PO/RO/SCHEME No.

STANDARD

1. All Dimensions are in mm.


2. All letters shall be engraved and painted with acrylic extyerior
grade paint in black colour.

3. The tagshall be tied with cable using 1 sqmm nylon wire.

4. Identification tag to be put on along the cable @ 3m distance at


alternate locationa as shown in the flag.

50 MM 50 MM Material - Aluminium
Thickness - 2mm
Distance - 2.5mtr.

FROM FEEDER NAME FROM FEEDER NAME

25 MM

25 MM
TO FEEDER NAME TO FEEDER NAME
33KV CKT-1 33KV CKT-2

1. IS 1255: 1983
2. Central Electricity Authority (Measures relating to Safety and Electric
Supply) Regulations, 2010.

FOR 3 CORE CABLE FOR 3 CORE CABLE

The utmost care shall be taken to avoid the contamination of the physical and biological
ID TAG CABLE components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
ID TAG

Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
environmental processes are adversely affected.

1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
3M 2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
4.Statitutory measures to be taken for pandemic like covid-19 or others.

02.12.2022 00

3M

TATA POWER CENTRAL ODISHA


ERECTION DIAGRAM (for 3 core twin cable) DISTRIBUTION LIMITED
PREPARED BY: YR/
PGA
IDENTIFICATION TAG EHV CABLE
APPROVED BY: KB

ISSUED BY: PG

NTS 1 OF 1 TPCODL-SID-HVD-0002 00
PO/RO/SCHEME No. STANDARD

1. All Dimensions are in mm.

150 MM DEEP RED COLOURED BACKGROUND


LETTERING IN BLACK

DANGER 33000V TPCODL CABLE 1. IS 1255: 1983


2. Central Electricity Authority (Measures relating to Safety and Electric
Supply) Regulations, 2010.
150 MM

ବିପଦ ୩୩୦୦୦ଭୋଲ୍ ଟିପିସିଓଡିଏଲ କେବଲ୍


The utmost care shall be taken to avoid the contamination of the physical and biological
components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
environmental processes are adversely affected.

1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
4.Statitutory measures to be taken for pandemic like covid-19 or others.
LDPE sheet of 100microns thick

02.12.2022 00

TATA POWER CENTRAL ODISHA


DISTRIBUTION LIMITED
PREPARED BY: YR/
PGA
WARNING TAPE FOR EHV CABLE LAYING
APPROVED BY: KB

ISSUED BY: PG

NTS 1 OF 1 TPCODL-SID-EHV-0003 00
PO/RO/SCHEME No. STANDARD

A
50 600
20 1. All Dimensions are in mm.

2.Reinforcement steel shall confirm to IS : 432( part-1) or IS 1786.


13

10 deg
6MM MS ROD 2.Grade of concrete shall be M20.
230

4.All letter shall be engraved with height and width as shown in the

75
drawing with 4mm depth.

5. Colour - Red

50
230 6. The upper side of each cable cover shall be marked by means of

A impression 4 mmÝeep with words “TPCODL 33KV” “Δ Δ”

25
SECTION -AA'
REINFORCEMENT DETAIL

1. IS 5820: 1970

600

40 46
46 16 600

75
TPCODL 33KV 50
60

The utmost care shall be taken to avoid the contamination of the physical and biological
components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
230

Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
24

environmental processes are adversely affected.

ELEVATION
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
22

PLAN 4.Statitutory measures to be taken for pandemic like covid-19 or others.

02.12.2022 00

TATA POWER CENTRAL ODISHA


DISTRIBUTION LIMITED
PREPARED BY: YR/
PGA
Precast Concrete Cable Cover
APPROVED BY: KB

ISSUED BY: PG

NTS 1 OF 1 TPCODL-SID-EHV-0005 00
LEGEND:-

B
4 Nos-8 diameter stirrups
75 300 500

50
25

R1

150

70
5 28
TPCODL 8

310
33KV CABLE IMPORTANT NOTES:-
225

&OFC 1. All dimensions are in mm.

450
6 Nos-8 diameter bar
2. Cable route marker shall be at an interval of 200 mtr. and also at turning point of the power cable route
ROUTE
3. Route/ Joint marker shall be installed approximate. 500 mm away from the cable route towards the
footpath.
800

800
4. Whenever there is a joint in the route , joint marker shall be used.

