Professional Documents
Culture Documents
RAIPUR
Prepared by
Dr. R. Manivannan
Faculty In-charge of PDC Lab
Associate Professor
Chemical Engineering
EXPERIMENT NO 1
AIM
To determine the flow coefficient CV of the equal percentage control valve / quick opening valve /
linear control valve.
SETUP REQUIRED
Control valve, pump, piping, ball valve, pneumatic compressor
EXPERIMENTAL PROCEDURE
3. Open the Control Valve fully. As the Control Valve is Air to close so pressure in diaphragm should
be 0 psig.
4. Adjust the Rotameter for 500 LPH flow by regulating the valve provided at the inlet line of the
Control Valve and wait for 5 minutes to steady the flow.
7. Increase the pressure slowly and record the Manometer & Rotameter reading up to 15 Psi.
8. Conduct the experiment for Linear Control Valve. As the Linear Control Valve is Air to Open, so
pressure in diaphragm should be more than 15 psig. Adjust this pressure in diaphragm by operating
the Pressure Regulator. Do not exceed this pressure more than 20 psig.
OBSERVATION:
CALCULATIONS
𝐺
𝐶𝑣 = 1.16𝑄√∆𝑃 = -----------------
RESULTS
Flow coefficient CV of the equal percentage control valve was determined to be ……………….
Flow coefficient CV of the linear control valve was determined to be …………………..............
Flow coefficient CV of the quick opening control valve was determined to be ………………….
EXPERIMENT NO 2
AIM
To study the inherent characteristics of equal percentage control valve / quick opening valve / linear
control valve.
SETUP REQUIRED
Control valve, pump, piping, ball valve, pneumatic compressor
EXPERIMENTAL PROCEDURE
1. Start the setup for Linear Control Valve.
3. Open the Control Valve fully. As the Control Valve is air to close so the pressure in the diaphragm
should be 15 psig.
4. Adjust the Rotameter for 500 LPH flow by regulating the valve provided at the inlet line of the
Control Valve.
8. Now slowly decrease the air pressure by the regulator so that the stem travel towards the closing
position becomes 2mm.
9. The pressure drop across the valve will increase. Throttle the regulatory valve at the inlet of the
control valve to maintain a pressure drop constant
10. Again note down the reading of rotameter and stem travel.
11. Repeat the procedure and take the readings at each 2mm stem travel till the valve is fully closed
(Pressure upto 0 psig).
12. Plot the graph of valve coefficient versus lift to show inherent characteristics of the control valve.
13. Conduct the same procedure for other to valves too. As the Linear Control Valve is Air to Open,
so Pressure in diaphragm should be 0 psig. Repeat the experimental procedure same as above, but
pressure in the diaphragm will be increased gradually.
OBSERVATION
Stem lift in mm 14 12 10 8 6 4 2 0
Q, LPH
ΔP, mm H2O
CALCULATIONS
𝐺
𝐶𝑣 = 1.16𝑄√∆𝑃 = -----------------
RESULTS
• The inherent characteristics of linear control valve was studied
• The inherent characteristics of equal percentage control valve was studied
• The inherent characteristics of quick opening valve was studied
• Valve coefficient versus lift is plotted to show the inherent characteristic of the control valve.
EXPERIMENT NO 3
AIM
To study the installed characteristics of equal percentage control valve, quick opening valve, linear
control valve.
SETUP REQUIRED
Control valve, pump, piping, ball valve, pneumatic compressor
EXPERIMENTAL PROCEDURE
3. Open the Control Valve fully. As the Control Valve is air to close so pressure in diaphragm should
be 0 psig.
4. Adjust the Rotameter for 500 LPH flow by regulating the valve provided at the inlet line of the
Control Valve.
8. Now slowly decrease the air pressure by regulator so that the stem travel towards the closing
position becomes 2mm.
9. Wait for 5 minutes to steady the flow and note down the reading of Rotameter, Manometer and
stem travel
10. Repeat the procedure and take the readings at each 2m stem travel till the valve is fully closed
(Pressure upto 15 psig)
11. Plot the graph of valve coefficient versus lift to show installed characteristic of the control valve.
13. Conduct the experiment for other two valves. As the Linear Control Valve is Air to Open, so
Pressure in diaphragm should be 0 psig. Repeat the experimental procedure same as above, but
pressure in the diaphragm will be increased gradually.
OBSERVATION
Stem lift in mm 14 12 10 8 6 4 2 0
Q, LPH
ΔP, mm H2O
CALCULATIONS
𝐺
𝐶𝑣 = 1.16𝑄√∆𝑃 = -----------------
RESULTS
• The installed characteristics of linear control valve was studied
• The installed characteristics of equal percentage control valve was studied
• The installed characteristics of quick opening valve was studied
• Flow versus lift was plotted to show the inherent characteristic of the control valve.
