WATER SUPPLY AND DISTRIBUTION - BACKFLOW, PLUMBX

PREVENTION DEVICES, ASSEMBLIES, AND METHODS


SPILL-PROOF PRESSURE-TYPE VACUUM BREAKER

152 mm - above all downstream piping


and flood rim of the receptor

Closes the vent prior to the check


opening

can be used indoors


Presentation by Group 2 of BSCE-2F
WATER SUPPLY AND DISTRIBUTION - BACKFLOW, PLUMBX

PREVENTION DEVICES, ASSEMBLIES, AND METHODS

Presentation by Group 2 of BSCE-2F


GENERAL REQUIREMENTS
LOGO HERE

Backflow prevention assembly must be tested


by a certified backflow assembly tester at the
time of installation
1.52 m- Installations elevated more than 1.52 m
above floor shall have permanent platform for
testers and maintenance person
2 pipe diameters or minimum 25 mm- air gap
from supply outlet to top surface of the
drainage
152mm- installation of atmospheric vacuum
breaker above flood level rim
43.3°C- minimum temperature for a backflow
prevention for hot water to operate
Presentation by Group 2 of BSCE-2F
PLUMBX
SPECIFIC REQUIREMENTS

152 mm- height of critical level above the


overflow rim of the water closet or the
highest part of a urinal

Vacuum Breakers of a water closet and


urinal flushometer valves shall be at the
discharge side of the flushometer valve 25 mm- height of ballcock above full opening
of overflow pipe
Presentation by Group 2 of BSCE-2F
PLUMBX
SPECIFIC REQUIREMENTS

152 mm- height of AVB of potable water


outlets with hose attachments above the
highest point of usage located on the
discharge side of the last valve Lawn sprinkling systems must have AVB
Presentation by Group 2 of BSCE-2F
PLUMBX MATERIALS

Cast Iron pipes


CPVC- may be used for hot and cold-water
distribution within a building
Up to 51 mm- cast iron fittings shall be galvanized
All small-sized malleable iron water fittings shall be
Malleable Cast Iron fittings galvanized.
8%- maximum lead content in water pipes and
fittings
Presentation by Group 2 of BSCE-2F
PLUMBX VALVES

Up to 51 mm- shall be brass


Over 51 mm- may be cast iron or brass
body
Each gate valve shall be fullway type

Fullway Gate Valve shall be installed on:


the discharge side of each water meter and on each unmetered water supply if the valve
controls all outlets
the discharge piping from water supply tanks
cold water supply pipe to each water heater
each apartment or dwelling occupied by more than 1 family
if controlling two or more openings
Presentation by Group 2 of BSCE-2F
PLUMBX VALVES

Control gate valve shall be installed in a water


supply line ahead of any automatic metering
valve which supplies a battery of fixtures.

Presentation by Group 2 of BSCE-2F


PLUMBX VALVES

Basket Strainer
Y-Strainer
- ideal for liquid applications
designed to protect
requiring high-flow capacity.
downstream from particles
- could hold more particles
that are not frequently
because of its larger size of
present in the applicaiton.
filtering part.

Presentation by Group 2 of BSCE-2F


GRAVITY SUPPLY TANKS
LOGO HERE

Gravity tanks shall be covered with return-


bend vent pipe not less than area of down-
feed riser
Screen must have 14-18 mesh per 25 mm
Float valve in a tank
Float valve must control the potable water
inlets to gravity tanks, or controlled by float
switch or electrode-type water level control

Gravity tanks shall be provided with a valved


drain pipe and overflow pipe
Cable float switch

Presentation by Group 2 of BSCE-2F


WATER PRESSURE PLUMBX

103 kpa- Minimum water supply pressure


that should be reached, otherwise, an
elevated tank or booster pump must be
installed
551 kpa- if the pressure is in excess of 551
kpa- pressure regulator preceded by an
adequately sized strainer shall be installed
1033 kpa- maximum pressure setting of
pressure relief valve
80%- all pipe size determinations shall be
based on 80% of the reduced pressure

Presentation by Group 2 of BSCE-2F