Effective Date 01.04.

2019
Delta Electronics India Pvt Ltd, Page No. Page 1 of 3
Bangalore Document No. D2.5K HV-31
Auxiliary Power Design Specifications Approved by VK/PR

DelCEN 2500 HV
Auxiliary Power Design Specifications
Principal of Operation:
The Auxiliary Transformer also called as Isolation Transformer is used to take the 3 phase power from the LV side
(600V ±10%) of the Grid transformer having 5 to 8% Voltage THD (Total Harmonic Distortion) and feed the power to
Auxiliary loads used within the 2.5MW Solar Central Inverter like pump, Heat exchanger cooling fans, cabinet fans,
Heaters, SMPS etc. The 600V primary side of the Grid transformer is connected to the Solar Inverter output which is a
3 phase PWM controlled IGBT based Inverter. The isolation transformer is placed inside the inverter panel. The input
impedance of the Isolation Transformer is such that the secondary Voltage THD should be <1%. This is a very
important spec that have been met. The SLD of the same is given in Fig. 1.

Fig. 1
Load Calculations:

Sl.
Components Description Remarks In kW In kVA
No

When Heater will "ON" other circuit in


1 Heater 250W 0.5 ---
"OFF" condition

2.8A full load during ACB ON/OFF, but


2 Aux power supply Normal condition load: 100W. due to that 0.1 0.13
0.584A is considered

3 Heat exchanger 2.2KW, PF=0.65 2.2 3.39

4 Cooling Pump 2.2KW, PF=0.65 2.2 3.39

Fans 11" for IP54 Fan "I":-0.59A PF:- 0.88 , P:-119W 1.428 1.623
5
Fans 6" for IP65 + Stack Fan "I":-0.25A,PF:-0.73, P:- 42W 0.42 0.575

This document is the property of Delta Electronics India Pvt Ltd and cannot be used by, or given to, other parties without prior authorisation
Effective Date 01.04.2019
Delta Electronics India Pvt Ltd, Page No. Page 2 of 3
Bangalore Document No. D2.5K HV-31
Auxiliary Power Design Specifications Approved by VK/PR

Sl.
Components Description Remarks In kW In kVA
No

1 DC Contactor, CB, Light, Pump Contactor, Considered average Current is 1A due to


6 --- ---
grounding contactor, pre charge. Opening time in (ms).

7 2 DC contactor, 4 heat Exchange contactor --- --- ---

8 Air-con 800W --- 0.8 0.8


9 230V power for zone monitoring solution --- --- ---

Inrush and continuous. ( only one ACB will


10 ACB Motor 0.115 0.115
consider for load current)

1F4 MCB: Considered for 1F4 and Aux transformer design. 7.263 10.023
Due to fan additional add buffer reduced to 8.88% --- 0.88

Auxiliary Transformer kVA design: --- 10.903

Total kVA rating = 11 kVA (Excluding Power sockets for external tools usage).

Electrical specifications:

Standards DIN EN 60938-2/DIN EN 60938-1/DIN EN 60076-6


Type 3ɸ Isolation Cum Auxiliary Transformer
Primary Windings 600V, 3ɸ, Delta connected
Secondary windings 400V, 3ɸ, Star connected
Frequency 50 Hz +/-2% (fundamental)
Nominal power 11KVA
Shielding To be grounded
Type of grounding Chassis to be grounded
Insulation level 2.5kV
Lightning current test DIN EN 60076-4
Uneven loading of the phases 30%
Frequent over currents See load table for inrush currents
Frequent periodic overload See load table for load duty
Exceptional operating conditions Converter operation
Maximum dV/dt 9000 V/µs
Voltage THD at primary side 5% to 8%
Voltage THD required at full load at secondary/load side 1% max, key input to design input impedance
Max. current THD 3%

This document is the property of Delta Electronics India Pvt Ltd and cannot be used by, or given to, other parties without prior authorisation
Effective Date 01.04.2019
Delta Electronics India Pvt Ltd, Page No. Page 3 of 3
Bangalore Document No. D2.5K HV-31
Auxiliary Power Design Specifications Approved by VK/PR

Thermals:

Natural air cooled. There is no forced air cooling for this isolation transformer.
The transformer (without any enclosure of its own) is placed inside IP54 cabinet
Cooling
along with other converter parts. The ambient temperature around the
transformer is 60°C.
Winding material copper
Core Material is vendor defined but selected to minimize the size of the transformer
Temperature class Class H (180°C)
Maximum altitude 2000 m
Maximum ambient temperature 60 °C
Sleeves at termination Silicon coated fiber glass (UL 94-V0)
Flammability rating As per UL94-V0

Mechanics:

Length, width and height 350 x 200 x 350mm


The transformer is mounted on base plate. Hence L channels needs to be provided at
Mounting
the base of the Transformer
Enclosure No enclosure is required for the transformer
Weight 79kg
Termination Primary 3 No’s of Terminal blocks for 3 phases, wire size: 6mm² with labels for identifications
Termination: 5 No’s of Terminal blocks for 3 phases, 1 Neutral and 1PE. size: 6mm² with labels for
Secondary identifications

Tests:

Routine Test DIN EN 61558-1


Type Test As Applicable

Notes:
1. The Peak Efficiency value of 99.25% of 2.5MW Inverter is derived including the Auxiliary Power consumption.
2. External Auxiliary Transformer can be provided as optional in a separate cubicle for higher capacity
requirements.