PROGRAM
SOLUTIONS FOR
P H O T O V O LTA I C
(ISSUE 11)
T H E CO M M I T M E N T O F M E R S E N I N S A F E R
A N D M O R E R E L I A B L E S O L A R P H OTOVO LTA I C
I N S TA L L AT I O N S
It is a mix of:
• Dedication – the solutions have been specifically
designed for protecting PV power systems.
General Standards
1-N
ecessary data required for calculations Nota: the table 104 of the IEC 60269-6 requires breaking tests
carried out at a mean value of recovery voltage fixed
of photovoltaic protection: at 100 (0->+5) % of the fuse rated voltage.
These conditions are the same as those of UL standards UL 248-19
M = number of modules in series in a string (a chain) or UL 2579.
N = number of strings (chains) in parallel So, the coefficient 1.2 is applicable with both IEC and UL fuses.
For the used module: 5 - Rated current required for gPV fuses:
IRM = maximum reverse current of a module The annex BB of the IEC 60269-6 standard gives information
to determine the rated current of the gPV fuse-link to be selected.
The same calculation has to be applied to the gPV fuses
Nota: the module is tested according to the standard 61730-2
at the string level and to the gPV fuses at the recombination level
at a value equal to:
or at the input of the inverter.
135% x IRM during 2 hours:
the module has to withstand this condition With an ambient temperature inside the box lower or equal
to 45°C, the fuse rating has to be higher than or equal to
Voc STC = open circuit voltage 1.4 x Isc STC according to IEC 60269-6.
Isc STC = short circuit current As in practice ambient temperature in the boxes can rise
up to 65°C or more, a further derating is needed.
STC = S tandard Test Conditions = irradiance 1 000 W/m , 2
ISC
1.35 In within two hours”.
group
(Nc-1)xISC ISC ISC
group group group
The time-current characteristics of Mersen gPV fuses
string
are in concordance with the following gates:
1 HP6M1 L1018565
0.37
2 HP6M2 M1018566 9,5mm
1.50
3 HP6M3 N1018567 38.1mm Ø 0.41
10.4mm
4 HP6M4 Q1018569
5 HP6M5 R1018570 DERATING COEFFICIENT
(% OF FUSE RATING)
6 HP6M6 S1018571
600VDC 1.4
UL Listed 7 HP6M7 T1018572
10
CSA Certified 8 HP6M8 V1018573
IEC 60269-6 Approved (gPV)
10 HP6M10 X1018575
1.2
12 HP6M12 Y1018576
15 HP6M15 Z1018577
20 HP6M20 A1018578
1.0
25 HP6M25 K1018610
30 HP6M30 L1018611
0.8
Fuse holders
NB OF CATALOG REFERENCE NB OF MODULES 0.6
PACKAGING INDICATOR
POLES NUMBER NUMBER (17.5MM)
1 US101HEL D1009979 1 12 No
1 US101IHEL Q1009461 1 12 Yes 0.4
1 USGM1HEL P1022294 1 12 No -30 -10 10 30 50 70
Electrical Characteristics
RATED VOLTAGE (V) NOMINAL CURRENT (A) CATALOG NUMBER 70% AMP RATING (W) 80% AMP RATING (W) 100% AMP RATING (W)
1 HP10M1 B1018579
0.37
2 HP10M2 C1018580 9,5mm
1.50
3 HP10M3 D1018581 38.1mm Ø 0.41
10.4mm
4 HP10M4 E1018582
5 HP10M5 F1018583 DERATING COEFFICIENT
(% OF FUSE RATING)
6 HP10M6 G1018584
1000VDC 1.4
UL Listed 7 HP10M7 H1018585
10
CSA Certified 8 HP10M8 J1018586
IEC 60269-6 Approved (gPV)
10 HP10M10 L1018588
1.2
12 HP10M12 M1018589
15 HP10M15 N1018590
20 HP10M20 P1018591
1.0
25 HP10M25 D1023825
30 HP10M30 E1023826
0.8
Fuse holders
NB OF CATALOG REFERENCE NB OF MODULES 0.6
PACKAGING INDICATOR
POLES NUMBER NUMBER (17.5MM)
1 US101HEL D1009979 1 12 No
1 US101IHEL Q1009461 1 12 Yes 0.4
1 USGM1HEL P1022294 1 12 No -30 -10 10 30 50 70
Electrical Characteristics
