You are on page 1of 1

NOTES:

1. DO NOT SCALE IN THE DRAWINGS.


2. THIS DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL OTHER PROJECT
* FOR INSULATED AND NONE INSULATED PIPES. * FOR INSULATED AND NONE INSULATED PIPES. * FOR INSULATED AND NONE INSULATED DUCTS. ARCHITECTURAL AND ENGINEERING DOCUMENTS.
3. REFER TO SPECIFICATION HVAC WITH DOCUMENT NUMBER RE611869 FOR
REFERENCE CODES AND STANDARDS.
4. FOR CONDENSATE DRAIN REFER TO PLUMBING DRAINAGE DRAWINGS.
cancel it or show it on the INSIDE BUILDING OUTSIDE BUILDING
ERW SCHEDULE 10 GALVANIZED STEEL architecture drawing 20 GAUGE GALVANIZED SHEET
PIPE SLEEVE METAL DUCT SLEEVE
cancel it or show it on the SEALANT 0A1 SCHEDULE 40 GALVANIZED STEEL
FIRE RATED JOINT SEALANT
PIPE SLEEVE FIRE DAMPER
architecture drawing PIPE
DUCT
FIRE RATED JOINT SEALANT WEATHER PROOF SEALANT

{+{50mm MAX
12mm 12mm
PIPE

(FOR BOTH SIDE)


H+200mm
{+{50mm MAX
12mm 12mm

12mm

ACCESS DOOR SIZE AS


PER MECHANICAL
SPECIFICATION

FALSE CEILING INTUMESCENT


EXPANDING FOAM FALSE CEILING
COMPRESSIBLE FILLER MATERIAL COMPRESSIBLE FILLER MATERIAL
ROCKWOOL, DENSITY 32kg/m³ COMPRESSIBLE FILLER MATERIAL
ROCKWOOL, DENSITY 32KG/m 3
ROCKWOOL, DENSITY 32KG/m 3 NOTE:
* REFER TO DETAIL 057 FOR UL NUMBERING
SYSTEM FOR FIRE STOP DESIGN

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
010 PIPE PENETRATION THROUGH INTERIOR WALLS, PARTITIONS (NON-FIRE RATED) 011 PIPE PENETRATION THROUGH FIRE RATED EXTERNAL WALL 012 DUCT PENETRATION THROUGH INTERIOR WALLS, PARTITIONS (FIRE RATED)
611709 SCALE 611709 SCALE 611709 SCALE
N.T.S N.T.S N.T.S
SH002 SH002 SH002

* FOR INSULATED AND NON INSULATED DUCTS. * FOR INSULATED AND NONE INSULATED PIPES. * FOR INSULATED AND NONE INSULATED DUCTS.

cancel it or show it on the


architecture drawing cancel it or show it on the
INSIDE BUILDING OUTSIDE BUILDING
architecture drawing
0A1

20 GAUGE GALVANIZED SHEET SCHEDULE 40 GALVANIZED STEEL 20 GAUGE GALVANIZED SHEET


METAL DUCT SLEEVE PIPE SLEEVE METAL DUCT SLEEVE
WEATHER PROOF SEALANT
FIRE RATED JOINT SEALANT FIRE RATED JOINT SEALANT SEALANT
AIR DUCT PIPE DUCT
cancel it or show it on the
architecture drawing

(FOR BOTH SIDE)


(FOR BOTH SIDE)

{+{50mm MAX
12mm 12mm 12mm 12mm
H+200mm

H+25mm

H

ACCESS DOOR INTUMESCENT
EXPANDING FOAM REFERENCE DRAWINGS
FIRE DAMPER
HVAC STANDARD DETAILS RA-611709-001 TO 009

COMPRESSIBLE FILLER MATERIAL FALSE CEILING FALSE CEILING HVAC GENERAL NOTES, LEGENDS AND SYMBOLS RA-611708-001 TO 002

ROCKWOOL, DENSITY 32KG/m 3 COMPRESSIBLE FILLER MATERIAL COMPRESSIBLE FILLER MATERIAL


ROCKWOOL, DENSITY 32kg/m³ ROCKWOOL, DENSITY 32KG/m 3
NOTE:
* REFER TO DETAIL 057 FOR UL NUMBERING
SYSTEM FOR FIRE STOP DESIGN

