STANDARD
50 MM 50 MM Material - Aluminium
Thickness - 2mm
Distance - 2.5mtr.
25 MM
25 MM
TO FEEDER NAME TO FEEDER NAME
33KV CKT-1 33KV CKT-2
1. IS 1255: 1983
2. Central Electricity Authority (Measures relating to Safety and Electric
Supply) Regulations, 2010.
The utmost care shall be taken to avoid the contamination of the physical and biological
ID TAG CABLE components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
ID TAG
Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
environmental processes are adversely affected.
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
3M 2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
4.Statitutory measures to be taken for pandemic like covid-19 or others.
02.12.2022 00
3M
ISSUED BY: PG
NTS 1 OF 1 TPCODL-SID-HVD-0002 00
PO/RO/SCHEME No. STANDARD
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
4.Statitutory measures to be taken for pandemic like covid-19 or others.
LDPE sheet of 100microns thick
02.12.2022 00
ISSUED BY: PG
NTS 1 OF 1 TPCODL-SID-EHV-0003 00
PO/RO/SCHEME No. STANDARD
A
50 600
20 1. All Dimensions are in mm.
10 deg
6MM MS ROD 2.Grade of concrete shall be M20.
230
4.All letter shall be engraved with height and width as shown in the
75
drawing with 4mm depth.
5. Colour - Red
50
230 6. The upper side of each cable cover shall be marked by means of
25
SECTION -AA'
REINFORCEMENT DETAIL
1. IS 5820: 1970
600
40 46
46 16 600
75
TPCODL 33KV 50
60
The utmost care shall be taken to avoid the contamination of the physical and biological
components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
230
Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
24
ELEVATION
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
22
02.12.2022 00
ISSUED BY: PG
NTS 1 OF 1 TPCODL-SID-EHV-0005 00
LEGEND:-
B
4 Nos-8 diameter stirrups
75 300 500
50
25
R1
150
70
5 28
TPCODL 8
310
33KV CABLE IMPORTANT NOTES:-
225
450
6 Nos-8 diameter bar
2. Cable route marker shall be at an interval of 200 mtr. and also at turning point of the power cable route
ROUTE
3. Route/ Joint marker shall be installed approximate. 500 mm away from the cable route towards the
footpath.
800
800
4. Whenever there is a joint in the route , joint marker shall be used.
140
000mm
650
5. In case of "joint marker" the word "joint" shall be engraved in place of route in front view.
200
FGL FGL
6. High yield strength deformed bars (Fe-415) conforming.
7. Grade of concrete shall be M-25 for the route marker
8. Clear cover to all reinforcement shall be 25 mm
.
9. All letter`s shall be engraved with height and width as shown in the drawing with 5mm depth.
200
350
10. The marker shall be painted with yellow as base colour and letters with black colour.
400
11. All paints used shall be weather proof and not fade within when exposed to U-V light for minimum 5 years.
12. Front side letters of marker-each letter of first row shall occupy 40mm wide space with a gap of 16 mm
25
200
between adjacent letters.
B 120 13. Front side letters of marker-each letter of first row shall occupy 20mm wide space with a gap of 8mm
between adjacent letters.
50
125 125
14. Back side letters of the marker-each letter of first row shall occupy 20mm wide space with a gap of 8mm
25 25
PCC 1:4:8 between adjacent letters the danger mark shall be engraved.
SECTION A-A SECTION B-B 15. Back side letters of marker-each letter of second row on back shall occupy 15mm wide space with a gap of
7mm between adjacent letters or else as specified in the drawing
450
FRONT ELEVATION 16. Approximate distance from the nearest cable to be painted on the marker according to the site below to
the arrow.the direction of arrow to be painted as per site each letter of this row shall occupy 15mm wide
450 & SECTION C-C space with a gap of 7mm between adjacent letters
300
300 U/G CABLE
4 Nos-8 diameter stirrups 75 75
120
500
75
ENVIRONMENTAL NOTES:-
The utmost care shall be taken to avoid the contamination of the physical and biological components of the
6 Nos-8 diameter bar earth/atmosphere system (such as leakage of SF6 gas, Spillage of Transformer oil, scrapping of plastic/electronic
A A
270
120
PLAN material etc.) to such an extent that normal environmental processes are adversely affected.
REINFORCEMENT DETAIL
U/G CABLE
75
C C
Marker 200 Thick CC 1:4:8 SAFETY NOTES:-
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
PLAN installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
4.Statitutory measures to be taken for pandemic like covid-19 or others.
Danger mark
Letters Engraved Engraved Letters Engraved
300 300
45
16 105 16
70
70
40 97 40
20 20 60
TPCODL TPCODL
103
20 4020 20 60
8 8
250
28 28
270
8 20 8 8
33KV CABLE 20 33KV CABLE 20
40 40
30 20 30
40
TPCODL shall be written here.
30 CONT ACT NO &OFC 30
450
JOINT
40
40
10
10
ROUTE
20
000mm 60 60
All Dimensions are in MM and Weights are in KG unless Specified.
140
for centre line of route marker to
0000mm be painted by erection BA.
FGL FGL FGL FGL FGL FGL
02-12-2022 00
350
350
350
NTS 1 OF 1 TPCODL-EHV-0004 00
PO/RO/SCHEME No. STANDARD
A A B B
TPCODL
Ø775
Ø780
Ø760 Ø780
Ø830 Ø760
Ø885 Ø830 Ø930
Ø995 Ø1105
SECTION A-A D D
SECTION C-C Environmental Notes:
The urmost care shall be taken to avoid the contamination of the
physical and biological components of the earth/atmosphere
system (such as leakage of SF6 gas, spillage of transformer oil,
Ø995
scrapping of plastic/electronic material etc.,) to such an extent
Ø1105 that normal environmental processes are adversely affected.
safety Notes:
1. All safety precautions i.e.usage of PPEs etc. need to be
PLAN OF BOTTOM RING taken care during the installation/construction.
