You are on page 1of 2

ENGLISH

INTRODUCTION INSTALLATION MAP


Symbols used in this Manual

INSTALLATION MANUAL AIR CONDITIONER This symbol alerts you to the risk of electric shock.

TYPE : WALL MOUNTED ! This symbol alerts you to hazards that may cause harm to the air conditioner.

! This symbol indicates special notes.


P/No : MFL67782105_v2 Installation plate
Sleeve
Bushing-Sleeve
• For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant. Putty(Gum Type Sealant)
TIPS FOR SAVING ENERGY - Using of (R22) piping, flare nut and tools may cause abnormally high pressure in the refrigerant
cycle (piping), and possibly result in explosion and injury.
Features Bend the pipe as closely
on the wall as possible,
Air filter but be careful that it
• It is desirable that the amount of residual oil less than 40 mg/10m.
Here are some tips that will help you minimize the power consumption when you use the air doesn't break.
Front Panel
conditioner. You can use your air conditioner more efficiently by referring to the instructions ON/OFF button
below:
Operation
• Do not share the outlet with other appliances.
• Do not cool excessively indoors. This may be harmful for your health and may consume more - It will cause an electric shock or a fire due to heat generation. Operation Vinyl tape (Wide)
lamp
electricity. • Do not use the damaged power cord. • Apply after carrying out a
- Otherwise, it may cause a fire or electrical shock. Signal Receiver drainage test.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• To carry out the drainage
• Keep doors or windows closed tightly while you are operating the air conditioner. • Do not modify or extend the power cord randomly. Ionizer test, remove the air filters
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air. - Otherwise, it may cause a fire or electrical shock. Saddle and pour water into the heat
• Speed up the fan to cool or warm indoor air quickly, in a short period of time. • Take care so that the power cord may not be pulled during operation. 3M Filter exchanger.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condition- - Otherwise, it may cause a fire or electrical shock.
Air outlet Air deflector
er is used for many hours. • Unplug the unit if strange sounds, smell, or smoke comes from it. (Vertical louver & Horizontal vane)
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the - Otherwise, it may cause electrical shock or a fire.
air flow or weaken the cooling / dehumidifying functions. • Keep the flames away.
- Otherwise, it may cause a fire. Gas side piping (Optional Parts)
Air inlet vents
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet Liquid side piping (Optional Parts)
hands. Additional drain pipe
- Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools. Vinyl tape (Narrow)
- Otherwise, it may cause a fire and electrical shock.
Air outlet vents Drain Hose
• Do not open the suction inlet of the indoor/outdoor unit during operation. Connecting cable
- Otherwise, it may electrical shock and failure. (Optional Parts)
For your records • Do not allow water to run into electrical parts. Copper tubing
- Otherwise, it may cause the failure of machine or electrical shock. Drain hose * The feature can be changed according to type of model.
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here: • Hold the plug by the head when taking it out.
- It may cause electric shock and damage. Connection wire
Model number : • Never touch the metal parts of the unit when removing the filter.
! NOTE
- They are sharp and may cause injury. Base plate • You should purchase the installation parts.
Serial number :
• Do not step on the indoor/outdoor unit and do not put anything on it.
You can find them on a label on the side of each unit. - It may cause an injury through dropping of the unit or falling down.
• Do not place a heavy object on the power cord. * The feataure can be changed according to type of model.
Dealer’s name :
- Otherwise, it may cause a fire or electrical shock.
Date of purchase :