013 DUCT PENETRATION THROUGH FIRE RATED EXTERNAL WALL 014 PIPE PENETRATION DETAILS (FIRE RATED) 015 DUCT PENETRATION THROUGH INTERIOR WALLS, PARTITIONS (NON-FIRE RATED)
611709 SCALE 611709 SCALE 611709 SCALE
N.T.S N.T.S N.T.S
SH002 SH002 SH002

1
4"DIA. MASONRY ANCHOR
we found the sand trap
(FOR CONCRETE WALL)
all "galvanized and painted" louver is embedded in the
NO. 14 SELF TAPPING
revised "galvanized" W
SCREW ( FOR METAL WALL) wall in 3D model, please

INSIDE
STEEL ANCHOR STEEL ANCHOR
SIGHT GLASS W-10
check and revised the
NOTE:
typical drawing
FILTER DRIER
CONCRETE SLAB CONCRETE SLAB 1. ALL DIMENSIONS ARE IN MILLIMETERS

WALL
SERVICE VALVE UNLESS OTHERWISE NOTED.
2. SAND TRAP LOUVER ASSEMBLY SHALL
GALVANIZED AND GALVANIZED AND
BE SUPPLIED BY CONTRACTOR.
PAINTED THREADED PAINTED THREADED LIQUID LINE

OUTSIDE
ROD ROD
SELF-EMPTYING SAND
25 102 51

51
DRAIN HOLES
NEOPRENE ISOLATOR NEOPRENE ISOLATOR
AIR COOLED OUTSIDE WALL INSIDE
SOLENOID VALVE (SV) VERT. BLADES
FLEXIBLE DUCT CONDENSING UNIT W+102
76 76
CONNECTION
(TYPICAL) SERVICE VALVE
NO. 14 SELF TAPPING
SCALE: N.T.S
SCREW (FOR METAL

25
SUCTION LINE
WALL)
DUCT REVISION VALIDATION

DUCT SPRING THIS REVISION NO. 0A1 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
FAN
(VIBRATION ISOLATOR) REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

25-00053-0007-111
FAN DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
FOR CONCRETE PAD DETAILS (CONSTRUCTION, SAND TRAP

H+102

H-10
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
MATERIAL, DIMENSIONS) PLEASE REFER TO LOUVER

H
BONDING JUMPER ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

(TYP.) STRUCTURAL DRAWINGS FS UFA


09/08/20 09/08/20
A FRONT VIEW B SIDE VIEW
CONCRETE PAD REV.NO. DATE REVISION DESCRIPTION

00 09/08/20 ISSUED FOR CONSTRUCTION


- SCALE : NTS - SCALE : NTS
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
25-00053-0007 CONSTRUCTION UNTIL CERTIFIED AND DATED

W+102 SAUDI ARABIAN OIL COMPANY

25
VERT. BLADES DRAWING TYPE
HVAC STANDARD HVA
SAND TRAP LOUVER
016 IN LINE FAN INSTALLATION DETAILS 017 AIR COOLED CONDENSING UNIT CONNECTION DETAIL 018 INSTALLATION DETAIL
1
4"DIA. MASONRY ANCHOR DETAILS -2
(FOR CONCRETE WALL)
611709 SCALE N.T.S
611709 SCALE N.T.S
611709 SCALE N.T.S MARITIME YARD PROJECT
SH002 SH002 SH002 SELF-EMPTYING SAND
DRAIN HOLES RAS AL KHAIR SAUDI ARABIA
UNIT NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

D000 964 K RA-611709 002 0A1


Saudi Aramco 2615 ENG. (05/05)
CAD CADD-05