Professional Documents
Culture Documents
b. Isolate power
a) Safety shoes and rubber gloves, b) Observing safety barriers, c) Notification of non-participating personnel in the shop of a
high voltage test in progress.
2. Have you had experience in the use of electrical standards such as NEC, NEMA, ANSI, etc?
NEMA: National Electrical Manufacturers Association.
IEEE: Institute of Electrical and Electronics Engineers
IEC : International Electro-technical Commission.
ANSI: American National Standards Institute
API: American Petroleum Institute
NFPA: National Fire Protection Association.
3. What are some of the instances when you may have used these standards?
At electrical testing and mechanical inspection of electrical equipment.
4. Are you familiar with the NEMA classes of insulation for motors and ANSI for transformers?
Electrical insulation systems are rated by standard NEMA (National Electrical Manufacturers Association) classifications according to
maximum allowable operating temperature:
o
C o
F o
C o
C
A 105 221 60 70
B 130 266 80 90
T(oF) = [T(oC)](9/5) + 32
Re: Transformer insulation class
http://www.electricalengineeringtoolbox.com/2014/08/nema-insulation-classes-for-transformers.html
the class number = the maximum °C of the transformer insulation
NEMA (National Manufacturer’s Association) has the following thermal or insulation classification as regards transformers (dry type):
Dry type transformer temperature rise is a specification for how hot the windings of a transformer will get when at full load.
This is the rise above a 40C ambient and with an additional allowance for an internal hot spot of 30C.
The insulation class is the actual temperature rating of the winding insulation.
The combination of the ambient + hot spot + rise should not exceed the insulation class.
Using the standard dry type temperature rises and maximum temperature per insulation class:
Class B insulation = 150C-(40C+30C)= 80C rise
Class F insulation = 185C-(40C+30C)= 115C rise
Class H insulation = 220C-(40C+30C)= 150C rise
It is very common to find a transformer built with a high insulation class and still be designed for a low temperature rise.
For example an H-80 transformer would have class H insulation but still be designed with an 80C rise, which is commonly achieved by
designing the transformer to have fewer losses and therefore less heat generation.
658124811.doc Page 2 of 10
Inspector Qualification
6. What is a hi—pot test and what are you trying to prove with this test?
658124811.doc Page 3 of 10
Inspector Qualification
ELECTRICAL - CABLE
1. What would you consider to be the basic purchase order information you would need to proceed with a cable
inspection assignment?
Answer: a) Size of the cable
b) Voltage rating
c) Quantity
2. When the quantity being purchased is not sufficient, according to the standards, to require complete testing, what
should the Inspector do?
Answer:
Witness the tests which are being conducted on this order and examine the vendors records of the latest complete tests
performed on this type cable.
3. What is some of the information the Inspector can find in the appropriate standards?
Answer: a) Conductor diameters, areas, resistance, stranding
Dimensional properties of conductors, insulations, sheath
b) Insulation thickness
c) Shielding, jacketing
d) Length of test samples
e) Electrical, Physical and aging requirements
2. What are the functions of the main and the auxiliary busses?
Answer: The main bus carries the load or primary power.
The auxiliary bus furnishes control power.
658124811.doc Page 4 of 10
Inspector Qualification
4. Name some of the components you would expect to find in a switchgear assembly.
Answer: Circuit breakers, starters, meters, relays, busses, terminal blocks, heaters.
A switchgear has two types of components:
Power conducting components, such as switches, circuit breakers, fuses, and lightning arrestors, that conduct or
interrupt the flow of electrical power
Control systems such as control panels, current transformers, potential transformers, protective relays, and
associated circuitry, that monitor, control, and protect the power conducting components
Switchgear From Wikipedia, the free encyclopedia
High voltage switchgear - A section of a large switchgear panel, in this case, used to control on-board casino boat power generation. –
Tram switchgear … This circuit breaker uses both SF6 and air as insulation.
In an electric power system, switchgear is the combination of electrical disconnect switches, fuses or circuit breakers used to
control, protect and isolate electrical equipment.
Switchgears are used both to de-energize equipment to allow work to be done and to clear faults downstream.
5. Describe the standard method for hi—pot testing the primary bus in a three—phase switchgear assembly.
Answer:
Ground phases 1 and 3, then apply high potential to phase 2.
If successful, reverse the procedure.
658124811.doc Page 5 of 10
Inspector Qualification
ELECTRICAL — MOTORS
1. How is a synchronous motor different from a squirrel cage induction motor?
Answer: It has a wound rotor.
Synchronous motor Rotor winding is fed with a DC supply with the help of slip rings.
In squirrel cage rotor, the rotor bars are permanently short-circuited with end rings.
In wound rotor, windings are also permanently short-circuited, hence no slip rings are required.
Synchronous motors require additional starting mechanism to initially rotate the rotor near to the synchronous speed.
No starting mechanism is required in induction motors.
The power factor of a synchronous motor can be adjusted to lagging, unity or leading by varying the excitation,
whereas, an induction motor always runs at lagging power factor.
Synchronous motors are generally more efficient than induction motors.
Synchronous motors are costlier.
Induction motors:
RPM = 60 x f / 2p; f = frequency in Hz; 2p = Double poles
Example: f = 50, 4 poles. RPM = 60 x 50 / 2 = 1500
9. When visually inspecting a motor, what would you consider to be the most critical dimensions?
Answer:
Shaft diameter, extension and height, bolt hole locations, terminal box location.
