NOTE

1.THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL RELEVANT


ARCHITECTS AND ENGINEERS DRAWINGS AND SPECIFICATIONS.
2. DRAINAGE PIPING SYSTEM SHALL BE PROPERLY ALIGNED AND
INSTALLED AT A UNIFORM SLOPE OF NOT LESS THAN 1.5% FOR
PIPES INSIDE BATHROOMS AND 1.2% FOR MAIN PIPES ON SITE
(UNLESS OTHERWISE NOTED). AND PIPES SHALL BE ADEQUATELY
SUPPORTED.
3. ALL PIPE DIAMETERS ARE IN MILLIMETRES UNLESS OTHERWISE STATED.
4. UNDERGROUND PIPES SHALL BE BURIED TO MINIMUM DEPTH
Ø25 Down F/A
Ø25 Down T/B Waste Water Drainage System Riser Diagram OF 50 CM. BELOW THE TOP OF THE GROUND AND AT A MINIMUM
DISTANCE OF 50 CM. FROM THE BUILDING.
W3 Sc.1:50 5. ALL PIPING PASSING THROUGH THE WALL, SLAB, BEAMS OR
S 3, 4 & 5 S 6, 7 & 8 ANY PART OF THE BUILDING, SHALL BE PROTECTED FROM BREAKAGE
Ø100 Vent Cap Ø100 Vent Cap AND PROVIDED WITH PIPE SLEEVES.
Toilet Living and Dining
Ø25
Ø25
Ø80

Ø80 HS
A=3.50m² 6. ALL PLUMBING WORKS PERFORMED SHOULD BE CARRIED BY LICENSED
FD Ceramic tile f.f ROOF FLOOR PLUMBER.
80 A=30.00m² BALCONY +15.30
LWH p.v.c tile f.f CERAMICTILE F.F
7. ALL MATERIALS, METHOD OF INSTALLATION AND QUALITY OF
WORKMANSHIP SHOULD BE SUBJECT TO THE APPROVAL OF THE
Ø100 Up T/A SANITARY ENGINEER.
Ø25 Ø25
Ø100 Down T/B 8. INTERNAL INSTALLATION OF COLD AND HOT WATER PIPES SHOULD BE
Ø25 Ø25
S 3 Ø100 Ø100 BE POLYPROPYLENE RANDOM COPOLYMER RESINES PP, TYPE 3 RAW
Ø80 Ø80
MATERIAL; PPR PIPES OF MINIMUM PN-20.
9. ALL PPR PIPE DIAMETERS SIZE GIVEN ARE EXTERNAL DIAMETER.
10. ALL HDPE PIPE DIAMETERS SIZE GIVEN ARE INTERNAL DIAMETER.
SH
11. FLOOR SLAB OF ALL WET AREAS (TOILET, KITCHEN, SHOWER, ETC.)
W4 MADE WITH APPROVED QUALITY CMENTIOUS WATER PROOFING
Ø25 Down F/A Ø80
REF.
FOURTH FLOOR Ø8 BEFORE FLOOR FINISH BEING DONE. CONSULT THE ENGINEER.
Ø25 Down T/B 0 FD
Bed Room S 4 Ø100
+12.10 WC KS
Ø50
12. UNPLASTICIZED POLYVINYL CHLORIDE (uPVC) OF MINIMUM PN-6 PIPES
AND FITTINGS SHOULD BE USED FOR ALL WASTE, DOWN PIPES AND
A=14.15m² Ø80 HWB

50
Ø100 Up T/A Ø80
p.v.c tile f.f S 7 Ø25 VENT DRAINAGE SYSTEM.

