Professional Documents
Culture Documents
JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, VOL. XX, NO. XX, XX XXXX 1
Abstract——Distributed generation units (DGUs) bring some er electronic converters (PECs) to the distribution networks
problems to the existing protection system, such as those associ‐ or at the customer side of the network [1]. PECs are used as
ated with protection blinding and sympathetic tripping. It is
interfaces in DGUs because they allow adapting the power
known that fault current limiters (FCLs) help minimize the neg‐
ative impact of DGUs on the protection system. In this paper, a generated by the RES to the needs of the power grid and
control-based FCL is proposed, i. e., the FCL is integrated into their high efficiency [2].
the DGU control law. To this end, a predictive control strategy Distributed generation (DG) introduces several improve‐
with fault current limitation is suggested. In this way, a DGU is ments to the distribution network such as the reduction of
controlled, not only for power exchange with the power grid transmission losses, power quality improvement, and in‐
but also to limit its fault current contribution. The proposal is
posed as a constrained optimization problem allowing taking in‐ crease in system reliability. However, high penetration of
to account the current limit explicitly in the design process as a DG brings new protection problems absent in the convention‐
closed-loop solution. A linear approximation is proposed to cope al power grid [3]. The integration of DGUs in the distribu‐
with the inherent nonlinear constraints. The proposal does not tion network changes the levels and paths of fault current,
require incorporating extra equipment or mechanisms in the leading to the malfunction of protective devices (PDs) due
control loop, making the design process simple. To evaluate the
proposed control-based FCL, both protection blinding and sym‐ to downstream faults (protection blinding) and sympathetic
pathetic tripping scenarios are considered. The controller con‐ tripping [4], [5].
fines the DGU currents within the constraints quickly, avoiding To deal with these protection problems, limiting both the
large transient peaks. Therefore, the impact on the protection penetration level and rating power of DGUs has been pro‐
system is reduced without the necessity that the DGU goes out posed [6], [7]. This approach relieves the problem but works
of service.
against achieving high penetration of DG. In the same direc‐
Index Terms—
—Distributed generation unit, fault current limit‐ tion, another proposal is to disconnect all DGUs under a
er, model-based predictive controller. fault condition [8], which limits the impact of DG on the
protection system. However, disconnecting DGUs from the
power grid could cause a large power imbalance and even
I. INTRODUCTION
the collapse of the power grid in a high penetration scenario.
the DGU to a value of twice the nominal current under a are illustrated in Fig. 1, where V s, Z s, and I s are the voltage,
faulty condition. Reference [18] proposes a virtual-imped‐ impedance, and current of the main grid, respectively; V dg,
ance-based FCL to limit the fault current contribution of a Z dg, and I dg are the voltage, impedance, and current of the
DGU. Reproducing the behavior of a traditional FCL, a vir‐ DGU, respectively; and Z load is the impedance load. This ef‐
tual impedance is connected in series with the DGU output fects are described below.
when detecting a fault by comparing the output current with 1 ) Protection blinding due to downstream faults: in the
a threshold. Meanwhile, in normal operation, the virtual im‐ scenario shown in Fig. 1(a), consider that the PD is set previ‐
pedance is kept to zero. The effect of this mechanism on the ously to the connection of DGU. When a fault occurs at the
control loop is that the voltage loop reference is adjusted to load side, the current measured by PD is only part of the to‐
a suitable value so as not to exceed the current limit value. tal fault current since I f = I s + I dg, and only I s passes through
Limiting the fault current contribution of DGUs can be PD. Therefore, if I dg is large enough, PD may act with inad‐
stated as a constrained control problem [19]. In [16] - [18], missible delay or even not act due to insufficient current
controllers are designed without considering constraints, then when the feeder is at fault.
modifications are introduced into the control loop to consid‐ 2) Sympathetic tripping: in the scenario shown in Fig. 1
er the constraints. In this paper, constraints are considered (b), assume that PD1 and PD2 are set previously to the con‐
from the beginning of the design process as a closed-loop so‐ nection of DGU. So, when a fault occurs in feeder2, the PD
lution. To this end, the controller is stated as a constrained that must act is PD2. If the DGU is connected to feeder1,
optimization problem, allowing considering the current limit then the direction of the current through PD1 may change,
explicitly in the design process. This current limit results in and if the DGU fault current is large enough, PD1 could be
a nonlinear constraint, then a linear approximation is pro‐ activated. If this happens, unreasonable electrical interrup‐
posed. Thus, a model-based predictive controller (MPC) in tion may occur in the healthy feeder, reducing the system re‐
the current control loop of a DGU is proposed and evaluat‐ liability.