140
000mm

650
5. In case of "joint marker" the word "joint" shall be engraved in place of route in front view.
200

FGL FGL
6. High yield strength deformed bars (Fe-415) conforming.
7. Grade of concrete shall be M-25 for the route marker
8. Clear cover to all reinforcement shall be 25 mm

.
9. All letter`s shall be engraved with height and width as shown in the drawing with 5mm depth.
200

350
10. The marker shall be painted with yellow as base colour and letters with black colour.

400
11. All paints used shall be weather proof and not fade within when exposed to U-V light for minimum 5 years.
12. Front side letters of marker-each letter of first row shall occupy 40mm wide space with a gap of 16 mm
25

200
between adjacent letters.
B 120 13. Front side letters of marker-each letter of first row shall occupy 20mm wide space with a gap of 8mm
between adjacent letters.

50
125 125
14. Back side letters of the marker-each letter of first row shall occupy 20mm wide space with a gap of 8mm
25 25
PCC 1:4:8 between adjacent letters the danger mark shall be engraved.

SECTION A-A SECTION B-B 15. Back side letters of marker-each letter of second row on back shall occupy 15mm wide space with a gap of
7mm between adjacent letters or else as specified in the drawing
450
FRONT ELEVATION 16. Approximate distance from the nearest cable to be painted on the marker according to the site below to
the arrow.the direction of arrow to be painted as per site each letter of this row shall occupy 15mm wide
450 & SECTION C-C space with a gap of 7mm between adjacent letters
300
300 U/G CABLE
4 Nos-8 diameter stirrups 75 75
120

500
75

ENVIRONMENTAL NOTES:-
The utmost care shall be taken to avoid the contamination of the physical and biological components of the
6 Nos-8 diameter bar earth/atmosphere system (such as leakage of SF6 gas, Spillage of Transformer oil, scrapping of plastic/electronic
A A
270
120

PLAN material etc.) to such an extent that normal environmental processes are adversely affected.

REINFORCEMENT DETAIL

U/G CABLE
75

C C
Marker 200 Thick CC 1:4:8 SAFETY NOTES:-
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
PLAN installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
4.Statitutory measures to be taken for pandemic like covid-19 or others.
Danger mark
Letters Engraved Engraved Letters Engraved
300 300
45

16 105 16
70

70
40 97 40
20 20 60

TPCODL TPCODL
103

20 4020 20 60
8 8
250

28 28

270
8 20 8 8
33KV CABLE 20 33KV CABLE 20
40 40

30 20 30

40
TPCODL shall be written here.
30 CONT ACT NO &OFC 30
450

JOINT
40

40
10

10
ROUTE
20

000mm 60 60
All Dimensions are in MM and Weights are in KG unless Specified.

Distance of nearest cable


200

140
for centre line of route marker to
0000mm be painted by erection BA.
FGL FGL FGL FGL FGL FGL

02-12-2022 00
350

350

350

300 TATA POWER CENTRAL ODISHA


INSCRIPTION DETAILS
FOR LETTERS
BACK VIEW FOR CABLE
MARKER
INSCRIPTION DETAILS
FOR LETTERS
DISTRIBUTION LIMITED

PREPARED BY: YR/PGA


RCC ROUTE / JOINT MARKER FOR
APPROVED BY: KB
33KV CABLES
ISSUED BY: PG

NTS 1 OF 1 TPCODL-EHV-0004 00
PO/RO/SCHEME No. STANDARD

ERMS NO. Eff. Date

A A B B
TPCODL
Ø775
Ø780
Ø760 Ø780
Ø830 Ø760
Ø885 Ø830 Ø930
Ø995 Ø1105

PLAN PLAN FOR COLLAR COVER SLAB PLAN


NOTES:-

5 Nos. 8mm dia 1. ALL DIMENSION ARE IN MM.


@100 mm c/c 2. CONCRETE SHALL BE M30 GRADE
& REINFORCEMENT SHALL BE
Fe415 GRADE
2 Nos.12mm 3. MINIMUM CONCRETE COVER ON
COVER dia lifting hooks REINFORCEMENT SHALL BE 25MM
C C ALL AROUND.
4. HEIGHT OF RING IS 235MM AND
5 Nos. 8mm dia COLLAR IS 225MM.
@100 mm c/c 5. THICKNESS OF EACH RING 50MM.
6. SPACING OF REBARS FOR ALL
RING SHALL BE 245MM C/C FOR
SECTION B-B TOP AND 300MM C/C FOR BOTTOM.
7. NOS. OF REBARS TO BE VARRY
FROM BOTTOM TO TOP RING.

