Created On:05-Apr-2023 02:43 AM Page 1 of 2

Cable Size
Report
Project name: as
Calculation name: ash

Cable: Multi-core / Thermoplastic (70 °C) / Copper Solid/Stranded / Armoured

Installation: C Clipped direct

N
O
Load: 100 A Power factor: 0.85

SI
Supply: 3 phase 400 V Fault level: 3 kA

Length of run: 50 m

Cable Size Results Current-carrying Capacity: PASS


R
Active cable: 1 x 25 mm² , 3/4C Current rating of circuit-derated: 102 A
Neutral cable: 1 x 25 mm² , 3/4C Spare current-carrying capacity of circuit: 2A
VE

Earth cable (copper): 1 x 16 mm² , 1C Overall derating factor: 1.00


Dictating factor for active size: Current Conductor operating temperature: 68.45 °C

Fault Loop Impedance: Voltage Drop: PASS


Total loop, Zs: 0.0925 Ω Voltage drop: 6.76 V
L

Source, Zext: 0.0185 Ω Voltage drop: 1.69 %


Cables, Zint: 0.0740 Ω Permissible voltage drop: 5%
IA

Maximum allowed, Zdevice: - Maximum length of run: 148 m


Touch voltage: 102.21 V
TR

Short-circuit Performance: PASS


Three Ph. Short-cct: 2872.2 A
Min. active size to withstand short-circuit: 7.83 mm²
Active-to-earth short-circuit current: 1455.5 A
Min. earth size to withstand short-circuit: 3.23 mm²

Protective Device: Unknown


Rating: - Duration of Short-circuit: 0.1 s
Thermal setting: - Earth fault time: -
Trip current: - RCD: -

Cable Pro Web © 2023 Electrotechnik Pty Ltd


Version 4.5.0.0 www.elek.com.au
Created On:05-Apr-2023 02:43 AM Page 2 of 2

References
Standards: British Standard BS 7671:2018

Tabulated current rating of cable: 102 A


Table name: 4D4A
Column No. 3

Conductor impedances used in voltage drop calculations


Resistance Reactance
Phase conductor: 1.5 Ω/km Phase conductor: 0.145 Ω/km
Table name: 4D4B Table name: 4D4B

N
Column No. : 4 Column No. : 4

O
SI
R
VE
L
IA
TR

Cable Pro Web © 2023 Electrotechnik Pty Ltd


Version 4.5.0.0 www.elek.com.au

You might also like