2. Barricades shall be used if found necessary.
3. warning board to be provided if necessary for safety
measures.
4. statitutory measures to be taken for pandemic like
covid-19 or others.
REVISION STATUS:-
150
SUPPLIER.
DETAIL-Y FGL
3. HOT DIP GALVANIZATION TO BE DONE AFTER FABRICATION.
FGL 4. EARTH PIT SHALL BE MADE OF BRICK & COVER WITH PLASTER AT SIDE INSIDE TIP.
5. PIPE ELECTRODE CONFIRMS TO IS.3043
75x12Mm GI FLAT 6. BRICK MASONARY SHALL BE PLASTERED WITH CEMENT MORTAR (1:4) ON ALL SIDES.
X
250
75
7. EARTH ENHANCEMENT MATERIAL SHALL BE OF MAKE DULY APPROVED. IT SHALL BE AS
250
75 PER IEEE-80 CLAUSE NO. 14.5 (D) BY TPCODL. DATA SHETT OF THE SAME SHALL BE
SUBMITTED SEPARATELY.
8. EARTH ENHANCEMENT MATERIAL OF TPCODL APPROVED MAKE TO BE USED OEM
100
RECOMMENDED MIXING VALUE/RATIO TO BE MENTIONED. TO BE SUBMITTED FOR
X
150
APPROVAL.
75x12Mm GI FLAT (BELOW FGL) 9. INCASE OF ANY DOUBT/CONFUSION IN THE DOCUMENT BA IS ADVISED TO TAKE CLARITY
75
BEFORE EXECUTION.
250
125 125 REFERENCES:
100MM DIA PVC SLEEVES 750 1. IS 1239(part-1) : Specification for steel tubes,tubulars &
other wrought steel fittings.
TO BE FILLED WITH BITUMEN
2. IS 1239 (part-2) : Specification for steel tubes, tubulars &
125
COMPOUND AFTER LAYING OF GI FLAT other steel fittings.
12MM DIA HOLE 3. Is 228 : method for chemical analysis for steels.
AFTER FIXING SURFACE 16MM DIA 4. IS 4736 : Specification for hot dip zinc coating on mild steel
SHALL BE COVERED WITH NUTS & BOLTS tubes.
75
5. IS 4759 : Specification for hot dip zinc coating on structural
40MM DIA 6 MTR BITUMEN OR GREACE
750
steel and other allied products.
150
LONG GI PIPE (HEAVY CLASS) 6. IS 1387 : General requirements for the supply of
metallurgical materials.
7. IS 1608 : Mechanical testing of metals - Tensile strength.
8. IS 4711 : Methods of sampling of steel pipes , tubes and
125
EARTH ENHANCEMENT fittings.
COMPOUND 9. IS 4740 : Code of practice for earthing.
10. IS 10478 : Hot rolled steel strip for welded tubes & pipes.
11. IS 12278 : Method for ring tensile test on metallic tubes.
TOP VIEW 12. IS 3043 : Code of practice for earthing.
13. IS 1367 : Technical Supply conditions for threaded steel
fastners.
14. IS 14394 : Industrial fastners nuts of product Grade C - Hot
Dip Galvanised.
15. IS 2016-1997 : Specification for plain washers.
225 225 16. IS 1730-1989 : Steel plates, sheets, strips and flats for
3000
Prepared by : TITLE:
YR/PGA
INSTALLATION DRAWING AND DETAILS OF EARTH PIPE
ELECTRODE-40MM WITH GOOMTY
Approved by : KCB
500
separately.
6. Earth enhancement material of TPCODL approved make to
be used OEM recommended mixing value/ratio to be
50X6 G.I. STRIP mentioned. to be submitted for approval.
WELDED 7. After welding of all hardwares on electrode complete
arrangement to be hot dip galvanized.
8. IN case of any doubt/confusion in this document,BA is
advised to take clarity before execution.
9. NO extra items shall be paid without prior TPCODL
approval.
150 75
12MM DIA HOLE
Reference:
40mm DIA 6 MTR. 1. IS 1239 (Part1): Specification for Steel Tubes, Tubular's & other wrought steel
LONG GI PIPE (CLASS-C) fittings.
2. IS 1239 (Part2): Specification for Steel Tubes, Tubular's & other steel fittings.
3. IS 228: Method for Chemical analysis of steels.
4. IS 4736 : Specification for Hot dip zinc coating on mild steel tubes
EARTH ENHANCEMENT 5. IS 4759: Specification for Hot dip zinc coating on structural steel and other allied
products.
COMPOUND (REFER NOTE-6)
6. IS 1387: General requirements for the supply of metallurgical materials.
7. IS 1608: Mechanical testing of metals-Tensile Strength.
8. IS 4711: Methods for sampling of Steel pipes, Tubes and fittings.
9. IS 4740: Code of practice for packaging of Steel Tubes.
10. IS 10748: Hot rolled Steel strip for welded tubes & pipes.
11. IS 12278: Method for ring tensile test on metallic tubes.
12. IS 3043-1987: Code of practice for earthing.
3000
13. IS 1367: Technical supply conditions for threaded steel fasteners.
14. IS 14394: Industrial fastners-Nuts of product Grade C- Hot Dip Galvanized.
15. IS 2016:-1997: Specification for plain Washers.
16. IS 1730-1989: Steel plates, sheets, Strips and flats for structural
17. And general Engineering purpose-Dimensions
18. IS 814-2004: covered Electrodes for manual metal Arc Welding of carbon and carbon
Manganese steel- specification.
The utmost care shall be taken to avoid the contamination of the physical and biological
components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
environmental processes are adversely affected.