EXPERIMENT NO 4
SETUP REQUIRED
Control valve, pump, piping, ball valve, pneumatic compressor
EXPERIMENTAL PROCEDURE
3. Open the Control Valve fully. As the Control Valve is air to close so pressure in diaphragm should
be 0 psig.
4. Adjust the Rotameter for 500 LPH flow by regulating the valve provided at the inlet line of the
Control Valve.
9. Wait for 5 minutes to steady the flow and note down the reading of Rotameter, Manometer and
pressure in psig.
10. Repeat the procedure and take the readings at +3 psig till the valve is fully closed (Pressure upto
15 psig).
11. Now increase the pressure upto 20 psig and start decreasing the pressure gradually upto 15 psig.
14. Repeat the procedure and take the readings at -3 psig till the valve is fully opened (Pressure upto
0 psig).
15. Calculate valve flow coefficient for actuator pressure for every reading.
16. Plot the graph of actuator pressure versus flow coefficient. The ratio of maximum difference
between flow coefficients at same actuator pressure to that of maximum flow coefficient is termed
as hysteresis.
Repeat the experiment for other two valves. As the Control Valve is air to open so keep in mind
this parameter during conducting the experiment.
OBSERVATION
CALCULATIONS
𝐺
𝐶𝑣 = 1.16𝑄√∆𝑃 = -----------------
RESULTS
Actuator pressure versus flow coefficient is plotted for all the three valves.
EXPERIMENT NO 5
STUDY OF RANGEABILITY
AIM
SETUP REQUIRED
Control valve, pump, piping, ball valve, pneumatic compressor
EXPERIMENTAL PROCEDURE
4. Note down the flow rate and pressure at inlet of control valve.
6. Note down the flow rate and pressure at inlet of control valve.
7. Repeat the experiment by keeping constant pressure drop across the control valve and note the
flow rates.
OBSERVATION
Pressure ΔP F Cv Remarks
(psig) mm of H2O LPH
Nearly 3 max
Nearly 15 min
CALCULATIONS
𝐶𝑣 𝑚𝑎𝑥
𝑅=
𝐶𝑣 𝑚𝑖𝑛
𝐹𝑚𝑎𝑥
𝑅=
𝐹𝑚𝑖𝑛
For equal % valve flow has an exponential characteristics of rangeability, F = Rm-1. R is the rangeability
of the valve and m is its fractional stem position.
RESULTS
EXPERIMENT NO 6
AIM
To study the step response of mercury manometer and water manometer
SETUP REQUIRED
Needle valve, U-tube manometer, Compressor
EXPERIMENTAL PROCEDURE
1) Mercury Manometer:
3. Adjust the needle valve and vent to raise the mercury level to 200mm from zero level.
4. Note the mercury level reading and quickly open the vent to apply the step change and record
the videograph. Note the top peak and bottom peak readings and also simultaneously note the
period of oscillation from the videograph.
2) Water Manometer:
3. Adjust the needle valve and vent to deflect the water column to 450mm from zero level.
4. Note the mercury level reading and quickly open the vent to apply the step change and record
the videograph. Note the top peak and bottom peak readings and also simultaneously note the
period of oscillation from the videograph.
TABULATION OF OBSERVATION
Mercury Manometer:
ConstantS
Manometer fluid = Mercury
Dynamic viscosity 𝜇 = 0.0016 kg/ms
Mass density 𝜌 = 13550 kg/m3
Column length L = 0.760 m
Tube diameter D = 0.005 m
Step change (mm):
Period of oscillation (sec):
SN Actual response* Period of oscillation (sec)
(mm)
1
2
3
*: Note peak values observed during oscillations.
Water Manometer:
ConstantS
Manometer fluid = water
Dynamic viscosity 𝜇 = 0.001 kg/ms
Mass density 𝜌 = 998 kg/m3
Column length L = 1.050 m
Tube diameter D = 0.022 m
Step change (mm):
Period of oscillation (sec):
SN Actual response* Period of oscillation (sec)
(mm)
1
2
3
*: Note peak values observed during oscillations.
CALCULATIONS
8. Theoretical response for different time values is calculated using the below equation
√1−𝜁 2 𝜁 √1−𝜁 2
𝑦(𝑡) = 𝐾𝑀 × {𝑒 −𝜁𝑡/𝜏 [cos ( 𝑡) + sin ( 𝑡)]}
𝜏 √1−𝜁 2 𝜏
RESULTS
EXPERIMENT NO. 7
AIM
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
OBSERVATION
Output Output
observed observed
Sr.
Type of sensor at at
No
Ambient 90°C
Temperature temperature
1 RTD Ω Ω
2 Thermistor KΩ KΩ
3 Thermocouple mV mV
RESULTS
• The RTD type temperature sensor shows resistance in................. Ω, which increases
with rise in temperature.