SECTION A-A D D
SECTION C-C Environmental Notes:
The urmost care shall be taken to avoid the contamination of the
physical and biological components of the earth/atmosphere
system (such as leakage of SF6 gas, spillage of transformer oil,
Ø995
scrapping of plastic/electronic material etc.,) to such an extent
Ø1105 that normal environmental processes are adversely affected.

safety Notes:
1. All safety precautions i.e.usage of PPEs etc. need to be
PLAN OF BOTTOM RING taken care during the installation/construction.
2. Barricades shall be used if found necessary.
3. warning board to be provided if necessary for safety
measures.
4. statitutory measures to be taken for pandemic like
covid-19 or others.
REVISION STATUS:-

06.02.23 0 ISSUED FOR CONSTRUCTION


REV
DATE REVISION
NO.

TATA POWER CENTRAL ODISHA


DISTRIBUTION LIMITED

DRAWN PGA TITLE:-

SECTION D-D CHECKED YR


CABLE LOOP CHAMBER
APPD. KB

ISSUED. PG SHEET DRAWING NO. REV.

SCALE NTS 1 OF 1 TPCODL-SID-EHV-0006 00


PO/RO/SCEME No: STANDARD

FUNNEL WITH C.I COVER WITH HANDLE


WIRE MESH HINGED TO CAST RON FRAME legend:
125 750 125 'A' : SIZE OF GI PIPE ELECTRODE

TEST LINK Important Notes :


1. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED.
2. ALL NECESSARY HARDWARES ARE HOT DIP GALVANIZED AND TO BE PROVED BY

150
SUPPLIER.
DETAIL-Y FGL
3. HOT DIP GALVANIZATION TO BE DONE AFTER FABRICATION.
FGL 4. EARTH PIT SHALL BE MADE OF BRICK & COVER WITH PLASTER AT SIDE INSIDE TIP.
5. PIPE ELECTRODE CONFIRMS TO IS.3043
75x12Mm GI FLAT 6. BRICK MASONARY SHALL BE PLASTERED WITH CEMENT MORTAR (1:4) ON ALL SIDES.
X

250

75
7. EARTH ENHANCEMENT MATERIAL SHALL BE OF MAKE DULY APPROVED. IT SHALL BE AS

250
75 PER IEEE-80 CLAUSE NO. 14.5 (D) BY TPCODL. DATA SHETT OF THE SAME SHALL BE
SUBMITTED SEPARATELY.
8. EARTH ENHANCEMENT MATERIAL OF TPCODL APPROVED MAKE TO BE USED OEM

100
RECOMMENDED MIXING VALUE/RATIO TO BE MENTIONED. TO BE SUBMITTED FOR
X

150
APPROVAL.
75x12Mm GI FLAT (BELOW FGL) 9. INCASE OF ANY DOUBT/CONFUSION IN THE DOCUMENT BA IS ADVISED TO TAKE CLARITY

75
BEFORE EXECUTION.

250
125 125 REFERENCES:
100MM DIA PVC SLEEVES 750 1. IS 1239(part-1) : Specification for steel tubes,tubulars &
other wrought steel fittings.
TO BE FILLED WITH BITUMEN
2. IS 1239 (part-2) : Specification for steel tubes, tubulars &

125
COMPOUND AFTER LAYING OF GI FLAT other steel fittings.
12MM DIA HOLE 3. Is 228 : method for chemical analysis for steels.
AFTER FIXING SURFACE 16MM DIA 4. IS 4736 : Specification for hot dip zinc coating on mild steel
SHALL BE COVERED WITH NUTS & BOLTS tubes.

75
5. IS 4759 : Specification for hot dip zinc coating on structural
40MM DIA 6 MTR BITUMEN OR GREACE

750
steel and other allied products.