IMPORTANT SAFETY INSTRUCTIONS INSTALLATION PARTS INSTALLATION


READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE. • When the product is submerged into water, always contact the service center. Select the best Location Outdoor unit
Name Quantity Shape
- Otherwise, it may cause a fire or electrical shock.
Always comply with the following precautions to avoid dangerous situations and ensure peak - There should not be any heat or steam near - Please do not place obstructions in front or
performance of your product. • Take care so that children may not step on the outdoor unit.
the unit. behind the unit as they may potentially inter-
- Otherwise, children may be seriously injured due to falling down.
- Select a place where there are no obstacles fere with the unit’s performance and operation.
! WARNING Installation plate 1 EA
around of the unit that could potentially inter- - If an awning is built over the unit to prevent
It can result in serious injury or death when the directions are ignored. ! CAUTION fere with the operation of the unit. direct sunlight or rain exposure, make sure that
The feature can be changed according to a type of model. heat radiation from the condenser is not
- Make sure that condensation drainage can
Installation be conveniently routed away. restricted.
! CAUTION Type "A" screw 5 EA
- Ensure that the space around the back and-
• Install the drain hose to ensure that drain can be securely done. - Do not install near a doorway.
It can result in minor injury or product damage when the directions are ignored. sides is more than 300mm. The space in front
- Otherwise, it may cause water leakage. - Ensure that the interval between a wall and
Type "B" screw 2 EA of the unit should be more than 700mm of
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the left (or right) of the unit is more than space. whilst still allowing adequate access
! WARNING the neighbors. 100mm. The unit should be installed as high above the unit for service repairs, as per speci-
• Installation or repairs made by unqualified persons can result in hazards to you and others. - Otherwise, it may cause dispute with the neighbors. as possible on the wall, allowing a minimum fications below.
Type "C" screw 2 EA of 200mm from ceiling.
• Air conditioner Shall be installed in accordance with national wiring regulations. • Always inspect gas leakage after the installation and repair of product. - Do not place animals and plants in the path of
- Otherwise, it may cause the failure of product. - Use a metal detector to locate studs to pre- the warm air.
• The information contained in the manual is intended for use by a qualified service technician familiar
vent unnecessary damage to the wall.
with safety procedures and equipped with the proper tools and test instruments. • Keep level parallel in installing the product. Remote control - Take the weight of the air conditioner into
- Otherwise, it may cause vibration or water leakage. 1 EA - The penetrating piping hole behind the unit
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunc- holder account and select a place where noise and
should not exceed manufactures recommen- vibration are minimum.
tion, property damage, personal injury and/or death.
dations and should be sealed well at time of
Operation installation, to prevent moisture, dust, ver- - Select a location, where the air and noise from
Installation Screws for fixing panels are attached to decoration panel. the air conditioning unit does not disturb neigh-
• Avoid excessive cooling and perform ventilation sometimes. min and any other foreign matter entering.
• Always perform grounding. - Otherwise, it may do harm to your health. bours and occupants.
- Otherwise, it may cause electrical shock.
• Don’t use a power cord, a plug or a loose socket which is damaged.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
- The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
INSTALLATION TOOLS More than
100 More than
Su
nro
More than 200 300 of
- Otherwise, it may cause a fire or electrical shock. • Do not use an appliance for special purposes such as preserving animals vegetables, precision ma- Figure Name Figure Name
• Installation of product must be carried out by a qualified and licence electrician and refrigeration me- chine, or art articles. More than 500
chanic, in accordance to all local AS/NZ Standards. - Otherwise, it may damage your properties.
- Otherwise, it may cause a fire, electrical shock, explosion or injury. • Do not place obstacles around the flow inlet or outlet. Screw driver Multi-meter More than Fe
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit. - Otherwise, it may cause the failure of appliance or an accident. 100 ob nce o
sta r More than
- If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not cle
s 300
attached securely, it could result in a fire or electric shock due to dust, water, etc. More than
Electric drill Hexagonal wrench (Unit : mm) 600
• Always install an air leakage breaker and a dedicated switching board.
More than
- No installation may cause a fire and electrical shock. 700 (Unit : mm)
• Do not keep or use flammable gases or combustibles near the air conditioner. * The feature can be changed according to
- Otherwise, it may cause a fire or the failure of product. Measuring tape, Knife Ammeter type of model.
- The unit should be installed on a flat, level,
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time. sturdy foundation to best absorb the normal
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly.
! CAUTION operating sound produced by the unit.
Hole core drill Gas-leak detector - To avoid, acceleration of corrosion and gen-
- It will cause a fire or electrical shock. Using only refrigeration copper tubing in eral ware and tear, affecting the condition of
• Do not install the product at a place that ther is concern of falling down. accordance to local Standards. the outdoor unit. It is highly recommended,
- Otherwise, it may result in personal injury. especially in corrosive environments. That a
Thermometer, reputable, recommended, transparent pro-
• Use caution when unpacking and installing. Spanner
Level
- Sharp edges may cause injury. tective coating/treatment is applied to the
entire outdoor unit at time of installation, fol-
• Thickness of copper pipes used are as shown “Flaring work” Table. lowed by scheduled ongoing preventative
- Never use copper pipes thinner than that in the table even when it is available on the market maintenance and ongoing treatment is
Torque wrench Flaring tool set
• Do not use kinked refrigeration copper tubing. applied as required, to continue upkeep of
- Otherwise, the expansion valve or capillary tube may become blocked with contaminants. product
Ø65 * The feature can be changed according to
Installation Plate type of model.
1 2 3