• The Thermistor type sensor shows resistance in .....................KΩ, which decreases with
rise in temperature.
• The thermocouple type sensor gives out put in ....................millivolts, which increases
with rise in temperature.
EXPERIMENT NO. 8
CHARACTERISTICS OF RTD
AIM
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
OBSERVATION
40
50
60
70
80
90
100
GRAPHS
RESULTS
EXPERIMENT NO. 9
CHARACTERISTICS OF THERMISTOR
AIM
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
OBSERVATION
20
30
40
50
60
70
80
90
100
GRAPHS
RESULTS
The resistance of thermistor in KΩ decreases gradually with the Temperature °C of the sensor.
EXPERIMENT NO. 10
CHARACTERISTICS OF THERMOCOUPLE
AIM
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
1. Two thermocouples (junctions) are connected and one of the thermocouples (Junctions) is kept in
ice bath to maintain constant reference junction. (Note: The connection/joint of two positive arms
of the thermocouples does not form a junction as the metals are same)
2. Arrange the experiment and keep both thermocouples
(junctions) and mercury thermometer in ice bath. Note the output voltage with digital multimeter.
Record the observations in following table.
3. Transfer one of the thermocouples (junctions) and mercury thermometer to hot water bath filled
with ice-cold water. Gradually increase the temperature of the hot water bath. Record the
observations at the interval of 10°C in the observation table. (Note: Wait for steady state for each
observation).
OBSERVATION
90
100
GRAPHS
RESULTS
EXPERIMENT NO. 11
AIM
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
OBSERVATION
• Connect the RTD PT-100 probe to the transmitter and ensure that transmitter output is correct
in the calibration range.
RESULTS
• The temperature transmitter is studied and calibrated.
EXPERIMENT NO. 12
AIM
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
1. Two thermocouples (junctions) are connected and one of the thermocouples (Junctions) is kept in
air to maintain constant reference junction. (Note: The connection/joint of two positive arms of the
thermocouples does not form a junction as the metals are same)
2. Connect the output of thermocouples given for study of Seebeck effect to digital milliVoltmeter.
Switch on digital milliVoltmeter.
3. Keep one of the thermocouple probes in air (at ambient temperature) and other in hot water bath
with thermometer.
4. Adjust the temperature of hot water bath to different temperatures shown in observation table by
switching the heater On and Off. Note the thermometer reading and corresponding milliVolts
generated for each temperature.
OBSERVATION
30
40
50
60
70
80
90
100
RESULTS
EXPERIMENT NO. 13
AIM
To determine the time constant of mercury in glass thermometer
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
OBSERVATION
GRAPH:
CALCULATIONS
• Mark the temperature of 63.2% of step change value on the graph.
• Note the time required for 63.2% step change. This is the time constant of thermometer. (63.2%
of step change value = 0.632 x (final temp – initial temp) + initial temp.)
RESULTS
EXPERIMENT NO.14
AIM
To determine the time constant of bimetal thermometer
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
OBSERVATION
GRAPH
CALCULATIONS
• Mark the temperature of 63.2% of step change value on the graph.
• Note the time required for 63.2% step change. This is the time constant of bimetal
thermometer. (63.2% of step change value = 0.632 x (final temp – initial temp) + initial temp.)
RESULTS
EXPERIMENT NO. 15
AIM
To determine the time constant of RTD sensor
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
TABULATION OF OBSERVATION
CALCULATIONS
• Mark the temperature of 63.2% of step change value on the graph.
• Note the time required for 63.2% step change. This is the time constant of RTD. (63.2% of
step change value = 0.632 x (final resistance – initial resistance) + initial resistance)
RESULTS
EXPERIMENT NO. 16
AIM
To determine the time constant of thermistor sensor
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
TABULATION OF OBSERVATION
CALCULATIONS
• Mark the temperature of 63.2% of step change value on the graph.
• Note the time required for 63.2% step change is the time constant of thermistor.
• 63.2% of step change value = 0.632 x (final thermistor reading – initial thermistor reading) +
initial thermistor reading)
GRAPHS
RESULTS
EXPERIMENT NO. 17
AIM
To determine the time constant of thermocouple sensor
SETUP REQUIRED
Temperature measurement setup
EXPERIMENTAL PROCEDURE
GRAPHS
CALCULATIONS
• Mark the temperature of 63.2% of step change value on the graph.