ed. Constraints on the currents are considered explicitly in
Vdg
the control loop that regulates them. Therefore, currents are Main grid
PCC
Idg Zdg DGU
quickly confined within the constraints. Moreover, with the Vs Z s Is
predictive characteristics of the controller, it is not necessary
to compare the DGU currents with any threshold or change PD If ZLoad
the control objectives. This property makes the design pro‐
Feeder
cess of the controller simple.
This paper is organized as follows. Section II presents the (a)
arising problem from DGUs on the protection system. Sec‐ Vdg
Idg Zdg
tion III describes the conventional operation mode of DGU DGU
to evaluate the proposal. Section IV explains the proposed PCC
control-based FCL. Section V shows the simulation results ZLoad1
Main grid PD1
for the different cases stated in Section II. Finally, in Section
Vs Is Feeder1
VI, the conclusions are presented. Zs
PD2 If ZLoad2
II. ARISING PROBLEMS FROM DGUS ON PROTECTION Feeder2
SYSTEM
(b)
When a failure occurs in the power grid, the smaller possi‐
Fig. 1. Different effects caused by DG on protection system. (a) Malfunc‐
ble portion of the network through the PDs must be isolated. tion of PD due to downstream fault. (b) Sympathetic tripping of PD1.
The coordination between PDs is achieved by tunning his
threshold current and action time. Action time is a function
of the fault current threshold for inverse-time overcurrent re‐ III. CONVENTIONAL OPERATION MODE OF DGU
lays, and the characteristics depend on specific PD type, ac‐ Typically, DGUs are controlled to behave as a current
cording to the IEEE C37.112 standard, as shown in Appen‐ source. Its fault current contribution depends on the fault lo‐
dix A. cation and the penetration level, size, type, and technology
After setting PDs, the connection of DGUs in the network of the DGU. Generally, the inverters used in DGUs are de‐
can produce coordination loss and/or sensitivity loss be‐ signed to be able to support the power grid during transitory
tween PDs. The miscoordination of PDs may cause false re‐ disturbances. In the worst case, if the fault current contribu‐
lay trips and disconnection of a greater network area, while tion continues for more than half a cycle [22], it typically
the sensitivity loss may prevent or delay the isolation of the does not exceed two times the steady-state current rating of
fault. As a consequence, delayed fault isolation will degrade the inverter [23].
the power quality. The impact of DG on the protection coor‐ In order to evaluate the proposal, a DGU connected to the
dination and/or sensitivity depends on the network load, the network by a full-scale voltage source inverter (VSI) is con‐
location and operation modes of the DGUs, and fault loca‐ sidered as shown in Fig. 2, where L f, C f, and R f are the filter
tion [20], [21]. inductor, capacitor, and resistor, respectively; v and i are volt‐
Different effects caused by DG on the protection system age and current, respectively; θ is the voltage phase used to
MUÑOZ et al.: CONTROL-BASED FAULT CURRENT LIMITER FOR MINIMIZING IMPACT OF DISTRIBUTED GENERATION UNITS... 3
synchronize the reference frame; P and Q are the active and loops, i.e., an internal loop that regulates the current injected
reactive power, respectively; the subscripts c and o means by the converter (current control loop) and an external loop
for terminal converter and output quantities, respectively; that regulates the power that the converter exchanges with
the power grid (droop control loop) generating the current
and subscripts d and q represent d-axis and q-axis values.
references i *cd and i *cq for the inner loop. Note that, as stated
The VSI operates as a grid-supporting converter [2], which above, our proposal rely on modifying the current control
means that the DGU adjusts its active and reactive power to loop. So, it is applicable regardless of the operation mode of
contribute to regulating both voltage amplitude and frequen‐ DGU since the current control loop is presented in all operat‐
cy. Figure 2 shows the overal control block diagram with two ing modes.
Droop loop
ω* P i*cd PCC
1
+ m + vod ic io
+ + vc
ω P* + MPC with
PWM
constraints VSI
ω*o Q i*cq Rf Lf
n 1
+ + voq
+ + Cf vo
ωo Q* +
ic,dq vo,dq
vod icd θ
dq vo,abc dq ic,abc vo,abc
voq icq ω PLL
abc abc
θ θ
Fig. 2. Overall control block diagram.