Indoor unit Unit Place a level on raised tab 3 Pull back the tubing holder. Bad case Indoor Outdoor Wrap the insulation material Connecting the Cables ! CAUTION
Outline A Type : 442 A Type : 442 4 Remove pipe port cover and positioning - Following bending case from right to left
Insulation around the connecting portion.
B Type : 434 B Type : 439 the tubing
Indoor Unit (More than 100~300mm
The power supply cables and field wiring
Fixing Installation Plate directly may cause damage to the tubing.
Drain hose length and 7mm thickness)
Extension 1 Overlap the connection pipe insulation Indoor unit
cables should be selected in accordance
drain hose
material and the indoor unit pipe insulation Connect the cable to the indoor unit by con- to local AS/NZS standards.
Left rear piping

The wall you select should be strong and solid Indoor unit back side view Tubing holder
enough to prevent vibration. material. Bind them together with vinyl necting the wires to the terminals on the con-
Ø65 tape so that there may be no gap.
Right rear piping

Ø65 trol board individually according to the outdoor


1 Before installation, confirm the position of Installation Plate unit connection. (Ensure that the color of the
a screw between chassis and Installation mm
A Type B Type Insulation material wires of the outdoor unit and the terminal No. ±3
10
Indoor Unit
plate. Drain hose
are the same as those of the indoor unit.)
175 A Type : 133 A Type : 95 217
B Type : 123 B Type : 170
(Unit : mm) Right Left
1 Insert the connecting cable through the
Downwards Backwards Connecting the installation pipe bottom side of indoor unit and connect the GN
/Y
and drain hose to the indoor unit. cable (You can see detail contents in 'Con- L
Flaring Work necting the cables' section) 20
1 Align the center of the pipes and sufficient- mm
Main cause for gas leakage is due to defect of * The feature can be changed according to a 2 Secure the cable onto the control board
type of model. ly tighten the flare nut by hand 2 Set the tubing cutting line upward.
flaring work. Carry out correct flaring work in with the cable retainer.
the following procedure. Wrap the area which accommodates the
rear piping housing section with vinyl tape. 3 Tape the tubing pipe, drain hose and the
connection cable. Be sure that the drain
hose is located at the lowest side of the
Cut the pipes and the cable Good case Cutting Line bundle. Locating at the upper side can The power and transmission cable between
A-Type
1 Use the piping kit accessory or the pipes - Press on the tubing cover and unfold the
Indoor unit tubing Flare nut Pipes
cause overflow from the drain pan through indoor and outdoor unit should be selected
B-Type purchased locally. tubing to downward slowly. And then bend the inside of the unit. in accordance to local AS/NZS standards.
to the left side slowly. 2 Tighten the flare nut with a wrench
2 Measure the distance between the indoor
and the outdoor unit. Outside Diameter Torque
2 Mount the installation plate on the wall 3 Cut the pipes a little longer than measured mm inch kgf·cm N·m
with type "A" screws. If mounting the unit distance. * The feature can be changed according to a Cutting Line
Gas Pipe Liquid Pipe
mm
on a concrete wall, use anchor bolts. type of model. Ø6.35 1/4 180~250 17.6~24.5
4 Cut the cable 1.5m longer than the pipe
Good Case Bad Case ±3
- Mount the installation plate horizontally length. Ø9.52 3/8 340~420 33.3~41.2 10
by aligning the centerline using Horizontal ! CAUTION Ø12.7 1/2 550~660 53.9~64.7 * Tubing cutting line have to be upward. View
meter . Ø15.88 5/8 630~820 61.7~80.4 Cover
Installation Information. For right piping.
Follow the instruction above. Connection pipe Indoor unit pipe GN
/Y
Open-end wrench Vinyl tape (wide) Wrap with vinyl tape
Terminal block L
Installation Plate (fixed) Remote controller 20
cable mm
Installation of Indoor Unit Connecting cable Connecting cable
Flare nut Cable retainer