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
SEE NOTE-6 4.Statitutory measures to be taken for pandemic like covid-19 or others.
06-02-2023 00
50 40 50
140 TATA POWER CENTRAL ODISHA
INSTALLATION DRAWING AND DETAILS DISTRIBUTION LIMITED
OF PIPE ELECTRODE -40mm
PREPARED BY: YR/PGA
INSTALLATION DRAWING AND DETAILS OF PIPE
APPROVED BY: KB ELECTRODE-40MM
ISSUED BY: PG
NTS 1 OF 1 TPCODL-SID-GEN-0002 00
PO/RO/SCHEME No. STANDARD
1000
is follows:
EXCAVATED EARTH during laying : 15D
Adjacent to joint or termination : 15D
HDPE 160mm DIA HDPE 160mm DIA 7.soil to be backfilled and compacted.
COMMON BURNT
1000
1000
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
CLAY COMMON BURNT
installation/construction.
2. Barricades shall be used if found necessary.
(MODULAR) 3. Warning board to be provided if necessary for safety measures.
CLAY 4.Statitutory measures to be taken for pandemic like covid-19 or others.
BRICKS. (MODULAR)
190X90X90 BRICKS.
190X90X90
11kV CABLE
08.12.2022 00 Issued for Scheme/Installation purpose
11kV CABLE
SAND
75
75
SAND
75
D D D DISTRIBUTION LIMITED
450 675 PGA/
PREPARED BY:
SECTION - SINGLE RUN 11kV CABLE LAYING SECTION - DOUBLE RUN 11kV CABLE LAYING YR
TYPICAL DETAIL OF 11 KV CABLE IN
APPROVED BY: KB
EXCAVATED TRENCH
ISSUED BY: PG
NTS 1 OF 2 TPCODL-SID-HV-0001 00
PO/RO/SCHEME No. STANDARD
F.G.L F.G.L
F.G.L F.G.L
1000
Power cable to gas/water main : 0.30 m.
1000
SECTION - FOUR RUN 11kV CABLE LAYING SECTION - THREE RUN 11kV CABLE LAYING
(ROAD CROSSING) (ROAD CROSSING)
1. IS 1255: 1983
2. Central Electricity Authority (Measures relating to Safety and Electric
Supply) Regulations, 2010.
1000
COMMON BURNT COMMON BURNT 1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
CLAY CLAY 2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
(MODULAR) (MODULAR) 4.Statitutory measures to be taken for pandemic like covid-19 or others.
BRICKS. BRICKS.
190X90X90 190X90X90
11kV CABLE 11kV CABLE
75
75
100 100
75
75
100 100
840 650 TATA POWER CENTRAL ODISHA
DISTRIBUTION LIMITED
SECTION - FOUR RUN 11kV CABLE LAYING SECTION - THREE RUN 11kV CABLE LAYING PREPARED BY: PGA/
YR
TYPICAL DETAIL OF 11 KV CABLE IN
APPROVED BY: KB
EXCAVATED TRENCH
ISSUED BY: PG
NTS 2 OF 2 TPCODL-SID-HV-0001 00
LEGEND:-
TEXT DEPTH
B
4 Nos-8 diameter stirrups
75 300 500
50
25
R1
150
70
8
28
5
TPCODL
310
11KV CABLE IMPORTANT NOTES:-
225
450
1. All dimensions are in mm.
6 Nos-8 diameter bar
&OFC
2. Cable route marker shall be at an interval of 200 mtr. and also at turning point of the power cable route
ROUTE 3. Route/ Joint marker shall be installed approximate. 500 mm away from the cable route towards the
footpath.
800
800
4. Whenever there is a joint in the route , joint marker shall be used.
140
000mm
650
5. In case of "joint marker" the word "joint" shall be engraved in place of route in front view.
200
.
9. All letter`s shall be engraved with height and width as shown in the drawing with 5mm depth.
200
350
10. The marker shall be painted with yellow as base colour and letters with black colour.
400
11. All paints used shall be weather proof and not fade within when exposed to U-V light for minimum 5 years.
12. Front side letters of marker-each letter of first row shall occupy 40mm wide space with a gap of 16 mm
25
200
between adjacent letters.
B 120 13. Front side letters of marker-each letter of first row shall occupy 20mm wide space with a gap of 8mm
50
between adjacent letters.
125 125 14. Back side letters of the marker-each letter of first row shall occupy 20mm wide space with a gap of 8mm
25 25 between adjacent letters the danger mark shall be engraved.
PCC 1:4:8
SECTION B-B 15. Back side letters of marker-each letter of second row on back shall occupy 15mm wide space with a gap of
SECTION A-A 7mm between adjacent letters or else as specified in the drawing
450
16. Approximate distance from the nearest cable to be painted on the marker according to the site below to
FRONT ELEVATION the arrow.the direction of arrow to be painted as per site each letter of this row shall occupy 15mm wide
450 & SECTION C-C space with a gap of 7mm between adjacent letters
300
300 U/G CABLE
4 Nos-8 diameter stirrups 75 75
120
500
75
ENVIRONMENTAL NOTES:-
The utmost care shall be taken to avoid the contamination of the physical and biological components of the
6 Nos-8 diameter bar earth/atmosphere system (such as leakage of SF6 gas, Spillage of Transformer oil, scrapping of plastic/electronic
270
120
PLAN material etc.) to such an extent that normal environmental processes are adversely affected.
A A
REINFORCEMENT DETAIL
U/G CABLE
75
C C
Marker 200 Thick CC 1:4:8 SAFETY NOTES:-
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
PLAN installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
4.Statitutory measures to be taken for pandemic like covid-19 or others.