150
LONG GI PIPE (HEAVY CLASS) 6. IS 1387 : General requirements for the supply of
metallurgical materials.
7. IS 1608 : Mechanical testing of metals - Tensile strength.
8. IS 4711 : Methods of sampling of steel pipes , tubes and

125
EARTH ENHANCEMENT fittings.
COMPOUND 9. IS 4740 : Code of practice for earthing.
10. IS 10478 : Hot rolled steel strip for welded tubes & pipes.
11. IS 12278 : Method for ring tensile test on metallic tubes.
TOP VIEW 12. IS 3043 : Code of practice for earthing.
13. IS 1367 : Technical Supply conditions for threaded steel
fastners.
14. IS 14394 : Industrial fastners nuts of product Grade C - Hot
Dip Galvanised.
15. IS 2016-1997 : Specification for plain washers.
225 225 16. IS 1730-1989 : Steel plates, sheets, strips and flats for
3000

325 structural and general engineerong purpose dimensions


17. IS 814-2004 : covered electrodes for manual metal Arc
welding of carbon and carbon manganese steel-specification.
6 6
25 50x6 GI FLAT Environmental Notes:
50x6 GI FLAT
45 75 45 45 48.8 25 45 45 75 45
50x6 GI FLAT 50x6 GI FLAT The urmost care shall be taken to avoid the contamination of the
physical and biological components of the earth/atmosphere
system (such as leakage of SF6 gas, spillage of transformer oil,
scrapping of plastic/electronic material etc.,) to such an extent
16 DIA X 50MM LONG GI that normal environmental processes are adversely affected.
BOLTS & NUTS, CHECK NUT
2 WASHERS (TYPICAL) 50X6 GI FLAT BENT TO
SHAPE & WELDED TO PIPE safety Notes:
40MM DIA GI PIPE DETAIL-Y (MORE THAN 50% COVERAGE 1. All safety precautions i.e.usage of PPEs etc. need to be
ON SURFACE AREA) taken care during the installation/construction.
2. Barricades shall be used if found necessary.
3. warning board to be provided if necessary for safety
measures.
75X12MM 75X12MM 4. statitutory measures to be taken for pandemic like
GI FLAT GI FLAT covid-19 or others.
RISER FROM STRUCTURE
Revision status :

50 40 50 06.02.2023 00 ISSUED FOR INSTALLATION PURPOSE


Issued Rev
No.
REMARKS:
140 6 Date:

SECTION X-X TATA POWER CENTRAL ODISHA


DISTRIBUTION LIMITED

Prepared by : TITLE:
YR/PGA
INSTALLATION DRAWING AND DETAILS OF EARTH PIPE
ELECTRODE-40MM WITH GOOMTY
Approved by : KCB

Issued by : PG SHEET: Drawing No. Rev No.

SCALE: NTS 1 of 1 TPCODL-SID-GEN-0001 00


PO/RO/SCHEME No. STANDARD
Rev No.00
ERMS NO. Eff. Date

7/10 1. All dimensions are in mm.


SWG GI WIRE TO 2. All necessary hardware's are hot dip galvanized and to be
EQUIPMENT/STRIP
provided by supplier.
FGL FGL 3. Hot dip galvanization to be done after all fabrication.
4. Pipe electrode confirms to IS:3043.
BACKFILLED WITH 5. Earth enhancement Material shall be of make duly
RIDDLED SOIL approved.IT shall be as per IEEE-80 clause no. 14.5 (d) by
TPCODL. data sheet of the same shall be submitted

500
separately.
6. Earth enhancement material of TPCODL approved make to
be used OEM recommended mixing value/ratio to be
50X6 G.I. STRIP mentioned. to be submitted for approval.
WELDED 7. After welding of all hardwares on electrode complete
arrangement to be hot dip galvanized.
8. IN case of any doubt/confusion in this document,BA is
advised to take clarity before execution.
9. NO extra items shall be paid without prior TPCODL
approval.

150 75
12MM DIA HOLE
Reference:
40mm DIA 6 MTR. 1. IS 1239 (Part1): Specification for Steel Tubes, Tubular's & other wrought steel
LONG GI PIPE (CLASS-C) fittings.
2. IS 1239 (Part2): Specification for Steel Tubes, Tubular's & other steel fittings.
3. IS 228: Method for Chemical analysis of steels.
4. IS 4736 : Specification for Hot dip zinc coating on mild steel tubes
EARTH ENHANCEMENT 5. IS 4759: Specification for Hot dip zinc coating on structural steel and other allied
products.
COMPOUND (REFER NOTE-6)
6. IS 1387: General requirements for the supply of metallurgical materials.
7. IS 1608: Mechanical testing of metals-Tensile Strength.
8. IS 4711: Methods for sampling of Steel pipes, Tubes and fittings.
9. IS 4740: Code of practice for packaging of Steel Tubes.
10. IS 10748: Hot rolled Steel strip for welded tubes & pipes.
11. IS 12278: Method for ring tensile test on metallic tubes.
12. IS 3043-1987: Code of practice for earthing.
3000
13. IS 1367: Technical supply conditions for threaded steel fasteners.
14. IS 14394: Industrial fastners-Nuts of product Grade C- Hot Dip Galvanized.
15. IS 2016:-1997: Specification for plain Washers.
16. IS 1730-1989: Steel plates, sheets, Strips and flats for structural
17. And general Engineering purpose-Dimensions
18. IS 814-2004: covered Electrodes for manual metal Arc Welding of carbon and carbon
Manganese steel- specification.