1 Hook the indoor unit onto the upper por- Connection Pipe
Wrench
tion of the installation plate.( engage the pipe Vinyl tape(narrow)
Type "A" Screws three hooks at the top of the indoor unit Indoor unit tubing
with the upper edge of the installation
plate) Ensure that the hooks are properly 3 Bundle the piping and drain hose together
by wrapping them with vinyl tape sufficient
! CAUTION
seated on the installation plate by moving 3 When needed to extend the drain hose of
it left and right enough to cover where they fit into the - The circuit diagram is subject to change
indoor unit, assembly the drain pipe as rear piping housing section.
Chassis without notice.
Hook shown on the drawing
- The earth wire should be longer than the
Wrap with vinyl tape common wires.
3 Measure the wall and mark the centerline.
It is also important to use caution concern- - When installing, refer to the circuit
Drain pipe Pipe
ing the location of the installation plate. diagram on the chassis cover.
Routing of the wiring to power outlets is
- Connect the wires firmly so that they
through the walls typically. Drilling the hole
Indoor unit drain hose may not be pulled out easily.
through the wall for piping connections Vinyl tape(wide)
must be done safely. Installation plate - Connect the wires according to color
Adhesive Vinyl tape(narrow) Drain hose codes, referring to the wiring diagram.

Burrs removal <Right side piping> Outdoor unit Outdoor


2 Unlock the tubing holder from the chassis Outdoor unit ! CAUTION
Handle
"A"

and mount between the chassis and instal- 1 Remove the tubing cover from the unit by - Connect the wires to the terminals on the
1. Completely remove all burrs from the cut
Bar Bar lation plate in order to separate the bottom control board individually. According to the confirmation of the
cross section of pipe/tube. loosening the screw.
Yoke side of the indoor unit from the wall. above conditions, prepare the wiring as
2. While removing burrs put the end of the Liquid side piping - Secure the cable onto the control board with
follows.
copper tube/pipe in a downward direction Cone Tape (Smaller diameter) the cord clamp.
while removing burrs location is also Connecting 1 Never fail to have an individual power
- Use a recognized circuit breaker between
cable circuit specifically for the air condition-
changed in order to avoid dropping burrs Copper pipe the power source and the unit.
Drain hose er. As for the method of wiring, be
into the tubing. A disconnecting device to adequately discon-
Connecting pipe guided by the circuit diagram posted
Clamp handle Tubing cover nect all supply lines must be fitted.
Pipe Red arrow mark on the inside of control cover.
Tubing Holder 2 The screw which fasten the wiring in
Reamer * The feature can be changed according to
Grade(Based on Cooling Capacity) the casing of electrical fittings are
* The feature can be changed according to the type of model. Circuit
2.5~3.5kW liable to come loose from vibrations to
Check the type of model. Breaker(A) which the unit is subjected during the
Point down 15A
1 Compare the flared work with the figures course of transportation. Check them
given below. Piping ! CAUTION and make sure that they are all tightly
fastened. (If they are loose, it could
2 If a flared section is defective, cut it off If the extension drain hose is routed cause burn-out of the wires.)