Danger mark
Letters Engraved Engraved Letters Engraved
300 300
45
105
70
70
16 16
40 97 40
103
20 20 60
20 20 60
8 8
TPCODL TPCODL
250
28 28
270
8 20 8 8
40 40
40 40
30 20 30
&OFC
40
40
10
10
JOINT
20
20
ROUTE 60
All Dimensions are in MM and Weights are in KG unless Specified.
000mm 60
200
140
for centre line of route marker to
000 mm0 be painted by erection BA.
FGL FGL FGL FGL FGL FGL
350 03-12-2022 00
350
350
300
TATA POWER CENTRAL ODISHA
INSCRIPTION DETAILS BACK VIEW FOR CABLE INSCRIPTION DETAILS
FOR LETTERS MARKER FOR LETTERS DISTRIBUTION LIMITED
NTS 1 OF 1 TPCODL-SID-HV-0002 00
PO/RO/SCHEME No. STANDARD
900
is follows:
900
HDPE PIPE 160 DIA HDPE PIPE 160 DIA 7.soil to be backfilled and compacted.
2D
D
145 145 155 160 45 160 155
450
675
SECTION -SINGLE RUN 1.1kV CABLE LAYING SECTION - DOUBLE RUN 1.1kV CABLE LAYING
(ROAD CROSSING) (ROAD CROSSING)
1.Central Electricity Authority (Measures relating to Safety and Electric
Supply) Regulations, 2010.
COMMON BURNT 1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
900
900
SAND
75
2D
D DISTRIBUTION LIMITED
450 675 YR/
PREPARED BY:
SECTION - SINGLE RUN 1.1kV CABLE LAYING SECTION - DOUBLE RUN 1.1kV CABLE LAYING PGA
TYPICAL DETAIL OF 1.1 KV CABLE IN
APPROVED BY: KB
EXCAVATED TRENCH
ISSUED BY: PG
NTS 1 OF 1 TPCODL-SID-LV-0001 00
PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT
PROJECT.:
LOA NO.:
CLIENT:
DESIGNED
DRAWN
CHECKED
APPROVED
Lifeline of odisha
CONTRACTOR:
Gupta Power Infrastructure Ltd. SCALE: SHT.
EPC Division
REV.
Cuttack puri Road Bhubaneswar-751006
TITLE: DRG. NO.:
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
GENERAL ARRANGEMENT OF 33Kv FOUR POLE
STRUCTURE WITH 11m GI RS JOIST
SHEET 01 0F 03
AS SHOWN
24/03/2021
EL 24/03/2021
RF
SS TCE.--------------------------------- -
TCE.--- STRUCTURE WITH 11m GI RS JOIST
GENERAL ARRANGEMENT OF 33Kv FOUR POLE
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
GENERAL ARRANGEMENT OF 33Kv FOUR POLE
STRUCTURE WITH 11m GI RS JOIST
SHEET 02 0F 03
AS SHOWN 24/03/2021
EL 24/03/2021
RF
SS TCE.--------------------------------- -
TCE.--- STRUCTURE WITH 11m GI RS JOIST
GENERAL ARRANGEMENT OF 33Kv FOUR POLE
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
GENERAL ARRANGEMENT OF 33Kv FOUR POLE
STRUCTURE WITH 11m GI RS JOIST
SHEET 03 0F 03
AS SHOWN 24/03/2021
EL 24/03/2021
RF
SS TCE.--------------------------------- -
Layout2, CESU, CESU
Layout3, CESU, CESU
Layout3 (2), CESU, CESU
CONSULTING ENGINEERS LIMITED
MUMBAI
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
20
0
1800
150 150
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
DANGER
11000 VOLTS
11000
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
DANGER
20 11000 VOLTS
0 11000
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
DANGER
11000 VOLTS
11000
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
DANGER
11000 VOLTS
11000
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
TYPICAL PILE DETAIL FOR FOUR POLE STRUCTURE OF
ZONE-1 FOR SINGLE & DOUBLE CIRCUIT OHL NETWORK
AS SHOWN
14/04/2022
CV
24/09/2022
RF SP PKR
RK TCE.12137B - CV -3000-DWG-30002 P1
TCE.12137B - CV -3000-DWG-30007 ZONE-2 FOR SINGLE & DOUBLE CIRCUIT OHL NETWORK
TYPICAL PILE DETAIL FOR FOUR POLE STRUCTURE OF
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
TYPICAL PILE DETAIL FOR FOUR POLE STRUCTURE OF
ZONE-2 FOR SINGLE & DOUBLE CIRCUIT OHL NETWORK
AS SHOWN
14/04/2022
CV
24/09/2022
RF SP PKR
RK TCE.12137B - CV -3000-DWG-30007 P1
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
RAIL
QUANTITIES FOR ONE FOUNDATION (WITHOUT OILPIT)