The utmost care shall be taken to avoid the contamination of the physical and biological
components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
environmental processes are adversely affected.

1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
SEE NOTE-6 4.Statitutory measures to be taken for pandemic like covid-19 or others.

06-02-2023 00

50 40 50
140 TATA POWER CENTRAL ODISHA
INSTALLATION DRAWING AND DETAILS DISTRIBUTION LIMITED
OF PIPE ELECTRODE -40mm
PREPARED BY: YR/PGA
INSTALLATION DRAWING AND DETAILS OF PIPE
APPROVED BY: KB ELECTRODE-40MM

ISSUED BY: PG

NTS 1 OF 1 TPCODL-SID-GEN-0002 00
PO/RO/SCHEME No. STANDARD

F.G.L F.G.L F.G.L F.G.L


1. All Dimensions are in mm.

2. The desired minimum clearances for the cables in ground


as follows:
Power cable to control cable : 0.2 m.
Power cables to communication cable : 0.30 m.
BACK FILLED WITH Power cable to gas/water main : 0.30 m.
EXCAVATED EARTH
3. Minimum recommended bending radii for 11 kV
BACK FILLED WITH
1000

1000
is follows:
EXCAVATED EARTH during laying : 15D
Adjacent to joint or termination : 15D

4. The sufficient longitudinal distance to be maintained between two


adjacent cable joints.

5. Cable route marker shall be at an interval of 200 mtr.and also


at turning point of the power cable.

6.Whenever there is a joint in the route, joint marker shall be used.

HDPE 160mm DIA HDPE 160mm DIA 7.soil to be backfilled and compacted.

11kV CABLE 11kV CABLE 8. (D) Diameter of Cable.

150 150 150 165 150 45 150 165


450
675
SECTION -SINGLE RUN 11kV CABLE LAYING SECTION - DOUBLE RUN 11kV CABLE LAYING
(ROAD CROSSING) (ROAD CROSSING)
1. IS 1255: 1983 (latest amendment)
3. Central Electricity Authority (Measures relating to Safety and Electric
Supply) Regulations, 2010.

F.G.L F.G.L F.G.L F.G.L


BACK FILLED WITH
EXCAVATED EARTH
The utmost care shall be taken to avoid the contamination of the physical and biological
BACK FILLED WITH components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
EXCAVATED EARTH Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
environmental processes are adversely affected.

COMMON BURNT
1000

1000

1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
CLAY COMMON BURNT
installation/construction.
2. Barricades shall be used if found necessary.
(MODULAR) 3. Warning board to be provided if necessary for safety measures.
CLAY 4.Statitutory measures to be taken for pandemic like covid-19 or others.
BRICKS. (MODULAR)
190X90X90 BRICKS.
190X90X90
11kV CABLE
08.12.2022 00 Issued for Scheme/Installation purpose
11kV CABLE
SAND
75
75

SAND

TATA POWER CENTRAL ODISHA


75

75

D D D DISTRIBUTION LIMITED
450 675 PGA/
PREPARED BY:
SECTION - SINGLE RUN 11kV CABLE LAYING SECTION - DOUBLE RUN 11kV CABLE LAYING YR
TYPICAL DETAIL OF 11 KV CABLE IN
APPROVED BY: KB
EXCAVATED TRENCH
ISSUED BY: PG

NTS 1 OF 2 TPCODL-SID-HV-0001 00
PO/RO/SCHEME No. STANDARD

F.G.L F.G.L
F.G.L F.G.L

1. All Dimensions are in mm.


BACK FILLED WITH
EXCAVATED EARTH 2. The desired minimum clearances for the cables in ground
BACK FILLED WITH as follows:
Power cable to control cable: 0.2 m.
EXCAVATED EARTH Power cables to communication cable : 0.30 m.