RATED VOLTAGE (V) NOMINAL CURRENT (A) CATALOG NUMBER 70% AMP RATING (W) 80% AMP RATING (W) 100% AMP RATING (W)
Modulostar® HelioProtection®
BUILDINGS
88,5
83
Characteristics
• Wiring: rigid wire = 1 - 16mm2 (18-6AWG),
flexible wire = 0.75 - 10mm2 (18-8AWG) 40,5
6,5
use 75°C wire CO only. 64,5
81,27
• Screw driver heads: Mersen
recommends use of PZ 2 or flat 5.5x1mm NB OF CATALOG REFERENCE NB OF MODULES
PACKAGING INDICATOR
heads (maximum diameter 6mm). POLES NUMBER NUMBER (17.5MM)
20.5 20.5
15 15.5 15.5
0.8
0.8
27 14 9 14
6
0.8 Ø 5.5 Ø 4.2 Ø 4.2
6.35 1.9
12.7
16 12
7 15
USGM1HEL
UltraSafe™ Fuseholders BUILDINGS
Additional Specifications:
• Screw-less, spring pressure terminals:
WAGO CAGE CLAMP ®.
• Wire Range:
#14 to 6 AWG (2.5 to 16mm2) Single Conductor;
#14 to 10 AWG (2.5 to 5.0mm2) Dual Conductor.
Ratings:
• Wire Type:
• Volts: 1000VDC maximum
60/75/90°C Solid/Stranded Copper.
• Amps : 30A maximum
No USGM1HEL P1022294 12
Photovoltaic 1 1000VDC 30
Yes USGM1IHEL N1022293 12
Basics characteristics
MAXIMUM BREAKING POWER LOSSES
RATED END CONTACTS
SIZE OPERATING VOLTAGE OPERATION CAPACITY
CURRENT CATALOG REFERENCE
FOR L/R ≤ 0,5ms @ Un 0.7In 0.8In PACKAGING
NUMBER NUMBER
mm V A kA W W
8 1,3 1,7 DC10HEL12C8 D1014188 45
10 1,3 1,7 DC10HEL12C10 T1012017 45
1 200 12,5 1,3 1,9 DC10HEL12C12,5 X1008754 45
D10xL85 gPV type 10
16 1,5 2,1 DC10HEL12C16 Y1008755 45
20 1,8 2,5 DC10HEL12C20 Z1008756 45
900 25 2,2 3 DC10HEL9C25 A1008757 45
HP15M
1500VDC Midget (10x85mm)
Engineered to protect
photovoltaic applications
Mersen’s HP15M photovoltaic (PV) fuse series
was engineered and designed specifically for
the protection of photovoltaic systems. Its enhanced
fuse construction makes it ideal for continuous
temperature and current cycling withstand adding
to system longevity. The 1500VDC rated HP15M,
designed for low minimum breaking capacity
capabilities of 1.35 times the fuse rated current value,
allows for safe circuit interruption under typical
low fault current conditions produced by PV arrays.
Protect your off-grid or grid tied PV system
from unexpected ground faults and line faults
using Mersen’s Helio Protection fuse line.
US15M1HEL
UltraSafe™ Fuseholders for PV Applications
Touch-safe design
increases user safety
Mersen UltraSafe™ modular fuse holders introduce
the next level of safety for Photovolatic applications
for 10x85mm fuses. UltraSafe™ fuseholders
are finger safe up to an IP20 grade of protection,
and the 10x85mm features a p ull out, pivoting
fuse carrier.
Features/Benefits: Applications:
• Bus bar termination clamp • All photovoltaic applications
• UL94V0 Material • Combiner box applications
Flammability Rating
• Wire terminal for use
with 90°C wire
• Wire range:
6 – 14 AWG stranded,
10 – 14 AWG solid,
Copper wire only
• IP20 Finger Safe
• Din Rail Mounting
• Recommended fuse usage:
HP15M
Ratings:
• Volts: 1500VDC Maximum
• SCCR: 50kA
Approvals:
• UL Recognized Component,
evaluated to UL 4248-18
• Evaluated to IEC60269-1
4248-18
PV-rated Switches
100A to 500A Up to 1000VDC
Mersen offers a range of DC disconnect switches
specially designed for PV applications, in 2 poles
and 2x2 poles configurations for double circuit
applications. The technology inside the switch
and the visible contacts allow a quick, safe, and reliable
DC breaking power at all current levels up to 1500VDC.