SR NO. DESCRIPTION LENGTH WIDTH HEIGHT TOTAL QTY. UNITS QUANTITIES FOR OIL PIT
1 EXCAVATION 3.4 3.2 1.425 15.504 Cu.M SR NO. DESCRIPTION LENGTH WIDTH HEIGHT TOTAL QTY. UNITS
2 RCC M20 RAFT 2.8 2.6 0.3 2.184 Cu.M 1 EXCAVATION 2*(4.25*0.325+3.2*0.425) 0.475 2.6 Cu.M
3 RCC M20 PEDESTAL 2.4 2 1.97 9.456 Cu.M 2 RCC M20 RAFT 13.3 0.125 0.7 1.16375 Cu.M
4 PCC M10 2.95 2.75 0.1 0.81125 Cu.M 3 RCC M20 PEDESTAL 0.125 0.675 Cu.M
5 SHUTTERING RAFT 10.8 0.3 3.24 Cu.M 4 PCC M10 0.075 0.609 Cu.M
5 SHUTTERING RCC OUTSIDE 13.8 0.7 9.66 Sq.m
6 SHUTTERING PEDESTAL 8.8 1.97 17.336 Cu.M Sq.m
6 SHUTTERING RCC INSIDE 12.8 0.575 7.36
7 SHUTTERING PCC BASE 11.4 0.1 1.14 Cu.M 7 SHUTTERING PCC 14.4 0.075 1.08 Sq.m
8 REFILLING 6.7 Cu.M 8 REINFORCEMENT STEEL 156.57 Kg.
9 REINFORCEMENT STEEL 474.38 Kg REINFORCEMENT DETAIL
LENGTH OF BAR INCLUDING TOTAL UNIT TOTAL
DIA OF NO OF DEVELOPMENT LENGTH,
SR NO. DESCRIPTION BAR RODS HOOKS & LAPS LENGTH WEIGHT WEIGHT
SR NO. DESCRIPTION LENGTH WIDTH HEIGHT TOTAL QTY. UNITS (kg/mtr) (Kg.)
1 BASE PLATE (6NO.S) 0.2 0.2 0.001 18.84 kg 1 WALL (HORIZONTAL RING) 12 4 0.15 13.3 0.15 13.6 0.89 48.42
2 RAIL-52Kg/mtr (2 Nos) 208 kg 2 WALL (VERTICAL) 12 68 0.075 0.6 0.075 0.75 0.89 45.39
FOUNDATION BOLT (4 Nos) kg 3 BASE OUTSIDE PEDESTAL (L) 12 8 0 3.125 0 3.125 0.89 22.25
3 1.44
REINFORCEMENT DETAIL 4 BASE OUTSIDE PEDESTAL (B) 12 6 0 3.525 0 3.525 0.89 18.82
LENGTH OF BAR INCLUDING UNIT TOTAL
NO OF DEVELOPMENT LENGTH,
SR NO. DESCRIPTION DIA OF BAR TOTAL QTY. WEIGHT WEIGHT
RODS HOOKS & LAPS 5 BASE WITHIN PEDESTAL (L) 12 21 0 0.3125 0 0.3125 0.89 5.84
(kg/mtr) (Kg.)
1 RAFT (L) 12 29 0.3 2.52 0.3 3.12 0.89 80.53 6 BASE WITHIN PEDESTAL (B) 12 25 0 0.7125 0 0.7125 0.89 15.85
2 RAFT (B) 12 27 0.3 2.72 0.3 3.32 0.89 79.78 156.57
3 PEDESTAL (VERTICAL) 12 57 0.15 2.19 0.075 2.415 0.89 122.51
PEDESTAL (HORIZONTAL
4 TOP COVER) (L) 12 16 0.3 1.92 0.3 2.52 0.89 35.88
PEDESTAL (HORIZONTAL
5 TOP COVER) (B) 12 14 0.3 2.72 0.3 3.32 0.89 41.37
6 PEDESTAL (HORIZONTAL RING) 12 14 0.15 8.48 0.15 8.78 0.89 109.4
7 BASE PLATE ROD 12 24 0 0.2 0.03 0.23 0.89 4.91
474.38
1.
TATA POWER
m10 (1:3:6)
CENTRAL ODISHA DISTRIBUTION LTD.
Soling
C OD
T P
C OD 33kV L C OD
T P
T P
CABLE
33kV L 33kV L
CABLE CABLE
1250
1250
1250
HDPE PIPE (40MM) Power cable to control cable : 0.20 m.
Power cables to communication cable : 0.30 m.
370
370
HDPE/HUME PIPE
370
100
100
100
33kV CABLE 33kV CABLE
4. Minimum recommended bending radius for 33 kV
is follows:
during laying : 15D
75
75
75
100
Adjacent to joint or termination : 15D
100 100 100 75 250 75
1000 600
1800
5. The sufficient longitudinal distance to be maintained
SECTION ON ORDINARY ROAD MULTIPLE CIRCUIT between two adjacent cable joints.
SECTION ON ORDINARY ROAD DOUBLE CIRCUIT SECTION ON ORDINARY ROAD
(OPEN CUT WITH PIPE) (OPEN CUT WITH PIPE) SINGLE CIRCUIT (OPEN CUT WITH PIPE)
6.The same section (including tiles & warning tape) is applicable
for cable joint bay also. RFID ball marker shall be installed
on each joint.
T P
L
C OD C OD 33kV
CABLE
T P
T P
33kV L 33kV L
CABLE CABLE 5.Warning tape - TPCODL-HVD-0016
G.L G.L G.L G.L
G.L G.L BACK FILLED WITH
BACK FILLED WITH EXCAVATED EARTH 6.Precast concrete cable cover - TPCODL-HVD-0017
EXCAVATED EARTH
WARNING TAPE
WARNING TAPE
The utmost care shall be taken to avoid the contamination of the physical and biological
OFC CABLE WITH components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
HDPE PIPE (40MM) Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
1250
1250
300
300
300
150
150
100
33kV CABLE 2. Barricades shall be used if found necessary.
150
75
75
75
02-12-2022 00
ISSUED BY: PG
NTS 1 OF 1 TPCODL-SID-EHV-0001 00
12 11 10 9 8 7 6 5 4 3 2 1
From Isolator
1CX300 sqmm
H 3000 Insulated Conductor H
A) High Voltage Cabinet
*B) Incoming Terminal
*C) Outgoing Terminal
D) Interrupting Pole
F) High Voltage cabinet earthing points
G) Low voltage control cabinet
2085 ±10
H) Low voltage cabinet earthing points
2200
J) Manual Trip Handle ABB SCOPE
K) Interlock Releasing lever
Q
L) Composite Cable
350 ±5
G M) PT mounting arrangment G
From OH Line N) Incoming Surge arresters
1CX300 sqmm P) Outgoing surge arresters
580
700
Insulated Conductor Q) Isolator
From PT R)Isolator Handle
1CX95 sqmm 760 760 T) Handle Holding Clamp
Insulated N
S)Pole for Recloser Mounting CUSTOMER SCOPE
2300
1950 ±10
Conductor B
D To Outgoing 825 435 *Incoming and outgoing terminals shall be based on
F C Insulated conductor. F
M Note:
From Surge arrester
1Cx95 Sqmm Pole as per Customer drawing No.