• Note the time required for 63.2% step change is the time constant of thermocouple
• 63.2% of step change value = 0.632 x (final temperature reading – initial temperature reading)
+ initial temperature reading
RESULTS
EXPERIMENT NO 18
AIM
SETUP REQUIRED
Interacting and Non-Interacting systems, electrical supply: 230 +/- 10 VAC, 50 Hz, single phase
electric supply with proper earthing. (Neutral-Earth voltage less than 5 VAC) 5A with three pin socket
with switch, water supply (Initial Fill)
EXPERIMENTAL PROCEDURE
2. A flexible pipe is provided at the Rotameter outlet. Insert the pipe in to the cover of the top Tank
1. Keep the outlet valves (R1 & R2) of the Tank 1 & Tank 2 slightly closed
3. Switch on the pump. Adjust Rotameter flow rates in steps of 10 LPH from 50 to 100 LPH and note
steady state levels for Tank 1 against each flow rate
4. From the data obtained select a suitable band for experimentation. (Say 90-100 LPH in which we
are getting more readings of tank level)
5. Adjust the flow rate at lower value of the band selected (say 90 LPH) and allow the level of the
Tank 1 to reach the steady state and record the flow and level at steady state
7. Immediately start recording the level of the Tank 1 at the interval of 15 sec, until the level reaches
at steady state
8. Carry out the calculations as mentioned in calculation part and compare the predicted and observed
values of the tank level
TABULATION OF OBSERVATIONS
Diameter of tank mm ID 92 mm
1 0
2 15
3 30
4 --
CALCULATIONS
Where
Where dH is change in level (Final steady state level - Initial steady state level) and dQ is change
flow (Final flow rate after step change - Initial flow rate)
Plot the graph of H(t) Vs time for observed and predicted levels
RESULTS
1 The step response of single capacity system was studied and a graph was plotted between time
vs. H (both observed and predicted).
2 It was observed that the theoretical value (predicted) of height matches with the experimental
values (observed).
EXPERIMENT NO 19
AIM
To obtain experimentally the step response of first order systems in non-interacting mode
SETUP REQUIRED
Interacting and Non-Interacting systems, electrical supply: 230 +/- 10 VAC, 50 Hz, single phase
electric supply with proper earthing. (Neutral-Earth voltage less than 5 VAC) 5A with three pin socket
with switch, water supply (Initial Fill)
EXPERIMENTAL PROCEDURE
2. A flexible pipe is provided at the Rotameter outlet. Insert the pipe in to the cover of the top Tank
1. Keep the outlet valves (R1 & R2) of both Tank 1 & Tank 2 slightly closed. Ensure that the
valve (R3) between Tank 2 and Tank 3 is fully closed
3. Switch on the pump and adjust the flow to @ 90 LPH. Allow the level of both the tanks (Tank 1
& tank 2) to reach at steady state and record the initial flow and steady state levels of both tanks
4. Apply the step change with increasing the Rotameter flow by @ 10 LPH
5. Record the level of Tank 2 at the interval of 30 sec, until the level reaches at steady state
7. Carry out the calculations as mentioned in calculation part and compare the predicted and
observed values of the tank level
OBSERVATIONS
1 0
2 30
3 60
CALCULATIONS
1 −t 1 −t
H 2 ( t )Pr edicted = A R 2 1 − 1 2 e 1 − e 2 .................(1)
1 − 2 2 1
Where
1 = A1 x R1
2 = A2 x R2
where 1 is time constant of tank 1, A1 is area of tank 1 and R1 is resistance of outlet valve of tank 1.
2 is time constant of tank 2, A2 is area of tank 2 and R2 is resistance of outlet valve of tank 2
R1 = dH1 /dQ
R2 = dH2 /dQ
where dH1 is change in level of tank 1 and dQ is change flow of from initial to final state and dH2 is
change in level of tank 2 at initial and final state.
Put the values in equation (1) to find out H2(t)Predicted and plot the graph of H2(t)Predicted and H2(t)Observed
vs time.
RESULTS
1 The step response of two first order systems arranged in non-interacting mode is studied and a
graph is plotted between time vs. H (both observed and predicted).
2 It is observed that the theoretical value (predicted) of height matches with the experimental
values (observed).
EXPERIMENT NO 20
AIM
To obtain experimentally the impulse response of first order systems in non-interacting mode
SETUP REQUIRED
Interacting and Non-Interacting systems, electrical supply: 230 +/- 10 VAC, 50 Hz, single phase
electric supply with proper earthing. (Neutral-Earth voltage less than 5 VAC) 5A with three pin socket
with switch, water supply (Initial Fill)
EXPERIMENTAL PROCEDURE
2. A flexible pipe is provided at the Rotameter outlet. Insert the pipe in to the cover of the top tank
(T1). Keep the outlet valves (R1 & R2) of both Tank 1 & Tank 2 slightly closed. Ensure that the
valve (R3) between two bottom tanks T2 and T3 is fully closed
3. Switch on the pump and adjust the flow to @ 90 LPH. Allow the level of both Tank 1 and Tank 2,
to reach the steady state and record the initial flow and steady state levels of both tanks.