The following droop laws are implemented in the droop ② a cost function and a set of constraints to establish the de‐
control loop: sired behavior of the system; and ③ an optimization process
ì P = -m(ω - ω ) + P
* * to find N c samples forward a control action that minimizes
í (1) the cost function and verifies the constraints.
î Q = -n(v o - v o ) + Q
* *
where ω* and v *o are the nominal system frequency and the A. Current Control Loop: Prediction
nominal voltage output, respectively; ω and v o are the sys‐ The control loop through the MPC regulates the currents
tem frequency and the voltage amplitude, respectively; P * i cd and i cq injected by the DGU to the connection point PCC.
and Q * are the active and reactive power references, respec‐ This connection is made through a coupling impedance, as
tively; and m and n are the droop slopes. shown in Fig. 2. The PEC will adjust its voltage v c accord‐
Regarding the current control loop, it is typically imple‐ ing to the current over L f, i. e., i c. It is necessary to have a
mented in the d-q synchronous reference frame using propor‐ dynamic model that relates the currents (controlled variable)
tional integral (PI) controllers. In this paper, to control and with the voltages generated by the PEC (manipulated vari‐
limit the DGU current contribution, the current control loop able) to implement the MPC control. From transforming the
is considered as a multivariable system, where the converter system to a d-q synchronous reference frame preserving the
current i c is constrained to not exceed a predefined value, i. amplitude, the following model, which represents the dynam‐
e., i c = i 2cd + i 2cq £ I max, where i cd and i cq are the i c compo‐ ics of the system, is obtained as:
nents in the d -axis and q - axis, respectively. æ Rf ö
ç- ω ÷
̇ ç
êé i cd úù = ç L f ÷ éi ù 1 éê v cd ùú 1 éê v od ùú
IV. PROPOSED CURRENT CONTROL LOOP: A ê ú ÷ ê cd ú + - (2)
̇
ë i cq û ç ç R ÷ ë i û L ë v û L f ë v oq û
-ω - ÷
f cq f cq
CONTROL-BASED FCL ç Lf ÷
The MPC objective is to find the control action trajectory è ø
which optimizes the behavior of the system output, verifying where v cd and v cq are the DGU voltage components in the d-
the constraints imposed on the inputs, outputs, and/or states and q-axes, respectively; vod and voq are the vo components in
using a dynamic model to predict system behavior [24]. The the d-axis and q-axis, respectively; and ω is considered con‐
control action is optimal in the sense that it minimizes a cost stant and equal to its nominal value for the prediction mod‐
function subject to constraints. The optimization process is el. The last term at the right side in (2) represents the impact
carried out within a time window or prediction horizon of of the network voltage on the dynamics and can be consid‐
N p forward samples, using the available information of sys‐ ered as a measurable disturbance.
tem state at the beginning of the time window. The control The first step in the problem statement following [24] is
action can change only N c samples in the future, which is to discretize the prediction model. Then, the model is rewrit‐
known as the control horizon, and satisfy N c < N p. In summa‐ ten in increments of the variables and expanded to incorpo‐
ry, the MPC has the following components: ① a dynamic rate integral action taking as outputs of the controlled vari‐
model to predict the system behavior N p forward samples; ables i cd and i cq. Therefore, (2) adopts the general form as:
4 JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, VOL. XX, NO. XX, XX XXXX
ì x[k + 1]= Ax[k]+ BDu[k]+ WDd[k] reference signal is assumed to remain constant within the
í (3) prediction horizon, hence R Ts = [ 1 1 1 1 ] 1 ´ N r s [k i ].
î y[k]= Cx[k] p
where A, B, W and C are the dynamic, imput, distunbance, The first term in (7) reflects the objective of minimizing the
and output matrices of the expanded model (3); k is the sam‐ error between the output prediction Y and the reference, and
pling time instant; x[k]= [ Di cd [k] Di cq [k] i cd [k] i cq [k] ] the second term in (7) penalizes the control action incre‐
T
ment;.
is the vector state; Du[k]= [ Dv cd [k] Dv cq [k] ] is the manipu‐
T
0
means that reactive power injection has the priority over ac‐
tive power injection, which is in accordance with the net‐
work codes.