1000
Power cable to gas/water main : 0.30 m.
1000

3. Minimum recommended bending radii for 11 kV cable is as


follows:
straight run : 15D
Adjacent to joint or termination : 15D

4. Cable route marker shall be at an interval of 200 mtr.


and also at turning point of the power cable route.
HDPE pipe 160mm DIA
5. Whenever there is a joint in the route , joint marker
HDPE 160mm DIA shall be used.
6. soil to be backfilled and compacted.
11kV CABLE
11kV CABLE 7.In case of more than 4 run of trefoil cable, the consecutive
distance between should be followed as mentioned in the drawing.

8.(D) Diameter of Cable.


100 150 50 150 50 100
100 150 50 150 150 50 150 100 150
950 750

SECTION - FOUR RUN 11kV CABLE LAYING SECTION - THREE RUN 11kV CABLE LAYING
(ROAD CROSSING) (ROAD CROSSING)

1. IS 1255: 1983
2. Central Electricity Authority (Measures relating to Safety and Electric
Supply) Regulations, 2010.

F.G.L F.G.L F.G.L F.G.L

BACK FILLED WITH BACK FILLED WITH


EXCAVATED EARTH EXCAVATED EARTH The utmost care shall be taken to avoid the contamination of the physical and biological
components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
environmental processes are adversely affected.
1000

1000

COMMON BURNT COMMON BURNT 1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.
CLAY CLAY 2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
(MODULAR) (MODULAR) 4.Statitutory measures to be taken for pandemic like covid-19 or others.
BRICKS. BRICKS.
190X90X90 190X90X90
11kV CABLE 11kV CABLE
75

75

08.12.2022 00 Issued for Scheme/Installation purpose


SAND SAND

100 100
75

75

100 100
840 650 TATA POWER CENTRAL ODISHA
DISTRIBUTION LIMITED
SECTION - FOUR RUN 11kV CABLE LAYING SECTION - THREE RUN 11kV CABLE LAYING PREPARED BY: PGA/
YR
TYPICAL DETAIL OF 11 KV CABLE IN
APPROVED BY: KB
EXCAVATED TRENCH
ISSUED BY: PG

NTS 2 OF 2 TPCODL-SID-HV-0001 00
LEGEND:-
TEXT DEPTH
B
4 Nos-8 diameter stirrups
75 300 500

50
25

R1

150

70
8
28
5
TPCODL

310
11KV CABLE IMPORTANT NOTES:-
225

450
1. All dimensions are in mm.
6 Nos-8 diameter bar
&OFC
2. Cable route marker shall be at an interval of 200 mtr. and also at turning point of the power cable route
ROUTE 3. Route/ Joint marker shall be installed approximate. 500 mm away from the cable route towards the
footpath.
800

800
4. Whenever there is a joint in the route , joint marker shall be used.

140
000mm

650
5. In case of "joint marker" the word "joint" shall be engraved in place of route in front view.
200

FGL FGL 6. High yield strength deformed bars (Fe-415) conforming.


7. Grade of concrete shall be M-25 for the route marker
8. Clear cover to all reinforcement shall be 25 mm

.
9. All letter`s shall be engraved with height and width as shown in the drawing with 5mm depth.
200

350
10. The marker shall be painted with yellow as base colour and letters with black colour.

400
11. All paints used shall be weather proof and not fade within when exposed to U-V light for minimum 5 years.
12. Front side letters of marker-each letter of first row shall occupy 40mm wide space with a gap of 16 mm
25

200
between adjacent letters.

B 120 13. Front side letters of marker-each letter of first row shall occupy 20mm wide space with a gap of 8mm

50
between adjacent letters.
125 125 14. Back side letters of the marker-each letter of first row shall occupy 20mm wide space with a gap of 8mm
25 25 between adjacent letters the danger mark shall be engraved.
PCC 1:4:8
SECTION B-B 15. Back side letters of marker-each letter of second row on back shall occupy 15mm wide space with a gap of
SECTION A-A 7mm between adjacent letters or else as specified in the drawing
450
16. Approximate distance from the nearest cable to be painted on the marker according to the site below to
FRONT ELEVATION the arrow.the direction of arrow to be painted as per site each letter of this row shall occupy 15mm wide
450 & SECTION C-C space with a gap of 7mm between adjacent letters
300
300 U/G CABLE
4 Nos-8 diameter stirrups 75 75
120