The product is ready and simple to install
independently of the polarity, with very limited
power losses, and with a 40% smaller footprint
than competition. The 1000V versions have 2
switching modules (poles) and the 1500V versions
have 3 modules.
Switch Body AMPERE RATING 100 160 200 250 315 400 500
1000VDC 2-pole Configuration MD100E11 MD160E11 MD200E11 MD250E11 MD315E11 MD400E11 MD500E11
1000VDC 2x2-pole Configuration MD100E22 MD160E22 MD200E22 MD250E22 MD315E22 MD400E22 MD500E22
1500VDC 3-pole Configuration MD315EV12 MD400EV12 MD500EV12
1500VDC 2x3-pole Configuration MD315EV33 MD400EV33 MD500EV33
SHAFTS
Shaft—SPAxxx
SPA130, SPA210, SPA290, SPA360, SPA430 SFB185, SFB280, SFB325, SFB395, SFB535
(xxx = length in mm)
HB65
AUXILIARY CONTACTS*
NO Right side mounting OA1G10 OA1G10 OA1G10 OA1G10 OA1G10 OA1G10 OA1G10
Accessories NC left side mounting OA3G01 OA3G01 OA3G01 OA3G01 OA3G01 OA3G01 OA3G01
Module for SF aux. contacts OEA28 OEA28 OEA28 OEA28 OEA28 OEA28 OEA28
OA1G01 *Rated 2A max continous @690VAC
OA1G10
OEA28
For MDxxxE22 and EV33 JUMP500-2 JUMP500-2 JUMP500-2
For MDxxxE11, E22, EV12** JUMP250 JUMP250 JUMP250 JUMP250 JUMP500 JUMP500 JUMP500
**Shipped with one link per circuit
JUMP500 JC500
TERMINAL SHROUDS FOR LUGS
SHAFTS
AUXILIARY CONTACTS*
Accessories NO Right side mounting OA1G10 OA1G10 OA1G10 OA1G10 OA1G10
NC left side mounting OA3G01 OA3G01 OA3G01 OA3G01 OA3G01
OA1G01 Module for SF aux. contacts OEA28 OEA28 OEA28 OEA28 OEA28
OA1G10
*Rated 2A max continous @690VAC
JC500-2
MD100U11 DC Switch 100A UL 2p X1043231 HB65 Handle black65mm IP65 NEMA 3R W1043368
MD180U22 DC Switch 180A UL 4p Y1043232 HB65X Handle black 65mm IP65 NEMA 4X X1043369
MD200U11 DC Switch 200A UL 2p Z1043233 HB95 Handle black 95mm IP65 NEMA 3R N1043913
MD250U11 DC Switch 250A UL 2p A1043234 HB95X Handle black 95mm IP65 NEMA 4X P1043914
MD250U22 DC Switch 250A UL 4p B1043235 HB125 Handle black 125mm IP65 NEMA 3R A1043372
MD320U11 DC Switch 320A UL 2p C1043236 HB125X Handle black 125mm IP65 NEMA 4X B1043373
MD320U22 DC Switch 320A UL 4p D1043237 HR65 Handle red 65mm IP65 NEMA 3R G1043378
MD400U11 DC Switch 400A UL 2p E1043238 HR65X Handle red 65mm IP65 NEMA 4X H1043379
MD400U22 DC Switch 400A UL 4p F1043239 HR95 Handle red 95mm IP65 NEMA 3R S1043917
MD250UV12 DC Switch 250A UL 1500V 3p L1050926 HR95X Handle red 95mm IP65 NEMA 4X T1043918
MD320UV12 DC Switch 320A UL 1500V 3p M1050927 HR125 Handle red 125mm IP65 NEMA 3R K1043381
MD400UV12 DC Switch 400A UL 1500V 3p N1050928 HR125X Handle red125mm IP65 NEMA 4X L1043382
HDD250 Handle direct MD100-250 G1047794
HDD400 Handle direct MD315-500 H1047795
MD100E11 DC Switch 100A IEC 1000V 2p G1043217 SFB280 Shaft SwitchFuse 12x12x280mm F1043423
MD160E11 DC Switch 160A IEC 1000V 2p H1043218 SFB325 Shaft SwitchFuse 12x12x325mm G1043424
MD200E11 DC Switch 200A IEC 1000V 2p J1043219 SFB395 Shaft SwitchFuse 12x12x395mm H1043425
MD250E11 DC Switch 250A IEC 1000V 2p K1043220 SPA130 Shaft pistol handle 6x6x130mm V1043919