5. Record the level of the Tank 2 at the interval of 30 sec, until the level reaches to steady state
7. Carry out the calculations as mentioned in calculation part and compare the predicted and observed
values of the tank level
OBSERVATIONS
1 0
2 30
3 60
4 --
CALCULATIONS
−t −t
e − e 2
1
H 2 ( t )Pr edicted = VR2 ..................(1)
1 − 2
(For 1, 2 and R2 refer values obtained in the step response experiment)
Put the values in above equation to find out H2(t)Predicted and plot the graph of H2(t)Predicted and
H2(t)Observed vs time.
RESULTS
1 The impulse response of two first order systems arranged in non-interacting mode was studied
and a graph was plotted between time vs. H (both observed and predicted).
2 It was observed that the theoretical value (predicted) of height matches with the experimental
values (observed).
EXPERIMENT NO 21
AIM
SETUP REQUIRED
Interacting and Non-Interacting systems, electrical supply: 230 +/- 10 VAC, 50 Hz, single phase
electric supply with proper earthing. (Neutral-Earth voltage less than 5 VAC) 5A with three pin socket
with switch, water supply (Initial Fill)
EXPERIMENTAL PROCEDURE
2. A flexible pipe is provided at the rotameter outlet. Insert the pipe in to the cover of the Tank 3.
Keep the outlet valve (R2) of Tank 2 slightly closed. Ensure that the valve (R3) between Tank 2
and Tank 3 is also slightly closed.
3. Switch on the pump and adjust the flow to @ 90 LPH. Allow the level of both Tank 2 and Tank
3, to reach the steady state and record the initial flow and steady state levels of both tanks
4. Apply the step change with increasing the Rotameter flow by @ 10 LPH
5. Record the level of the Tank 2 at the interval of 30 sec, until the level reaches at steady state
7. Carry out the calculations as mentioned in calculation part and compare the predicted and
observed values of the tank level
OBSERVATIONS
Diameter of tanks ID 92 mm
1 0
2 30
3 60
4 --
CALCULATIONS
1 1
exp( t ) − exp( t )
..............(1)
H 2 (t ) Predicted = AR2 1 −
1 1
−
Where
Where 2 is time constant of tank 2, A2 is area of tank 2 and R2 is resistance of outlet valve of tank 2
3 is time constant of tank 3, A3 is area of tank 3 and R3 is resistance of outlet valve of tank 3.
1 1 A3 R2
b= + + .................................................(2)
2 3 2 3
−b b 2 1
= + − ...................................(3)
2 2 2 3
−b b 2 1
= − − ...................................(4)
2 2 2 3
Considering non linear resistance at outlet valve of both tanks, it can calculated as
Where dH is change in tank height for change in flow dQ. Calculate the values of b, and from
equations 2-4.
Substitute the values in equation (1) to find out H2(t)Predicted and plot the graph of H2(t)Predicted and
H2(t)Observed vs time
RESULTS
1 The step response of two first order systems arranged in interacting mode is studied and a graph
is plotted between time vs. H (both observed and predicted).
2 It is observed that the theoretical value (predicted) of height matches with the experimental
values (observed).
EXPERIMENT NO 22
AIM
SETUP REQUIRED
Interacting and Non-Interacting systems, electrical supply: 230 +/- 10 VAC, 50 Hz, single phase
electric supply with proper earthing. (Neutral-Earth voltage less than 5 VAC) 5A with three pin socket
with switch, water supply (Initial Fill)
EXPERIMENTAL PROCEDURE
1. Start up the set up
2. A flexible pipe is provided at the Rotameter outlet. Insert the pipe in to the cover of Tank 3. Keep
the outlet valve (R2) of Tank 2 slightly closed. Ensure that the valve (R3) between both Tank 2 and
Tank 3 is slightly closed
3. Switch on the pump and adjust the flow to @ 90 LPH. Allow the level of both the tanks to reach
at steady state and record the initial flow and steady state levels.
4. Apply impulse input by adding 0.5 lit of water in Tank 3
5. Record the level of the Tank 2 at the interval of 30 sec, until the level reaches to steady state
6. Record final steady state level of Tank 3
7. Carry out the calculations as mentioned in calculation part and compare the predicted and observed
values of the tank level
OBSERVATIONS
Diameter of tankS ID 92mm
1 0
2 30
3 60
4 --
CALCULATIONS
H2(t)observed = (Level at time t - level at time 0) x 10 -3
H 2 ( t )Predicted =
VR2
2 3 ( − )
( e( t ) − e( t ) ) ...............................................(7)
Put the values in above equation to find out H2(t)Predicted and plot the graph of H2(t)Predicted and H2(t)
Observed vs time.