and do flaring work again. 1 Insert the connecting cable through the inside the room, insulate the hose with an
bottom side of indoor unit and connect the insulation material* so that dripping from L N 1(L) 2(N) 3(C) 3 Specification of power source.
Putting nut on Smooth all round cable (You can see detail contents in sweating (condensation) could not dam- 4 Confirm that electrical capacity is suffi-
- Remove flare nuts attached to indoor and Inside is shiny without scratches 'Connecting the cables' section) age furniture or floors. Torque wrench cient.
Terminal block
outdoor units, then put them on the 2 Secure the cable onto the control board • Foamed polyethylene or equivalent is Over 5mm 5 See that the starting voltage is main-
pipe/tube which have completed its burr = Improper flaring = with the cable retainer. recommended. (0.2") Power cord Power connecting cable tained at more than 90 percent of the
removal. 3 Lift up the cover of terminal block slightly. rated voltage marked on the name
Gas side piping
(not possible to put them on after finishing plate.
4 Tape the tubing pipe, drain hose and the (Bigger diameter)
flare work) Flare nut 6 Confirm that the cable thickness is as
Inclined Surface Cracked Uneven connection cable. Be sure that the drain
damaged thickness
hose is located at the lowest side of the 2 Align the center of the pipings and specified in the power source specifi-
Even length
all round bundle. Locating at the upper side can sufficiently tighten the flare nut by hand. Outside Diameter Torque cation. (Particularly note the relation
cause overflow from the drain pan through between cable length and thickness.
Copper tube mm inch kgf·cm N·m
the inside of the unit. 7 Always install an earth leakage circuit
Ø6.35 1/4 180~250 17.6~24.5 breaker in a wet or moist area.
Connecting the Piping Ø9.52 3/8 340~420 33.3~41.2 Tubing cover
8 The following would be caused by
<Left side piping>
1 Open the panel of the indoor unit. Ø12.7 1/2 550~660 53.9~64.7 voltage drop.
2 Remove the chassis cover from the unit by Ø15.88 5/8 630~820 61.7~80.4 - Vibration of a magnetic switch, which
loosing 3 screws. ! CAUTION will damage the contact point, fuse
breaking, disturbance of the normal
Flaring work Provide the circuit breaker between function of the overload.
power source and the unit as shown by
Drain hose 9 The means for disconnection from a
1 Firmly hold copper pipe in a bar with the power supply shall be incorporated in
dimension shown in table below. 3 Finally, tighten the flare nut with torque
Tape wrench until the wrench clicks. the fixed wiring and have an air gap
2 Carry out flaring work with the flaring tool. - When tightening the flare nut with torque contact separation of at least 3mm in
Connecting
cable wrench, ensure the direction for tighten- Main power source each active(phase) conductors.
Outside diameter A Thickness Drain hose ing follows the arrow on the wrench. 10 Open the terminal cover block
mm inch mm mm Connecting pipe before connecting the indoor side
wire.
Ø6.35 1/4" 1.1~1.3 0.7 Air Circuit Breaker
Conditioner
Ø9.52 3/8" 1.5~1.7 0.8 ! NOTE Use a circuit breake
or time delay fuse.
Ø12.7 1/2" 1.6~1.8 0.8
Insert the drain hose at left side when
Ø15.88 5/8" 1.6~1.8 1.0 you use left side piping type.