470 ±5
Insulated conductor SUP-2010015-JOIST-11-TATA POWER-GA
J Not in ABB Scope.
P
1305
PE1- HV+LV+PT
11000
A
PE2-SA
6825 ±10
7000
K
PE3-ISOLATOR
E T E
394 394
528 ±10
~500
4700
530
4230 ±10
3700
Y
R
D D
Z
G
1770 ±10
1385 ±10
1400
L
S
1800
3000
50
25 12.5
2 Holes
M8
16
B B
2REA054559A0003
ISO 2768 T.1 Lengths and Angle f Thread Quality Tolerance
ISO 2768 T.2 Geometrical Tolerances H. KX L . "6g-6H" ISO 965 © Copyright 2019 ABB. All rights reserved. IP Class 0 Group Technology Management 2/2
12 11 10 9 8 7 6 5 4 3 2 1
CONSULTING ENGINEERS LIMITED
MUMBAI
CONSULTING ENGINEERS LIMITED
MUMBAI
TATA POWER CENTRAL
ODISHA DISTRIBUTION LTD.
PONRAJ G A 09-08-2022
JEEVAN SANGRAM 09-08-2022
KHAJAN BHARDWAJ 09-08-2022
POURUSH GARG 09-08-2022 A1
DRAWING NO : TPCODL-HVD-0009
1-HOLE DIA - 26MM
PONRAJ G A 09-08-2022
JEEVAN SANGRAM 09-08-2022
KHAJAN BHARDWAJ 09-08-2022
POURUSH GARG 09-08-2022
A1
DRAWING NO : TPCODL-HVD-0010
Notes:
1. This particular circuit arrangement only applicable for H pole with
100X270 lacing plate. For H pole with 200X270 Lacing plate different
drawing shall be used.
2. Incase of any discrepancy in dimension and level between drawing.
the contractor shall seek the clarification before proceeding.
3. Any required hole as per drawing need to be done at site.
PONRAJ G A 22-02-2023
SRASTANTH MOHANTY 22-02-2023
KHAJAN BHARDWAJ 22-02-2023
POURUSH GARG 22-02-2023
A1
DRAWING NO : TPCODL-HVD-0014
80,63
PONRAJ G A 15-02-2023
SRASTANTH MOHANTY 15-02-2023
KHAJAN BHARDWAJ 15-02-2023
POURUSH GARG 15-02-2023
A1
DRAWING NO : TPCODL-HVD-0012
33 KV Double Circuit 14MTR.H-POLE
DP STRUCTURE
PONRAJ G A 15-02-2023
SRASTANTH MOHANTY 15-02-2023
KHAJAN BHARDWAJ 15-02-2023
POURUSH GARG 15-02-2023
A1
DRAWING NO : TPCODL-HVD-0012
BOM OF 33KV SINGLE POLE WITH V CROSSARM
ITEM WT WT/ ITEM TOTAL WT.
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
NO (KG/MTR) (KG) (KG)
150x150/ 380.6 /
1 RSJ POLE/ WPB 160 JOIST 13000 1 34.6 / 30.44 449.8/ 395.72
160x152 334.84
2 33KV CROSS ARM 100x50x6 CHANNEL 2071 1 9.56 19.799 19.799
3 FLAT FOR V 65x6 FLAT 65 4 3.06 0.199 0.796
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
FLAT
M16 12 0.014 0.168
WASHER
SPRING
M16 12 0.009 0.108
WASHER
FLAT
M8 4 0.005 0.020
WASHER
SPRING
M8 4 0.002 0.008
WASHER
DANGER
11000 VOLTS
11000
DANGER
11000 VOLTS
11000
All Dimensions are in MM and Weights are in KG unless Specified.
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
33KV LINE SINGLE POLE WITH V PHIROJ UTTARAY, E&Q
CHECKED BY:
CROSS ARM (with 13mtr. 150x150 RSJ or K.C.BHARDWAJ,E&Q
APPROVED BY: P GARG, E&Q
WPB 160)
ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0001 REV NO:
BOM OF 180 DEGREE CUT POINT SINGLE POLE
ITEM WT WT/ ITEM TOTAL WT.
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
NO (KG/MTR) (KG) (KG)
150x150/ 380.6 /
1 RSJ POLE/ WPB 160 JOIST 13000 1 34.6 / 30.44 449.8/ 395.72
160x152 334.84
18x24mm Slot 18mm Hole for STRAIGT CROSS ARM
2 100x50x6 CHANNEL 1700 2 9.56 16.252 32.504
HOLE for Fixing H/W Fittings 3
BOTTOM
FISH PLATE 50x6 FLAT 280 8 2.36 0.661 5.286
50.0000
Nuts 4
STRAISGT CROSS ARM
100x50x6 CHANNEL 306 2 9.56 2.925 5.851
TOP
5 DANGER BOARD 200x6 FLAT 250 1 9.42 2.355 2.355
BACK CLAMP FOR
1no 18mm HOLE 6 25x3 FLAT 510 1 0.59 0.301 0.301
DANGER BOARD
7 STAY CLAMP 50x8 FLAT 551 1 3.14 1.730 1.730
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
TOTAL WT EXCEPT
48.027
POLE
TOP
Fish Plate
50 x 6 x 250mm
FLAT
M16 30 0.014 0.420
WASHER
SPRING
M16 30 0.009 0.270
WASHER
2-18x24mm SLOT
HOLE 2-26mm HOLE 2-18x24 SLOT M8
FLAT
4 0.005 0.020
FOR 33KV GI PIN HOLE WASHER
FOR FISH PLATE
FOR FISH PLATE
SPRING
M8 4 0.002 0.008
WASHER
18mm HOLE 18x24 SLOT HOLE 18x24 SLOT
FOR CENTER BOLT TOTAL WEIGHT 4.879
FOR SIDE BOLT HOLE
FOR SIDE BOLT
DANGER
11000 VOLTS
11000
18mm HOLE
FOR SIDE BOLT
DANGER
11000 VOLTS
11000
All Dimensions are in MM and Weights are in KG unless Specified.