RESULTS
1 The impulse response of two first order systems arranged in interacting mode was studied and
a graph was plotted between time vs. H (both observed and predicted).
2 It was observed that the theoretical value (predicted) of height matches with the experimental
values (observed).
EXPERIMENT NO 23
AIM
To study the characteristics of flapper nozzle system and to determine the gain of flapper nozzle
system.
SETUP REQUIRED
EXPERIMENTAL PROCEDURE
1. Adjust the air supply to 20 psig by air regulator.
2. Increase the gap between flapper and nozzle to get 3 psi signal pressure and note the dial reading.
3. Decrease the gap between flapper and nozzle by gap adjusting screw. Note the dial gauge reading
for each psi change in signal pressure. Ensure that supply pressure is maintained at 20 psi.
4. Repeat the set of observation by increasing the gap.
OBSERVATIONS
Increasing:
10 90
11 100
Decreasing:
CALCULATIONS
𝑐ℎ𝑎𝑛𝑔𝑒 𝑖𝑛 𝑠𝑖𝑔𝑛𝑎𝑙 𝑝𝑟𝑒𝑠𝑠𝑢𝑟𝑒
𝐺𝑎𝑖𝑛 𝑜𝑓 𝑓𝑙𝑎𝑝𝑝𝑒𝑟 𝑛𝑜𝑧𝑧𝑙𝑒 𝑠𝑦𝑠𝑡𝑒𝑚 = 𝑝𝑠𝑖/𝑚𝑚
𝑐𝑜𝑟𝑟𝑒𝑠𝑝𝑜𝑛𝑑𝑖𝑛𝑔 𝑐ℎ𝑎𝑛𝑔𝑒 𝑖𝑛 𝑛𝑜𝑧𝑧𝑙𝑒 𝑔𝑎𝑝
(Note: Plot the graph of signal pressure (y) verses nozzle gap (x) and calculate the slope)
RESULTS
EXPERIMENT NO 24
AIM
To study the linearity of I/P converter.
SETUP REQUIRED
I/P converter setup
EXPERIMENTAL PROCEDURE
1. Start up the set up.
2. Put digital calibrator in source mode.
3. Give current input in the step of 4 mA from 4 to 20 mA by slowly rotating the knob of digital
calibrator.
4. Note down corresponding pressure on output pressure gauge in psig.
5. Tabulate above readings in the observation table given below.
OBSERVATIONS
S. No. Input current Standard Output Pressure Actual Output Pressure
(mA) (psig) (psig)
1 4 3
2 8 6
3 12 9
4 16 12
5 20 15
CALCULATIONS
• Linearity: Linearity of I/P converter is 5% maximum of output span between 3 to 15 psig (as stated
by manufacturer). Therefore 5/100 * (15-3) = 0.6 psig. This is the maximum deviation in the
output.
• Plot graph of Input current (mA) on X axis and output pressure (psig) on Y-axis. Draw a straight
line that best fits all the points.
• The graph shows the straight line.
• Observe the maximum deviation in output and compare with specified by manufacturer.
RESULTS
• Some deviation in actual linearity of I/P converter from manufacturer’s specification was observed,
as it depends upon accuracy of pressure gauges used, accuracy of digital calibrator and visual error
in recording the readings.
EXPERIMENT NO 25
AIM
To study the hysteresis of I/P converter.
SETUP REQUIRED
I/P converter setup
EXPERIMENTAL PROCEDURE
1. Start up the set up.
2. Put digital calibrator in source mode.
3. Give current input in the step 4 mA from 4 to 20 mA by slowly rotating the adjust knob on digital
calibrator.
4. Note down corresponding output pressure on output pressure gauge in psig.
5. Now note the output pressure in psig by applying input current in decreasing mode from 20 mA to
4 mA.
6. Tabulate above readings in the observation table given below.
OBSERVATIONS
S. No. Input Output S. No. Input Output Hysteresis
current pressure current pressure (psig)
(mA) (psig) (X) (mA) (psig) (Y) (Y) – (X)
1 4 1 4
2 8 2 8
3 12 3 12
4 16 4 16
5 20 5 20
CALCULATIONS
• Hysteresis of I/P converter is 0.5 psig typical (as stated by manufacturer). Calculate hysteresis by
using formula:
• Hysteresis =Output at decreasing Input – Output at increasing input.
• Plot the graph showing hysteresis as input (increasing and decreasing) on X axis and corresponding
output on Y-axis.
RESULTS
• Some deviation in hysteresis of I/P converter was observed as it depends upon accuracy of pressure
gauges used accuracy of digital calibrator and visual error in recording the readings.
EXPERIMENT NO 26
AIM
To study the accuracy of I/P converter.