MD100E22 DC Switch 100A IEC 2x1000V 4p L1043221 SPA210 Shaft pistol handle 6x6x210mm P1043431
MD160E22 DC Switch 160A IEC 2x1000V 4p M1043222 SPA290 Shaft pistol handle 6x6x290mm Q1043432
MD200E22 DC Switch 200A IEC 2x1000V 4p N1043223 SPA360 Shaft pistol handle 6x6x360mm W1043920
MD250E22 DC Switch 250A IEC 2x1000V 4p P1043224 SPA430 Shaft pistol handle 6x6x430mm X1043921
MD315E11 DC Switch 315A IEC 1000V 2p Q1043225
MD400E11 DC Switch 400A IEC 1000V 2p R1043226
MD500E11 DC Switch 500A IEC 1000V 2p S1043227
Terminal Shrouds
MD315E22 DC Switch 315A IEC 2x1000V 4p T1043228 PART # DESCRIPTION REF #
MD400E22 DC Switch 400A IEC 2x1000V 4p V1043229 TS250-14 Term.shrd 250A switch 1p L/4 A1043464
MD500E22 DC Switch 500A IEC 2x1000V 4p W1043230 TDS400 Term.shrd MD250-500 1p L/1 A1045534
MD315EV12 DC Switch 315A IEC 1500V 3p C1050918 TDS250S Term.shrd MD100-250 1p S /1 Z1045533
MD400EV12 DC Switch 400A IEC 1500V 3p D1050919
MD500EV12 DC Switch 500A IEC 1500V 3p E1050920
MD315EV33 DC Switch 315A IEC 2x1500V 6p F1050921
Jumpers
MD400EV33 DC Switch 400A IEC 2x1500V 6p G1050922 PART # DESCRIPTION REF #
MD500EV33 DC Switch 500A IEC 2x1500V 6p J1050924 JUMP250 Jumper bar for 250A DC switch F1043469
JUMP500 Jumper bar for 500A DC switch G1043470
JUMP500-2 Jumper bar for 1500V E33 S1051300
JC250 Jumper cover for JUMP250 H1043471
JC500 Jumper cover for JUMP500 J1043472
JC500-2 Jumper cover for JUMP500-2 V1051302
HelioProtection® Fuse
HP10NH 1000VDC SOLAR
FARMS
A F
E G G
Plain blade
B
dimensions D H
O
(mm)
= = N
C
A
F
Direct
mounting B D H I
dimensions J
O
(mm) C
K
L
M
N
A B C D E F G H I J K L M N O
HelioProtection® Fuse
HP12NH – 1250VDC SOLAR
FARMS
A F
E G G
Plain blade
dimensions B
D
N
H
(mm)
= = M
C
F
A
Direct
H I N
mounting B D
J
= =
dimensions K
(mm) C
L
M
A B C D E F G H I J K L M N
HelioProtection® Fuse
HP15NH – 1500VDC SOLAR
FARMS
Features/Benefits: Applications:
• Global acceptance • All photovoltaic applications Approvals:
• Low fault current interrupting • Inverter DC input protection
capability
• IEC 60269-6
• Re-combiner applications
• Temperature cycle withstand (sub combiner, array
capability combiner, master combiner)
• UL 2579
• Durable construction for
enhanced system longevity
• RoHS compliance
• High efficiency with low
power losses
A
E F
G G
Plain blade
dimensions B
D
(mm) H
= K =
C N
A F
R R
= =
Direct
mounting
ØI
B D
dimensions H
(mm) J
K
C L
M
N
A B C D E F G H I J K L M N
Photovoltaic Fuse-holders
1000VDC
NH fuse-bases for NH fuse-links gPV 1000VDC, size 1, 250A, single pole
RATED IMPULSE
CATALOG REFERENCE POWER
WITHSTAND DESIGN PACKAGE
NUMBER NUMBER ACCEPTANCE
VOLTAGE Uimp
HPBB11PPR
HPBB21PPR
NH fuse-base for short NH fuse-links gPV, sizes 1, type PP, open design (dimensions in mm)
66 122,5
60
32
250
146
81
25
209
Ø 20,5
176
Ø 10,5
M 10
35
126 In case of multipole units in parallel
30
80
without barriers a distance of 8mm must
192
be considered between the live parts of
258 the fuses.