Chassis cover

4 5 6 7
Installation of DRED Module Checking the Drainage In cases where the outdoor unit is installed
above the Indoor unit perform the following.
Air purging with vacuum pump Finishing the Job - Replace the valve caps at both gas and liquid
side service valves and fasten them tight.
3 Remove the WLAN Port Cap. ! NOTE
1 Remove the cover control from the unit by This completes air purging with a vacuum pump.
loosening the screw. Connect the wires to To check the drainage. 1 Tape the piping and connecting cable from - Preparation • When Dry Contact Mode is operated,
- With a service valve wrench, turn the valve of - Replace the pipe cover to the outdoor unit by
the terminals on the control board individu- 1 Pour a glass of water on the evaporator. down to up. Check that each tube(both liquid and gas liquid side counter-clockwise to fully open the WLAN Function can not be used.
ally as the following. side tubes) between the indoor and outdoor one screw
2 Ensure the water flows through the drain 2 Secure the taped piping along the exterior valve Now the air conditioner is ready for test run. • In WLAN mode when you want to change to a dry
2 Connecting cable between outdoor unit wall. Form a trap to prevent water entering units have been properly connected and all
hose of the indoor unit without any leakage - Turn the valve of gas side counter clockwise to contact mode, normal operation after 3 minutes.
and DRED(Demand Response Enabling the room. wiring for the test run has been completed. * The feature can be changed according to the
and goes out the drain exit. fully open the valve
Device) Shall be double insulation layer. Remove the service valve caps from both type of model.
3 Fix the piping onto the wall using saddle or the gas and the liquid side on the outdoor - Loosen the charge hose connected to the gas
3 Connect the connecting cable to DRED equivalent unit. Note that both the liquid and the gas side service port slightly to release the pressure,
according to the diagram below. side service valves on the outdoor unit are then remove the hose. Test Running
(Select one of the two ways) kept closed at this stage. Settlement of outdoor unit
Connecting area Seal a small opening - Replace the flare nut and its bonnet on the gas
drain hose - Check that all tubing and wiring are properly connected.
around the pipings - Leak test side service port and fasten the flare nut secure-
DRED with gum type sealant. Connect the manifold valve(with pressure ly with an adjustable wrench. This process is * The feature can be changed according to a - Check that the gas and liquid side service
very important to prevent leakage from the sys- - Fix the outdoor unit with a bolt and
Leakage
gauges) and dry nitrogen gas cylinder to this type of model. valves are fully open.
LAN 3 2 1 C L N 1(L) 2(N) 3 checking
tem. nut(ø10mm) tightly and horizontally on a con-
service port with charge hoses. crete or rigid mount.
Drain pan
BR BL - When installing on the wall, roof or rooftop, Prepare remote controller
Trap
! CAUTION Indoor unit anchor the mounting base securely with a 4 Equipped with a WLAN module.
Insert batteries before using the remote con-
Drain
nail or wire assuming the influence of wind
hose Be sure to use a manifold valve for air and earthquake. trol. The battery type used is AAA (1.5 V).
Leakage
checking
purging. If it is not available, use a stop - If the vibration of the unit is transmitted to 1 Remove the battery cover by pulling it ac-
valve for this purpose. The knob of the the pipe, secure the unit with an anti-vibra- cording to the arrow direction.
Clamper 3-way valve must always be kept close. tion rubber.
- Pressurize the system to maximum
Remote Agent Trap 250 P.S.I.G. (17.6 kgf/cm2G) (R-22
model) or 400 P.S.I.G. (28.1 kgf/cm2G) Bolt
(R-410A model) with dry nitrogen gas
and close the cylinder valve when the
or
gauge reading reaches 250 P.S.I.G. (17.6
kgf/cm2G) (R-22 model) or 400 P.S.I.G. 2 Insert new batteries making sure that the
DRED
Air Purging (28.1 kgf/cm2G) (R-410A model). Next Outdoor unit
(+) and (–) of battery are installed correctly.
The air and moisture remaining in the refriger- step is leak test with liquid soap.
LAN 3 2 1 C L N 1(L) 2(N) 3 Manifold valve * The feature can be changed according to a
ant system have undesirable effects as indi-
cated below. type of model.
Pressure Tubing connection
BR BL

* The feature can be changed according to


- Pressure in the system rises. ! CAUTION gauge Lo Hi

the type of model. - Operating current rises.


