation On High Neutral Earthing Resistor
686+j686 686+j1200 686+j4800 4800+j686 Temperature When Islanded Generator Connected To Utility Grid,” The
9th International Power and Energy Conference, Oct. 2010.
Load Terminal
[7] R. F. Arritt, R. C. Dugan, “Distributed generation interconncetion
transformer and grounding selection”, IEEE Power and Energy Society
Fig. 9. Third harmonic current at generator, zig-zag transformer and load General Meeting - Conversion and Delivery of Electrical Energy in the
terminals for combined resistive and inductive load 21st Century, USA, 2008.
[8] D. Selkirk, M. Savostianik, K. Crawford, “The Dangers of Grounding
IV. CONCLUSION Resistor Failure”, IEEE Industry Applications Magazine , Sept/Oct.
The cable capacitor provides the earth path for third 2010.
harmonic current to return to generator neutral. Since cable [9] H. L. Jou, J. C. Wu, K. D. Wu, W. J. Chiang, Y. H. Chen, “Analysis of
zig–zag transformer applying in the three-phase four-wire distribution
capacitance is in parallel connection with combined resistive power system,” IEEE Trans. Power Delivery, vol. 20, no. 2, pp.1168–
and inductive load, their net impedance decides the magnitude 1173, Apr. 2005.
of third harmonic current. The presence of cable capacitance [10] M. F. Abdullah, N. H. Hamid, Z. Baharudin and M. F. I. Khamis,
and generator inductance creates series resonance at 9th and 15th “Triplen Harmonics Currents Propagation Through Medium Voltage
harmonic number. In practice the cable capacitance value Distribution Network,” Fourth International Conference on Modeling,
represents cable length, size and number of cable in parallel. Simulation & Applied Optimization, April, 2011.
385