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
33KV LINE SINGLE POLE WITH 180 PHIROJ UTTARAY, E&Q
CHECKED BY:
DEGREE CUT POINT(13mtr. 150x150 K.C.BHARDWAJ,E&Q
APPROVED BY: P GARG, E&Q
RSJ/WPB 160)
ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0002 REV NO:
BOM OF 90 DEGREE CUT POINT SINGLE POLE
18x24mm Slot 18mm Hole for ITEM
NO
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
WT
(KG/MTR)
WT/ ITEM
(KG)
TOTAL WT.
(KG)
HOLE for Fixing H/W Fittings 1 RSJ POLE/ WPB 160
150x150/
160x152
JOIST 13000 1 34.6 / 30.44
380.6 /
334.84
449.8/ 395.72
Nuts 2
STRAIGT CROSS ARM
100x50x6 CHANNEL 1700 4 9.56 16.252 65.008
BOTTOM
3 FISH PLATE 50x6 FLAT 280 16 2.36 0.661 10.573
STRAISGT CROSS ARM
4 100x50x6 CHANNEL 306 4 9.56 2.925 11.701
1no 18mm HOLE TOP
5 DANGER BOARD 200x6 FLAT 250 1 9.42 2.355 2.355
BACK CLAMP FOR
6 25x3 FLAT 510 1 0.59 0.301 0.301
DANGER BOARD
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
Ø26.0000
NUT & BOLTS REQUIRED
STRAISGT
NUT & LENGTH STRAIGT CROSS FISH DANGER STAY TOTAL UNIT WT
CROSS ARM EARTHING TOTAL WT. (Kg)
(mm) (No) (Kg)
Fish Plate
50 x 6 x 250mm
TOP
M16 50 1 1 0.134 0.134
M16 90 3 3 0.188 0.564
M16 150 16 16 0.270 4.320
M16 200 8 6 14 0.331 4.634
M8 70 2 2 0.033 0.066
FLAT
M16 68 0.014 0.952
WASHER
SPRING
M16 68 0.009 0.612
WASHER
FLAT
M8 4 0.005 0.020
WASHER
SPRING
M8 4 0.002 0.008
WASHER
DANGER
11000 VOLTS
11000
DANGER
All Dimensions are in MM and Weights are in KG unless Specified.
11000 VOLTS
11000
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
33KV LINE SINGLE POLE WITH 90 PHIROJ UTTARAY, E&Q
CHECKED BY:
DEGREE CUT POINT(13mtr. 150x150 K.C.BHARDWAJ,E&Q
APPROVED BY: P GARG, E&Q
RSJ/WPB 160)
ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0003 REV NO:
BOM OF GI ITEMS OF 33KV 13MTR INLINE DOUBLE POLE(FOR SPACE CONSTRAINT)
ITEM WT WT/ ITEM TOTAL WT.
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
NO (KG/MTR) (KG) (KG)
150x150/ 449.8/
1 RSJ POLE/ WPB 160 JOIST 13000 2 34.6 / 30.44 899.6/ 791.44
160x152 395.72
2 DP TOP CHANNEL 100x50x6 CHANNEL 3250 2 9.56 31.070 62.140
3 FISH PLATE 50x6 FLAT 280 6 2.36 0.661 3.965
4 CROSS BRACING 75x40x4.8 CHANNEL 1960 5 7.14 13.994 69.972
5 CROSS BRACING 50X50x6 ANGLE 3432 4 4.50 15.444 61.776
6 DANGER BOARD 200x6 FLAT 250 2 9.42 2.355 4.710
BACK CLAMP FOR DANGER
7 25x3 FLAT 510 2 0.59 0.301 0.602
BOARD
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
FLAT
M16 82 0.014 1.148
WASHER
SPRING
M16 82 0.009 0.738
WASHER
FLAT
M8 8 0.005 0.040
WASHER
SPRING
M8 8 0.002 0.016
WASHER
DANGER
11000 VOLTS
11000
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
33KV LINE DP USING 13 MTR 150X150 PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ,E&Q
RSJ/WPB 160(FOR SPACE CONSTRAINT
APPROVED BY: P GARG, E&Q
CASES)
ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0004 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
GUARD WIRE
CROSS-LACING
20
0
3300
150 150
1.
DANGER
11000 VOLTS
11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
33KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: K.C.BHARDWAJ,E&Q
DOUBLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160) ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0005 REV NO:
SHEET: 1 OF 2
BOM OF GI ITEMS OF 33KV ROAD CROSSING ON DOUBLE POLE
ITEM WT WT/ ITEM TOTAL WT.