To avoid nitrogen entering the refrigerant
- Cooling(or heating) efficiency drops. 5 Close the front panel.
system in a liquid state, the top of the Open Close - Lift down both sides of the panel sloghtly 3 Reattach the cover by pushing it back into posi-
- Moisture in the refrigerant circuit may freeze cylinder must be higher than its bottom tion.
and block capillary tubing. when you pressurize the system. Usually,
Clamper
- Water may lead to corrosion of parts in the the cylinder is used in a vertical standing
refrigeration system. position.
! NOTE
Remote Agent
Therefore, after evacuating the system, take a
leak test for the piping and tubing between • Use 2 AAA(1.5volt) batteries. Do not use

h Make use of the wires connected with O-ring.


the indoor and outdoor unit. ! WARNING Vacuum pump rechargeable batteries.
• Remove the batteries from the remote con-
There is a risk of fire and explosion.
4 Secure the cable onto the control board Inert gas (nitrogen) should be used troller if the system is not used for a long time.
with the holder (clamper). when you check plumbing leaks, cleaning * The feature can be changed according to a
or repairs of pipes etc. type of model.
5 Refix the cover control to the original posi-
tion with the screw. If you are using combustible gases
including oxygen, product may have the
risk of fires and explosions.

Drain piping Forming the Piping - Do a leak test of all joints of the tubing(both Evacuation Evaluation of the performance Pump down Installation requirements that In case of installing the outdoor unit on the
indoor and outdoor) and both gas and liquid sea side, setup a windbreak to prevent sea
1 The drain hose should point downward for Form the piping by wrapping the connecting side service valves. This is performed when the unit is relocated
need apply for corrosive envi- wind.
easy drain flow. portion of the indoor unit with insulation Bubbles indicate a leak. Be sure to wipe off - Connect the charge hose end described in Operate the unit for 15~20 minutes, then
material and secure it with two kinds of vinyl the soap with a clean cloth. the preceding steps to the vacuum pump to check the system refrigerant charge:
or the refrigerant circuit is serviced. ronments
Pump Down means collecting all refrigerant
tapes. evacuate the tubing and indoor unit.
Downward slope
- After the system is found to be free of leaks,
Confirm the "Lo" knob of the pressure Gauge
- Measure the pressure of the gas side service into the outdoor unit without the loss of refrig- ! CAUTION Windbreak
- If you want to connect an additional drain relieve the nitrogen pressure by loosening valve. erant.
hose, the end of the drain outlet should be the charge hose connector at the nitrogen is open. Then, run the vacuum pump. - Do not install the product in areas where
The operation time for evacuation varies with - Measure the air temperature from inlet and
routed above the ground. Secure the drain cylinder. When the system pressure is outlet of air conditiioner. corrosive chemicals and gases are pro-
hose appropriately. reduced to normal, disconnect the hose from tubing length and capacity of the pump. The ! CAUTION duced.
the cylinder. following table shows the time required for - Ensure the difference between the inlet and Sea wind
Pipe Be sure to perform Pump Down proce- - Do not install the Air Conditioning unit in
Drain hose
Evacuation. outlet temperature is more than 8°C.
dure in the cooling mode. areas exposed to direct sea winds (salty
Vinyl tape(narrow) - For reference; the gas side pressure at opti- winds). Which may lead to corrosion.
Manifold valve mum condition is shown on table (cooling) Corrosion, particularly on the condenser
Indoor unit
Pressure
2 Do not make drain piping like the gauge The air conditioner is now ready to use. and evaporator fins, could cause product
Lo Hi
Pump Down Procedure malfunction or inefficient performance.
following.
Liquid side
Wrap with - If in the event that the outdoor unit is
Inlet temperature - Connect a low-pressure gauge manifold hose
vinyl tape(wide) Charge hose installed or exposed to sea winds and that
to the charge port on the gas side service
Do not raise valve. alike. Additional measures, such as those - It should be strong enough like concrete to
Nitrogen gas Discharge air indicated below must apply. prevent the sea wind from the sea. Such