500
75

ENVIRONMENTAL NOTES:-
The utmost care shall be taken to avoid the contamination of the physical and biological components of the
6 Nos-8 diameter bar earth/atmosphere system (such as leakage of SF6 gas, Spillage of Transformer oil, scrapping of plastic/electronic
270
120

PLAN material etc.) to such an extent that normal environmental processes are adversely affected.
A A
REINFORCEMENT DETAIL

U/G CABLE
75

C C
Marker 200 Thick CC 1:4:8 SAFETY NOTES:-
1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
PLAN installation/construction.
2. Barricades shall be used if found necessary.
3. Warning board to be provided if necessary for safety measures.
4.Statitutory measures to be taken for pandemic like covid-19 or others.
Danger mark
Letters Engraved Engraved Letters Engraved
300 300
45

105
70

70
16 16
40 97 40
103
20 20 60

20 20 60
8 8
TPCODL TPCODL
250

28 28

270
8 20 8 8
40 40

40 40
30 20 30

11KV CABLE 20 TPCODL shall be written here.


11KV CABLE 20
30 CONT ACT NO 30
450

&OFC
40

40
10

10
JOINT
20

20

ROUTE 60
All Dimensions are in MM and Weights are in KG unless Specified.

000mm 60
200

Distance of nearest cable

140
for centre line of route marker to
000 mm0 be painted by erection BA.
FGL FGL FGL FGL FGL FGL

350 03-12-2022 00
350

350

300
TATA POWER CENTRAL ODISHA
INSCRIPTION DETAILS BACK VIEW FOR CABLE INSCRIPTION DETAILS
FOR LETTERS MARKER FOR LETTERS DISTRIBUTION LIMITED

PREPARED BY: YR/PGA


RCC ROUTE / JOINT MARKER FOR
APPROVED BY: KB 11KV CABLES
ISSUED BY: PG

NTS 1 OF 1 TPCODL-SID-HV-0002 00
PO/RO/SCHEME No. STANDARD

F.G.L F.G.L F.G.L F.G.L


1. All Dimensions are in mm.

2. The desired minimum clearances for the cables in ground


as follows:
Power cable to control cable : 0.2 m.
Power cables to communication cable : 0.30 m.
BACK FILLED WITH Power cable to gas/water main : 0.30 m.
EXCAVATED EARTH
3. Minimum recommended bending radii for 1.1 kV
BACK FILLED WITH

900
is follows:
900

EXCAVATED EARTH during laying : 12D


Adjacent to joint or termination : 12D

4. The sufficient longitudinal distance to be maintained between two


adjacent cable joints.

5. Cable route marker shall be at an interval of 200 mtr.and also


at turning point of the power cable.

6.Whenever there is a joint in the route, joint marker shall be used.

HDPE PIPE 160 DIA HDPE PIPE 160 DIA 7.soil to be backfilled and compacted.

1.1kV CABLE 1.1kV CABLE 8. (D) Diameter of Cable.

2D
D
145 145 155 160 45 160 155
450
675
SECTION -SINGLE RUN 1.1kV CABLE LAYING SECTION - DOUBLE RUN 1.1kV CABLE LAYING
(ROAD CROSSING) (ROAD CROSSING)
1.Central Electricity Authority (Measures relating to Safety and Electric
Supply) Regulations, 2010.

F.G.L F.G.L F.G.L F.G.L


BACK FILLED WITH
EXCAVATED EARTH
The utmost care shall be taken to avoid the contamination of the physical and biological
BACK FILLED WITH components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
EXCAVATED EARTH Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal
environmental processes are adversely affected.