SETUP REQUIRED
I/P converter setup
EXPERIMENTAL PROCEDURE
1. Start up the set up as mentioned in commissioning part above.
2. Now put digital calibrator in source mode.
3. Give current input in the step of 4 mA from 4 to 20 mA by slowly rotating the knob of digital
calibrator.
4. Note down corresponding pressure on output pressure gauge in psig.
OBSERVATIONS
S. No. Input current Standard Output Actual Output Deviation (psig)
(mA) Pressure (psig) (X) Pressure (psig) (Y) (Y) – (X)
1 4 3
2 8 6
3 12 9
4 16 12
5 20 15
CALCULATIONS
Uncertainty error (%) = ((Y-X)/X) ͯ 100
Calculate average uncertainty error
Accuracy (%) = 100 – average uncertainty error (%)
RESULTS
• Accuracy of I/P converter was found to be ……………………………
EXPERIMENT NO 27
AIM
To study the repeatability of I/P converter.
SETUP REQUIRED
I/P converter setup
EXPERIMENTAL PROCEDURE
1. Start up the set up.
2. Now put digital calibrator on source mode.
3. Give current input in the step 4 mA from 4 to 20 mA by slowly rotating the adjust knob on digital
calibrator.
4. Note down corresponding output pressure on output pressure gauge in psig.
5. Now repeat the above steps for more trials.
6. Tabulate above readings in the observation table given below.
OBSERVATIONS
S. No Input current Output pressure S. No. Input current Output pressure
(mA) (psig) (X) (mA) (psig) (Y)
Trial 1 Trial 2
1 4 1 4
2 8 2 8
3 12 3 12
4 16 4 16
5 20 5 20
Trial 3 Trial 4
1 4 1 4
2 8 2 8
3 12 3 12
4 16 4 16
5 20 5 20
CALCULATIONS
Repeatability: Note down the values of output for same input in repeated trials. Repeatability can be
found out in % of each reading.
RESULTS
Repeatability of I/P converter was found to be ……………………………
EXPERIMENT NO 28
AIM
To study the linearity of P/I converter.
SETUP REQUIRED
P/I converter setup
EXPERIMENTAL PROCEDURE
1. Start up the set up.
2. Put digital calibrator in measure mode.
3. Give pressure input in the step of 3 psig from 3 to 15 psig by slowly rotating the air regulator.
4. Note down corresponding current output on digital calibrator in mA.
5. Tabulate above readings in the observation table given below.
OBSERVATIONS
S. No. Input Pressure (psig) Standard Output current Actual Output current
(mA) (mA)
1 3 4
2 6 8
3 9 12
4 12 16
5 15 20
CALCULATIONS
• Plot graph of Input pressure (psig) on X axis and output current (mA) on Y-axis. Draw a straight
line that best fits all the points. The graph shows the straight line.
• Observe the maximum deviation in output and compare with specified by manufacturer.
RESULTS
• Some deviation in actual linearity of P/I converter from manufacturer’s specification was observed,
as it depends upon accuracy of pressure gauges used, accuracy of digital calibrator and visual error
in recording the readings.
EXPERIMENT NO 29
AIM
To study the hysteresis of P/I converter.
SETUP REQUIRED
P/I converter setup
EXPERIMENTAL PROCEDURE
1. Start up the set up.
2. Put digital calibrator on measure mode.
3. Give pressure input in the step of 3 psig from 3 to 15 psig by slowly rotating the air regulator.
4. Note down corresponding current output on digital calibrator in mA.
5. Now note the output current in mA by applying input pressure in decreasing mode from 15 psig to
3 psig.
6. Tabulate above readings in the observation table given below.
OBSERVATIONS
S. No. Input Output S. No. Input Output Hysteresis
pressure current pressure current (psig)
(psig) (mA) (X) (psig) (mA) (Y) (Y) – (X)
Increasing input current Decreasing input current
1 3 1 15
2 6 2 12
3 9 3 9
4 12 4 6
5 15 5 3
CALCULATIONS
• Calculate hysteresis by using formula:
• Hysteresis =Output at decreasing Input – Output at increasing input.
• Plot the graph showing hysteresis as input (increasing and decreasing) on X axis and corresponding
output on Y-axis.
RESULTS
• Some deviation in hysteresis of P/I converter was observed as it depends upon accuracy of pressure
gauges used accuracy of digital calibrator and visual error in recording the readings.
EXPERIMENT NO 30
AIM
To study the accuracy of P/I converter.