Regarding the fault current limitation, it is a common
practice to limit the current to twice its rated value during a
Imax fault [16]-[17]. In order to highlight the flexibility and poten‐
-Imax 0 -Imax tial of the proposed control-based FCL, it is proposed to lim‐
icd it the fault current contribution of the DGU according to the
Nonlinear constraint; Linear constraint
severity of the abnormality [25].
Fig. 3. Current constraint.
ì P*
ï V bus1 ³ 0.88V *
ï 0.88V *
ξ 1 [A(1:)x[k i ]+ B(1:)DU[k i ]]+ I max = í (12)
ïï V P*
ξ 2 [A(2:)x[k i ]+ B(2:)DU[k i ]]£ ξ 3 I max (10) V < 0.88V *
ïî bus1 (0.88V * )2 bus1
th
where the notation (i:) represents the i row of the matrix.
Finally, by rewriting (10), the following inequality constraint where V * is the nominal voltage; and V bus1 is the voltage at
is obtained as follows and is in the form of (8). the connection point of the DGU, as shown in Fig. 4. In this
way, if the DGU is located close to the fault location which
[ξ ]
ξ2
1 B DU[k i ]£ ξ
3I - [ ξ 1 ξ 2 ] Ax[k i ] produces the greatest impact on the protection system, the
max
(11)
M γ
voltage sag experienced by the DGU is deeper. Therefore,
Note that I max can be chosen in accordance with the partic‐ its contribution to the fault current during the fault is re‐
ularities of the system and even be changed according to the duced without limiting its power contribution under normal
state of the system. conditions.
A. Scenario 1: Protection Blinding
V. SIMULATION RESULTS
In this scenario, a balanced short circuit is considered at
Figure 4 shows the test network (medium voltage) consid‐
point A as shown in Fig. 4, which occurs at t = 1 s. The tran‐
ered to evaluate the proposed control-based FCL, in which
sient responses of the currents injected by the DGU, with
the adverse effects of DG on the protection system are pre‐
and without FCL, are shown in Figs. 5(a) and 5(b), respec‐
sented. Line impedance [2] is (0.161 + j0.190) Ω/km. Cou‐
tively. Without FCL, the DGU increases its current contribu‐
pling filter parameters of the DGU are R f = 0.038 Ω; L f = tion without exceeding the limit of twice its nominal current,
1.52 mH; and C f = 20 μF. This test network exhibits the prob‐ i.e., 355 A in this scenario, so the typical FCL that limits the
lems stated in Section II. It is considered as an original net‐ current to twice the rated current would not act in this case.
work (black line network) formed by two feeders connected When the proposed control-based FCL is activated on the
to the point of common coupling (PCC). Feeder1, with a DGU, the current is quickly confined within the constraint
length of 60 km, connects the load to the substation. Feed‐ despite the suddenness of the disturbance, which causes a
er2, with a length of 20 km, connects the load from PCC. practically instantaneous voltage drop. Figure 6(a) shows the
Both feeders have an inverse time overcurrent relay (PD1 current transient in the i d - i q plane, and Fig. 6(b) shows the
and PD2), which follows the law shown in the Appendix A. time evolution of its components. Points A to D pointed out
One DGU is connected 10 km away from PCC, which oper‐ in Fig. 6(a) agrees to the time instants A to D pointed out in
ates as explained in Section III (blue line network) with the Fig. 6(b). Note that the constraint under normal conditions is
proposed current control loop presented in Section IV. Table I exceeded only at the initial instant for less than half cycle
shows the typical parameters for the configuration of the PDs. (< 1 ms). So, the current is limited within the constraints dur‐
To evaluate the impact of DG on the protection system, ing voltage sag in less than a network cycle (< 15 ms). This
two scenarios are considered. In the first scenario, called pro‐ fast response avoids that any protection, either the PDs of
tection blinding, a short circuit occurs at point A on feeder the system or DGU protection, acts due to transient peaks.
TABLE I Regarding this, the benefit of the proposed control-based
PDS CONFIGURATION FCL is twofold: not only avoids the protection blinding but
also guarantees that the DGU never goes out of service due
PD Curve characteristic TD I th (A) to overcurrent.