Ø
FD
Ø40 Down F/A Kitchen Ø100 Down T/B Ø25 BALCONY Ø80 Ø80 ALL uPVC WASTE WATER PIPES SHOULD NOT BE HEATED FOR

50
Ø100 Up T/A Ø50
Ø40 Down T/B A=10.00m² CERAMICTILE F.F

Ø
Ø100 Ø100 CONNECTION. ALL PIPING CONNECTION SHOULD BE MADE WITH
Ceramic
Ø100 tile f.f
Down T/B
W 6 APPROVED FITTINGS. ALL uPVC WASTE WATER INSTALLATION TO
50
Bed Room

Ø25
Ø25
Ø80
BE DONE EXPOSED UNDER SLAB.
LWH
Ø80
Kitchen FD
Ø80 80 A=14.50m²
p.v.c tile f.f
A=6.00m² CORRIDOR LWH
HS
Toilet SH
Ø25
Ø25
Ø80

Ceramic tile f.f TERRAZZO TILE F.F A=5.50m²


Ø80
REF.

Ceramic tile
FDf.f

Ø25
Ø25
Ø80
Ø80
THIRD FLOOR Ø8
Ø25
Ø25
Ø80

Ø80 50 0 FD
BALCONY +9.90 WC KS
PVC TILE F.F FD LWH
Ø80 HWB
Ø50 LEGEND(SN)

50
Ø80
Ø25

Ø
Ø80 FD
Ø80 Ø80
BT Bath Tub
Ø25

50
FH 2,3 & 4
Ø40 Down F/A Ø50 DP Down Pipe
Ø100 Up T/A F.EXT

Ø
Ø100
Ø100 Down T/B Ø40 Down T/B CORRIDOR FD Floor Drain
TERRAZZO TILE F.F

S 6 W 7 F/A From Above


F/B From Below
Living and Dining SH F/RWT
HS
From Roof Water Tank
Hand Spray

REF.
A=32.60m² Ø80 HWB Hand Wash Basin
p.v.c tile f.f SECOND FLOOR Ø8
0 FD
+6.70 WC KS KS Kitchen Sink
Ø50
Ø80 HWB
LS Laboratory Sink

50
Ø80
Kitchen

Ø
FD
Ø80 Ø80 LWH Liter Water heater
A=9.30m²

50
Ø50
Ceramic tile f.f Living and Dining MH Manhole

Ø
Ø25
Ø25
Ø80

Ø100 Ø100
Ø80 A=24.00m² S-1 Waste Water Riser
80Toilet
A=4.00m²
LWH
Bed Room
A=30m²
FD p.v.c tile f.f SH Shower
HS
Ceramic tileØ80
f.f T/B To Aove
Ø25
Ø25
Ø80

FD p.v.c tile f.f T/B To Below


SH
50 W-1 Water Riser
S 1 S 2 WM Washing Machine
LWH Ø8 Ø80
FRIST FLOOR 0 FD
Ø100 +3.50 WC KS
WC Water Closet
W 5 Ø25 Ø80 Ø80 W 8
BALCONY Ø50 Cold Water Supply PPR Pipe
Ø25 Down F/A Ø100 Up T/A Ø80 HWB

50
Ø25 PVC TILE F.F
Ø25 Ø25 Down F/A Ø80
Ø25BALCONY Ø100 Down T/B Hot Water Supply PPR Pipe

Ø
Ø32 Down T/B FD
Ø25
PVC TILE F.F
Ø25 Ø32 Down T/B Ø80 Ø80
Water Pipe With Gate Valve

50
Ø100 Up T/A S 8 Ø50

Ø
Ø100 Down T/B Waste Water Drainage Pipe

To

To
Ø100 Ø100 Ø100 Ø100

M
M
1st- 3rd FLOOR PLAN

H
H
Sanitary Installation

Ø1

Ø1
GROUND FLOOR

00
00
Sc 1:50 +0.40
WC WC WC
Ø100
WC
Ø100

Date Revision Signature

Project:
MIXED USE BUILDING

TITLE DEED NO.:

Owner:
ENE ALEMITU GELEMO

Location: CITY Kebele House No


Gondar 18 --

SN
Dwg Title: Roof plan Sanitary Installation
Fire Fighting System & Details

Des. by:

Drawn By:
02
Checked by: 03
Date:
Scale: 1:50, 1:100 June ,2020