SETUP REQUIRED
P/I converter setup
EXPERIMENTAL PROCEDURE
1. Start up the set up.
2. Now put digital calibrator in measure mode.
3. Give pressure input in the step of 3 psig from 3 to 15 psig by slowly rotating the air regulator.
4. Note down corresponding current output on digital calibrator in mA.
OBSERVATIONS
S. No. Input pressure Standard Output Actual Output Deviation (mA)
(psig) Current (mA) (X) Current (mA) (Y) (Y) – (X)
1 3 4
2 6 8
3 9 12
4 12 16
5 15 20
CALCULATIONS
Uncertainty error (%) = ((Y-X)/X) ͯ 100
Calculate average uncertainty error
Accuracy (%) = 100 – average uncertainty error (%)
RESULTS
• Accuracy of P/I converter was found to be ……………………………
EXPERIMENT NO 31
AIM
To study the repeatability of P/I converter.
SETUP REQUIRED
P/I converter setup
EXPERIMENTAL PROCEDURE
1. Start up the set up.
2. Now put digital calibrator on measure mode.
3. Give pressure input in the step of 3 psig from 3 to 15 psig by slowly rotating the air regulator.
4. Note down corresponding current output on digital calibrator in psig.
5. Now repeat the above steps for more trials.
6. Tabulate above readings in the observation table given below.
OBSERVATIONS
S. No Input pressure Output current S. No. Input pressure Output current
(psig) (mA) (psig) (mA)
(X) (Y)
Trial 1 Trial 2
1 3 1 3
2 6 2 6
3 9 3 9
4 12 4 12
5 15 5 15
CALCULATIONS
Repeatability: Note down the values of output for same input in repeated trials. Repeatability can be
found out in % of each reading.
RESULTS
Repeatability of P/I converter was found to be ……………………………
EXPERIMENT NO 32
AIM
To study the operation of P controller.
SETUP REQUIRED
Universal process control trainer with workstation
EXPERIMENTAL PROCEDURE
1. Click Select Experiment |Select P mode |Click Start.
2. Adjust the process value by switching the controller to manual mode to a particular flow (say 50
%) on the screen and set this output as bias (MR) value. Change the proportional band to 100%.
3. Switch the controller to auto mode.
4. Apply step change of 5% to set point.
5. Switch the controller to manual mode. Decrease proportional band to half of the previous value.
With each decrease, obtain a new response of the step change. Ensure that the set point changes
are around the same operating point (Say 50%).
6. Using trial and error approach, find a value of proportional band so that the response to a step
change has at most one overshoot and one undershoot.
7. Set the controller to the settings obtained in the above step and wait for the system to reach at
steady state.
OBSERVATIONS
RESULTS
EXPERIMENT NO 33
AIM
To study the operation of PI controller.
SETUP REQUIRED
Universal process control trainer with workstation
EXPERIMENTAL PROCEDURE
1. Click Select Experiment |Select PI Mode |Click Start.
2. Select PI Mode. Set the proportional band estimated in Proportional control. And integral time
500 sec, which will cut off the derivative action and widen the effect of integral action.
3. Set the set point to desired flow value (@50%). Allow the process to reach at steady state.
Record the steady state error.
4. Switch the controller to manual mode. Reduce the integral time to half of the previous value.
Switch to Auto mode and apply step change (+/- 5%) to the set point. Note the response of the
system.
5. Repeat above step to observe the effect of changes in Integral setting.
OBSERVATION
• Observe the effect of reducing integral time on offset and on the response of the process.
RESULTS
EXPERIMENT NO 34
AIM
To study the operation of PD controller.
SETUP REQUIRED
Universal process control trainer with workstation
EXPERIMENTAL PROCEDURE
1. Click Select Experiment |Select PD Mode |Click Start.
2. Select PD controller. Set the proportional band estimated from Proportional control (P only) set
derivative time to 0 sec.
3. Set the set point to desired value (@50%). Allow the process to reach at steady state. Note the
response of the system.
4. Switch the controller to manual mode Increase the derivative time by 1 sec. Switch to Auto mode
and apply step change to the set point by 5%. Note the response of the system.
5. Increase the derivative time gradually and observe the process response for step change.
OBSERVATIONS
• Compare the steady state response of the PD controller with PI controller obtained in the
previous experiment.
• Note the effect of noisy flow measurement on the derivative action
RESULTS
EXPERIMENT NO 35
AIM
SETUP REQUIRED
Universal Process Control Trainer with Workstation
EXPERIMENTAL PROCEDURE
1. Click Select Experiment |Select PID Mode |Click Start
2. Switch the controller to manual mode.
3. Change the proportional band to the value that estimated in proportional controller. Set integral
time and derivative time based on the responses in previous experiments.
4. Adjust the set point to @ 50 %. Switch the controller to auto mode. Apply step change of 5%.
Observe the process response.
5. Change the proportional band, integral time, derivative time and observe the response of the
process for step change for each change in setting.
OBSERVATIONS
• Compare the steady state response of the PID controller with P. PI and PD controller
obtained in the above experiment.
RESULTS