PD1 Extremely inverse 0.15 90 Figure 7 shows the root mean square (RMS) current
PD2 Extremely inverse 0.15 275 through PD1. The solid blue line corresponds to the case
6 JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, VOL. XX, NO. XX, XX XXXX
300 the case where there is no DGU (solid blue line), and it de‐
Current (A) 100 lays only about three more network cycles (0.06 s) to oper‐
-100 ate, reducing the protection blinding.
-300 500
0.98 0.99 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 Without DGu
Time (s)
400 Without FCL
(a)
120 With DGU and FCL
Current (A)
300
Current (A)
60
0 200
-60
-120 100
0.98 0.99 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08
Time (s)
0
(b) 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
Fig. 5. DGU current. (a) Without FCL. (b) With FCL. Time (s)
Fig. 7. RMS current through PD1.
120
100 Figure 8 shows the voltage and frequency at the PCC un‐
80 der the same three simulation conditions. From Fig. 8(a), it
60 can be observed that the voltage drops by twice the time
40 when the fault current of the DGU is not limited. Therefore,
20 this extended voltage dip could lead to both malfunction or
Idg, q
-100 0.8
-120 0.6 Without DGU; With DGU
-125 -100 -75 -50 -25 0 25 50 75 100 125 150 0.4
Idg, d 0.2 With DGU and FCL
Nonlinear constraint under normal condition 0
0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
Linear constraint under normal condition Time (s)
Nonlinear constraint during voltage sag (a)
Linear constraint during voltage sag; Idg with FCL 50.4
Frequency (Hz)
(a) 50.2
200 50.0
A BC D
Current (A)
even less than that under normal conditions since the voltage 1.5
Without DGU
With DGU
sag is deeper than that in scenario 1.
Voltage (p.u.)
With DGU and FCL
1.0
400
Current (A)
200 0.5
0
-200
0 0.5 1.0 1.5 2.0 2.5
-400 Time (s)
0.98 0.99 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08
Time (s) (a)
Frequency (Hz)
(a) 50.4 Without DGU
180 With DGU
50.5 With DGU and FCL
Current (A)
120
50.0
60
0 49.8
-60 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
Time (s)
-120
0.98 0.99 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 (b)
Time (s) Fig. 11. Voltage and frequency at bus 1 in feeder1. (a) Voltage. (b) Fre‐
(b) quency.
Fig. 9. Transient responses of currents injected by DGU. (a) Without FCL.
(b) With FCL.
VI. CONCLUSION
In this paper, a control-based FCL is proposed to mini‐
Figure 10 shows the current through PD1 and PD2 for the mize the impact of DG on the protection system. The FCL
three simulation cases. It can be observed that if the fault is based on predictive control without altering the topology
current injected by the DGU is not limited (solid red line), of the control loop, implementing some kind of fault detec‐
PD1 is activated before PD2 isolates the fault (approximate‐ tor, or changing the control objectives. Therefore, it is easier
ly at t = 1.65 s). Then, the service in the healthy feeder is in‐ to understand and tune in comparing with other strategies
terrupted. Therefore, in this scenario, limiting the DGU fault found in the literature. Moreover, this is a closed-loop solu‐
current is essential to avoid sympathetic tripping. Figure 11 tion that considers the constraints as a control objective di‐
shows the voltage and frequency at bus 1 in feeder1. It can rectly in the current control loop. Thus, it is possible to im‐
be noted that when no limit exists in the fault current of pose the current constraints quickly, in less than 1 ms, which
DGU, after the activation of PD1, both the frequency and is a substantial improvement compared with other proposals.
the voltage drop to zero. This is due to that feeder1 having This fast response of the proposed strategy is crucial to
no power source is able to impose the voltage and frequen‐ avoid that any protection, either PDs of the system or protec‐
cy. In this case, the DGU must go out of service. PD1 is not tions of the DGU, acts due to transient peaks. Therefore, the
activated when limiting the DGU fault current. Thus, once proposed control-based FCL not only reduces the impact of
the fault is isolated by the action of PD2 (approximately at the DGU on the protection system but also allows the DGU
t = 2 s), both the voltage and frequency return to their nor‐ to ride through the fault connected to the power grid. Both
mal values. This is similar to the case in which the DGU is protection blinding and sympathetic tripping scenarios are
not connected. studied and simulated. The simulation results show that the
300 Without DGU proposed strategy can substantially diminish the deterioration
With DGU in the protection system.
Current (A)
( )
Current (A)
A
500 Without DGU t(I) = TD ×
+B (A1)
With DGU M -1 P