2-way valve - Open the gas side service valve halfway and
cylinder(in vertical
(Close) Gas side purge the air in the manifold hose using the construction should be strong, safe and
standing position)
refrigerant. durable to withstand sea winds and environ-
Additional measures that need mental conditions.
Water
Cap - Close the liquid side service valve(all the
Outdoor unit
way). apply - The height and width should be more than
leakage In cases where the outdoor unit is installed 150% of the outdoor unit.
below the indoor unit perform the following. Discharge - Turn on the unit's operating switch and start If the outdoor unit is to be installed close to
Accumulated *The feature can be changed according a type the cooling operation. - Keep more than 70 cm of space between
1 Tape the piping, drain hose and connecting 3-way valve temperature the seaside, then direct exposure to the sea
drain water of model. (Close) outdoor unit and the windbreak for easy air
cable from down to up. - When the low-pressure gauge reading wind should be avoided.
Air flow.
2 Secure the tapped piping along the exteri- becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 Install the outdoor unit on the opposite side of
or wall using saddle or equivalent. Required time for Evacuation when 30 gal/h Outside The pressure of P.S.I.G.), fully close the gas side valve and the sea wind direction.
Soap water method vacuum pump is used Refrigerant ambient the gas then quickly turn off the unit. Now Pump - Select a well-drained place.
Water Down procedure is completed, and all refrig- Ensure that a reputable, recommended,
Waving Seal small openings If tubing length is TEMP. side service valve.
leakage If tubing length is erant is collected into the outdoor unit. transparent protective coating/treatment is
around pipings with a - Remove the caps from the 2-way and 3-way longer than 10m applied to the entire outdoor unit at time of
less than 10m (33 ft)
gum type sealant. valves. (33 ft) installation, followed by scheduled ongoing
- Remove the service-port cap from the 3-way 10 min. or more 15 min. or more 8.5~9.5kg/cm2G Sea wind preventative maintenance and ongoing treat-
Tip of drain hose R-410A 35°C (95°F) Installation of WLAN Module ment is applied as required, to continue
valve. (120~135 P.S.I.G.)
dipped in water Connecting cable
- Apply a soap water or a liquid neutral deter- - When the desired vacuum is reached, close
(Optional Accessory) upkeep of product.
Saddle Pipings gent on the indoor unit connection or out- the knob of the 3-way valve and stop the 1 Turn off the power and unplug the power - For any concerns, additional advise or
Water door unit connections by a soft brush to vacuum pump. *The feature can be changed according a type of cord.
check for leakage of the connecting points of recommendations please contact LG
leakage Ditch model. 2 Open the front cover. Electronics
the piping.
- Lift up both sides of the cover slightly. - Periodic ( more than once/year ) cleaning
Taping - If bubbles come out, the pipes have leakage
of the dust or salt particles stuck on the
Less than
50mm gap
Drain hose
! NOTE heat exchanger by using water
* Do not use seawater when you clean up
If the actual pressure is higher than
Sea wind the heat exchanger.
shown, the system is most likely over-
charged, and charge should be removed.
If the actual pressure are lower than
* The feature can be changed according to shown, the system is most likely under-
type of model. charged, and charge should be added.

Trap is required to prevent water


* The feature can be changed according to a
from entering into electrical parts.
type of model.

8 9 10 11

- Note (Memo) -

Piping Length and Elevation


Pipe Size
Standard Max. Max. Additional
Capacity
GAS LIQUID Length Length Elevation Refrigerant
(kW) A (m) B (m)
(m) (g/m)
mm inch mm inch
2.5kW/
Ø9.52 3/8 Ø6.35 1/4 7.5 20 10 20
3.5kW

Indoor unit
Outdoor unit

A
A

B Outdoor unit Indoor unit


B

! CAUTION
• Capacity is based on standard length and maximum allowable length is on the basis of reli-
ability.
• Additional refrigerant must be charged after 12.5m.

Operation ranges
The table below indicates the temperature ranges the air conditioner can be Operated within.

Mode Indoor temperature Outdoor temperature


Cooling 18°C ~ 30°C -10°C ~ 48°C
Heating 16°C ~ 30°C -15°C ~ 24°C

12 13 14 15

You might also like