10. When a hand cranked megger is used to check most three—phase induction motors, how many tests are required?
Why?
Answer:
One. The motor windings are connected internally so a test on one lead checks the entire winding.
11. Describe how the winding resistance would be checked on a three—phase motor.
Answer:
A resistance measurement would be taken between leads A and B, then B and C, then C and A.
The three readings should be identical.
658124811.doc Page 7 of 10
Inspector Qualification
ELECTRICAL — TRANSFORMERS
1. What is the principal function of a power transformer?
Answer: Transform alternating current by induction from primary circuits to secondary circuits usually with changed values of
voltage and current.
5. Why are most power transformers equipped with tap changer mechanisms?
Answer: To cope with voltage drop in a distribution system by using the mechanism to change the turn ratio in the transformer.
Current-voltage reactors also reduced the voltage disturbances on the rest of the system.
It is installed in feeders and ties, in generators leads, and between bus sections, for reducing the magnitude of short circuit currents and the
effect of the respective voltage disturbance
658124811.doc Page 8 of 10
Inspector Qualification
INSPECTOR (QUALIFICATION)
1. What would you Consider to be the basic parts of a high voltage power cable?
Insulation properties.
2. What descriptive information does the NEC require to be marked on all conductors and cable?
a) Rating voltage
b) Manufacture name
c) AWG size
IN ALTRO - IN OTHER
a) N° of conductors
b) Rating Voltage
c) Length ikn???
CHECK
3. The direct-current voltage test will be applied for how many minutes for shielded cable?
Answer:
a) 5 minutes
b) 10 minutes
c) 15 minutes
d) 20 minutes
a) 5 min
b) (controllare se 10 min) – SU ALTRO 10min – CHECK
B) (check if 10 min) - ON OVER 10min - CHECK
I TEST CHE IO HO ESEGUITO SUI CAVI SECONDO IEC RICIEDEVANO UN TEMPO DI 5 MINUTI. RITENGO QUINDI CHE a) SIA PIU’ USATO.
PERO’ IN ALCUNI CASI DURA ANCHE 10 min. DIPENDE DAL TEST
THE TESTS I TAKEN ON THE CABLES UNDER IEC RECEIVED A TIME OF 5 MINUTES. HOWEVER THAT (a) IS MORE USED.
PERO 'IN EVERY CASE DURING EVEN 10 min. DEFECTS FROM TEST
4. The alternating-current voltage test will be applied for how many minutes? (For shielded cable?)?
Answer: a) 5 minutes
b) 10 minutes
c) 15 minutes
d) 20 minutes
a) 5 min
MA ANCHE 10
BUT ALSO 10
a) 5 minutes
O anche 10, dipende dal test
Or even 10, it depends on the test
5. TRUE OR FALSE:
The direct-current spark test is applicable to single-conductor cable and assemblies of insulated single-conductor cables
without insulation shield, metallic sheath, or metallic armour.?
FALSE (True-ikn)
Will be performed to test the insulation continuity
NOTA: QUESTA DOMANDA E LA NR. 77) DICONO ESATTAMENTE UNA IL CONTRARIO DELL’ALTRA. LA RISPOSTA CORRETTA È TRUE
NOTE: THIS QUESTION AND NO. 77) EXACTLY SEND A CONTRARY OF THE OTHER. THE CORRECT RESULT IS TRUE
FALSE,,ikn??, it is applicable on insulated single conductor to check the continuity insulation.
Risposta corretta TRUE - TRUE correct answer
IN ALTRO - IN OTHER
658124811.doc Page 9 of 10
Inspector Qualification
7. In accordance with the NEC, conductors and cables shall be durably marked on the surface at intervals not exceeding how
many inches?
Answer: a) 18 inches
b) 24 inches
c) 36 inches
d) 48 inches
24 inches
SU ALTRO 36 E U ALTRO ANCORA 48- check ALWAYS MORE THAN 36 AND ALWAYS 48- CHECK
NON HO TROVATO NULLA SU QUESTO I did not find any one on this
Levent Gökay-Prysmian: İsmail Bey sayfa 70-136 madde B de belirtiliyor. Ama şıklarda yer almıyor. Kuvvetle ihtimal doğru cevap d olmalı.
8. TRUE OR FALSE: Metal-covered multi-conductor cables shall employ a marker tape located within the cable and running
for its complete length, in lieu of cable surface marking.?
True
9. In accordance with the NEC which of the following colours would be permitted for an equipment grounding conductor.?
Answer:
a) Black
b) Green with a Yellow Stripe
c) White
d) Natural Grey
e) Green
B, Green with yellow stripes
http://www.ecmweb.com/qampa/stumped-code-nec-requirements-identifying-circuit-conductors-and-more
Insulated equipment grounding conductors size 6 AWG and smaller must have a continuous outer finish either green or green with one or more yellow stripes,
in conformance with 250.119 [210.5(B)].
On equipment grounding conductors 4 AWG and larger, insulation can be permanently reidentified with green marking at the time of installation at every
point where the conductor is accessible [250.119(A)].
Ungrounded conductors must be identified as follows [210.5(C)]:
658124811.doc Page 10 of 10