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
NO (KG/MTR) (KG) (KG)
150x150/ 449.8/ 1799.2/
1 RSJ POLE/ WPB 160 JOIST 13000 4 34.6 / 30.44
160x152 395.72 1582.88
2 DP TOP CHANNEL 100x50x6 CHANNEL 3150 4 9.56 30.114 120.456
3 FISH PLATE 50x6 FLAT 280 12 2.36 0.661 7.930
4 CHANNEL FOR GUARDING 75x40x4.8 CHANNEL 3700 4 7.14 26.418 105.672
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
FLAT
M16 176 0.014 2.464
WASHER
SPRING
M16 176 0.009 1.584
WASHER
FLAT
M8 16 0.005 0.080
WASHER
SPRING
M8 16 0.002 0.032
WASHER
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
33KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: K.C.BHARDWAJ,E&Q
DOUBLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160) ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0005 REV NO:
SHEET: 2 OF 2
POLE STRUCTURE
33KV LINE WITH RSJ 150X150 SINGLE
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
33KV LINE WITH RSJ 150X150 SINGLE
POLE STRUCTURE
AS SHOWN 20/04/2021
EL 20/04/2021
RF
SS -
POLE STRUCTURE
33KV LINE WITH WPB 160X152 SINGLE
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
33KV LINE WITH WPB 160X152 SINGLE
POLE STRUCTURE
CONSULTING ENGINEERS LIMITED
MUMBAI
AS SHOWN 20/04/2021
EL 20/04/2021
RF
SS -
2.5%
NOTES :-
BILL OF MATERIALS
BILL OF MATERIALS
DANGER
11000 VOLTS
11000
DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000
DANGER
11000 VOLTS
11000
All Dimensions are in MM and Weights are in KG unless Specified.
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
DANGER
11000 VOLTS
11000
DANGER
11000 VOLTS
11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
HOLE
30°- 4
5°
DANGER
11000 VOLTS
11000
DANGER
11000 VOLTS
11000
18x24mm SLOT
HOLE 22mm HOLE FOR 18x24 SLOT
FOR FISH PLATE 11KV GI PIN HOLE
FOR FISH PLATE
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
Ø26.0000
DANGER
11000 VOLTS
DANGER
11000
11000
VOLTS 11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
11000
11000
DANGER
VOLTS
11000
11000
DANGER
VOLTS
DANGER
11000 VOLTS
DANGER
11000
11000
VOLTS
11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
DANGER
11000 VOLTS
11000
DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE DP WITH AB SWITCH PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
(with 11mtr. 150x150 RSJ or WPB 160)
APPROVED BY: P GARG, E&Q
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0001 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000
DANGER
11000 VOLTS
11000
All Dimensions are in MM and Weights are in KG unless Specified.
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE DP WITHOUT AB SWITCH PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
(with 11mtr. 150x150 RSJ or WPB 160)
APPROVED BY: P GARG, E&Q
DANGER
11000 VOLTS
11000
DANGER
11000 VOLTS
11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE SINGLE POLE WITH V PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
CROSS ARM (with 11mtr. 150x150 RSJ or
WPB 160) APPROVED BY: P GARG, E&Q
HOLE
30°- 4
5°
DANGER
11000 VOLTS
11000
DANGER
11000 VOLTS
11000
18x24mm SLOT
HOLE 22mm HOLE FOR 18x24 SLOT
FOR FISH PLATE 11KV GI PIN HOLE
FOR FISH PLATE
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE SINGLE POLE CUT POINT 180 PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
DEGREE(with 11mtr. 150x150 RSJ or WPB
160) APPROVED BY: P GARG, E&Q
Ø26.0000
DANGER
11000 VOLTS
DANGER
11000
11000
VOLTS 11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE SINGLE POLE CUT POINT 90 PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
DEGREE(with 11mtr. 150x150 RSJ or WPB
160) APPROVED BY: P GARG, E&Q
DANGER
11000 VOLTS
11000
DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV INTERPOSING LINE DP FOR PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
EXISTING 9MTR 11KV LINE
APPROVED BY: P GARG, E&Q
DANGER
11000 VOLTS
DANGER
11000
11000
VOLTS
11000
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV INTERPOSING POLE HAVING PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
CANTELEVER ARRANGEMENT FOR
9MTR EXISTING 11KV LINE APPROVED BY: P GARG, E&Q
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
11KV LINE WITH WPB 160X152 SINGLE
POLE STRUCTURE
AS SHOWN 31/03/2021
EL 31/03/2021
RF
SS TCE.--------------------------------- -
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
20
0
1800
150 150
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
11KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: PHIROJ UTTARAY, E&Q
K.C.BHARDWAJ, E&Q
SINGLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160)
ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS DRAWING NO: TPCODL-MVD-0009 REV NO:
ISSUE DT: 05/07/2021
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
DANGER
11000 VOLTS
11000
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
11KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: PHIROJ UTTARAY, E&Q
K.C.BHARDWAJ, E&Q
SINGLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160)
ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS DRAWING NO: TPCODL-MVD-0009 REV NO:
ISSUE DT: 05/07/2021
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
DANGER
20 11000 VOLTS
0 11000
1.
TITLE:- NAME
11KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: K.C.BHARDWAJ, E&Q
DOUBLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160) ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0010 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
11KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: K.C.BHARDWAJ, E&Q
DOUBLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160) ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0010 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
DANGER
11000 VOLTS
11000
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
11KV LINE DP USING 13 MTR 150X150 DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
RSJ/WPB 160(FOR SPECIAL CASE OF CHECKED BY: K.C.BHARDWAJ, E&Q
HEIGHT REQUIREMENT AND SPACE APPROVED BY: P GARG, E&Q
CONSTRAINT ) ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0011 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
DANGER
11000 VOLTS
11000
1.
TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE DP USING 11 MTR 150X150 PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
RSJ/WPB 160(FOR SPACE CONSTRAINT
APPROVED BY: P GARG, E&Q
CASES)
ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0012 REV NO:
2.5%
F09(PEG-P-102)
Rev No.00
Eff. Date 01.04.2019
02
01
dd.mm.yyyy 00 XXXXXXXXXXXXXXXXXXXXXXX
XX
XX
ANNEXURE
XX
XX