CANOPY COLUMN
(DESIGN-BUILD) 1. DETAILS SHOWN ARE PROVIDED AS A NON-SITE SPECIFIC BASIS OF DESIGN. DESIGN IS BASED ON 150 MPH WIND, 3-SEC
BASE COVER PLATE GUST, EXPOSURE C, ASCE 7-16, IBC SOIL CL ASS 5. CONFIRM THAT THE REQUIREMENT MEETS OR EXCEEDS SITE SPECIFIC
DESIGN CRITERIA AND CONSTRAINTS. VERIFY COMPLIANCE WITH ACTUAL DIMENSIONS OF DESIGN/BUILD STRUCTURES
AND/OR PREFABRICATED UNITS PURCHASED.
2. THE MINIMUM UPLIFT FACTOR OF SAFETY FOR CANOPY FOUNDATIONS SHALL NOT BE LESS THAN 2.0.
1 1/2" NONSHRINK GROUT
(3) #3 TIES @ 3" O.C. 3. PROVIDE THE MINIMUM FROST PROTECTION DEPTH FROM FINISHED GRADE TO THE BOTTOM OF ANY EXTERIOR FOOTING
OR TURN DOWN BUILDING SLAB.
2" CLR.
CONCRETE / SIDEWALK
SURFACE. SEE CIVIL 1/2" ISOLATION JOINT
4. THE ENGINEER OF RECORD (EOR) MUST PROVIDE WRITTEN CONFIRMATION THAT THE PROJECT GEOTECHNICAL
ENGINEER HAS REVIEWED THE PLANS AND SPECIFICATIONS AND THAT THE DESIGN IS IN COMPLIANCE WITH THE
RECOMMENDATIONS OF THE GEOTECHNICAL REPORT.
5. MAINTAIN MINIMUM EDGE DISTANCE SHOWN OR AS RECOMMENDED BY KIOSK MANUFACTURER AND ANCHOR
MANUFACTURER, WHICHEVER IS GREATER. COORDINATE OVERALL FOUNDATION SLAB DIMENSIONS WITH CIVIL AND KIOSK
MANUFACTURER.
6. ALL CONCRETE FOUNDATIONS AND SLABS SHALL, AT A MINIMUM, BE REINFORCED TO RESIST SHRINKAGE AND
TEMPERATURE STRESSES IN ACCORDANCE WITH ACI 318-14, SECTION 24.4.
CANOPY COLUMN
(DESIGN-BUILD)
BASE COVER PLATE
2" CLR.
CONCRETE / SIDEWALK
SURFACE. SEE CIVIL 1/2" ISOLATION JOINT
6 1/2" (MIN.) 6
(SEE NOTE 5) S-301
1/2" ISOLATION JOINT SIM.
CONCRETE / SIDEWALK
SURFACE. SEE CIVIL #4 @ 12" O.C., EA. WAY
(MIN.)
6"
(SEE NOTE 1)
(TYP.)
SEE NOTE 3
(SEE NOTE 1)
2 6" (MIN.) POROUS FILL
#4 @ 12" O.C. SEE NOTE 4
5' - 6"
3'-6" 9 1
(4) #5 VERT. BARS
LOW VOLUME CHANGE FILL
#4 BAR
ON COMPACTED SUBGRADE
SEE NOTE 4
3" CLR.
(TYP.)
1' - 0"
(MIN.)
3" CLR.
(TYP.)
3'-6"
3" CLR.
(TYP.)
1 MAIN ENTRANCE CANOPY FOUNDATION 2 PEDESTRIAN ENTRY CANOPY FOUNDATION 3 THICKENED SLAB EDGE SECTION
S-301 S-301 S-301
1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0"
4 TYPICAL SECURITY KIOSK BASE ANCHORAGE - B.I.G. 5 TYPICAL SECURITY KIOSK BASE ANCHORAGE - PAR-KUT 6 TYPICAL SERVICE LOBBY BASE ANCHORAGE 7 TYPICAL BUS SHELTER BASE ANCHORAGE - B.I.G.
S-301 S-301 S-301 S-301
3" = 1'-0" 3" = 1'-0" 3" = 1'-0" 3" = 1'-0"
S-301
N 0.3 2023-05-03 65% DESIGN
ENTRANCE DETAILS
HDR, INC. 1301 BURLINGTON STREET NOT FOR CONSTRUCTION Council Bluffs, IA
Proj. No.10362927
1917 SOUTH 67th STREET SUITE 100
OMAHA, NE 68106 N KANSAS CITY, MO 64116
(402) 399-1000 P 816.361.1177 SCALE: As indicated PHASE: 65% DESIGN