NH fuse-base for short NH fuse-links gPV, sizes 2, type PP, open design (dimensions in mm)
66 122.5
60
35
250
146
25
81
225
201
Ø 10
Ø 20.5
M 10
35
126 In case of multipole units in parallel
30
89
without barriers a distance of 8mm must
192
be considered between the live parts of
258 the fuses
NH fuse-base for short NH fuse-links gPV, sizes 1, type PP with touch protection (dimensions in mm)
87
67,2
32
80
10
6 Ø
111,5
25
146
25
137
176
209
250
35,6
81
30 20,5
18
Ø
10,5
M 10
2
60 35 25
115
122,5
NH fuse-base for short NH fuse-links gPV, sizes 2, type PP with touch protection (dimensions in mm)
87
35
67,2
89
6
10
250
35,6
Ø
18
146
115
20,5 25
25
81
30
145
201
225
Ø
10,5
2,5
60 M 10
115 35 25
122
Photovoltaic Fuse-holders
1500VDC - open version
Open Fuse bases for NH long fuse-links gPV up to 1500VDC, 1 pole, SCCR 50kA
RATED IMPULSE
CATALOG REFERENCE POWER
WITHSTAND RATING DESIGN PACKAGE
NUMBER NUMBER ACCEPTANCE
VOLTAGE Uimp
SP36121 B1026353 59 8kV 250 open design, screw mounting, for NH1Xl fuse link 1
SP36122-123 P1025054 95 8kV 630 open design screw mounting, for NH2Xl and NH3L fuse links 1
8,5
35 14
270,5
250,5
302,5
2 holes Ø 8,5
125,5
109
6
57 14
8,5
15
230,5 10 54
10
11
40
Dimensions SP36122-123
213
155
10
8,5
14
6
284
264
115
316
2 holes Ø 8,5
109
14
57
15
8,5
10
220 54
10
11
40
Photovoltaic Fuse-holders
1500VDC - protected version
Protected fuse-bases for NH long fuse-links gPV up to 1500VDC, one pole, SCCR 15kA
RATED IMPULSE
CATALOG REFERENCE POWER
WITHSTAND RATING DESIGN PACKAGE
NUMBER NUMBER ACCEPTANCE
VOLTAGE Uimp
* can accept Mersen gPV fuse-links size 121 and NH2XL rated 250A with derating.
** can accept NH3L fuses up to 630A with derating. A
mind.6
106
Ø 10,5
30
HPBB1XL1PPFS
270
188
148
25
10
NH-1XL
106
Schnitt A-A 47 30 60
mind. 6
97,6 60 A
101,5
131
HPBB2XL3LPPFS
Ø10,5
216,9
135
299
165
15,7
25
30
108
36
20 48 30 21 mind. 6
147 80,7
68
Ø 10,5
215,4
HPBB2XL3LPBFS
135
165
131
25
265
15,7
30
108
36
20 48 30
147 80,7
Reversible installation
• Reversible chassis to allow
Wide range cable entry from above or
• Ucpv up to 1500VDC below
Approvals/standards
• UL 1449
• EN-50539-11
STP T2 40 PV Imax
STP T2 40 Imax
90 mm
mm 70
17,5 mm
65 m L1 L2 24V+ TRX+ TRX- GND
mm m
PE
18
90 mm
86 mm
- 8946 - BR-HELIO-FR-011-0616
EP.MERSEN.COM