COMMON BURNT 1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
900

900

CLAY COMMON BURNT


installation/construction.
2. Barricades shall be used if found necessary.
(MODULAR) 3. Warning board to be provided if necessary for safety measures.
CLAY 4.Statitutory measures to be taken for pandemic like covid-19 or others.
BRICKS. (MODULAR)
190X90X90 BRICKS.
190X90X90
1.1kV CABLE
08.12.2022 00 Issued for Scheme/Installation purpose
1.1kV CABLE
SAND
75
75

SAND

TATA POWER CENTRAL ODISHA


75

75

2D
D DISTRIBUTION LIMITED
450 675 YR/
PREPARED BY:
SECTION - SINGLE RUN 1.1kV CABLE LAYING SECTION - DOUBLE RUN 1.1kV CABLE LAYING PGA
TYPICAL DETAIL OF 1.1 KV CABLE IN
APPROVED BY: KB
EXCAVATED TRENCH
ISSUED BY: PG

NTS 1 OF 1 TPCODL-SID-LV-0001 00
PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT

PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT


PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT

PROJECT.:

LOA NO.:

PMA FOR DDUGJY CESU AREA: NAME DATE

CLIENT:
DESIGNED

DRAWN
CHECKED

APPROVED
Lifeline of odisha
CONTRACTOR:
Gupta Power Infrastructure Ltd. SCALE: SHT.
EPC Division
REV.
Cuttack puri Road Bhubaneswar-751006
TITLE: DRG. NO.:

PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT


TCE.--- STRUCTURE WITH 11m GI RS JOIST
GENERAL ARRANGEMENT OF 33Kv FOUR POLE

TP CENTRAL ODISHA
DISTRIBUTION LIMITED
GENERAL ARRANGEMENT OF 33Kv FOUR POLE
STRUCTURE WITH 11m GI RS JOIST
SHEET 01 0F 03

CONSULTING ENGINEERS LIMITED


MUMBAI

AS SHOWN
24/03/2021

EL 24/03/2021

RF

SS TCE.--------------------------------- -
TCE.--- STRUCTURE WITH 11m GI RS JOIST
GENERAL ARRANGEMENT OF 33Kv FOUR POLE

TP CENTRAL ODISHA
DISTRIBUTION LIMITED
GENERAL ARRANGEMENT OF 33Kv FOUR POLE
STRUCTURE WITH 11m GI RS JOIST
SHEET 02 0F 03

CONSULTING ENGINEERS LIMITED


MUMBAI

AS SHOWN 24/03/2021

EL 24/03/2021

RF

SS TCE.--------------------------------- -
TCE.--- STRUCTURE WITH 11m GI RS JOIST
GENERAL ARRANGEMENT OF 33Kv FOUR POLE

TP CENTRAL ODISHA
DISTRIBUTION LIMITED
GENERAL ARRANGEMENT OF 33Kv FOUR POLE
STRUCTURE WITH 11m GI RS JOIST
SHEET 03 0F 03

CONSULTING ENGINEERS LIMITED


MUMBAI

AS SHOWN 24/03/2021

EL 24/03/2021

RF

SS TCE.--------------------------------- -
Layout2, CESU, CESU
Layout3, CESU, CESU
Layout3 (2), CESU, CESU
CONSULTING ENGINEERS LIMITED
MUMBAI
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

PIN OR STRAIN INSULATOR

20
0

1800
150 150
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE PROTECTIVE GUARDING


ACROSS MAJOR ROAD CROSSINGS ON
SINGLE POLE(USING 13MTR
150RSJ/WPB 160)
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE PROTECTIVE GUARDING


ACROSS MAJOR ROAD CROSSINGS ON
SINGLE POLE(USING 13MTR
150RSJ/WPB 160)
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
20 11000 VOLTS
0 11000
1.

3000 TATA POWER


150 150 CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE PROTECTIVE GUARDING


ACROSS MAJOR ROAD CROSSINGS ON
DOUBLE POLE(USING 13MTR
150RSJ/WPB 160)
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE PROTECTIVE GUARDING


ACROSS MAJOR ROAD CROSSINGS ON
DOUBLE POLE(USING 13MTR
150RSJ/WPB 160)
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE DP USING 13 MTR 150X150


RSJ/WPB 160(FOR SPECIAL CASE OF
HEIGHT REQUIREMENT AND SPACE
CONSTRAINT )
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE DP USING 11 MTR 150X150


RSJ/WPB 160(FOR SPACE CONSTRAINT
CASES)
ZONE-1 FOR SINGLE & DOUBLE CIRCUIT OHL NETWORK TCE.12137B - CV -3000-DWG-30002
TYPICAL PILE DETAIL FOR FOUR POLE STRUCTURE OF

TP CENTRAL ODISHA
DISTRIBUTION LIMITED
TYPICAL PILE DETAIL FOR FOUR POLE STRUCTURE OF
ZONE-1 FOR SINGLE & DOUBLE CIRCUIT OHL NETWORK

CONSULTING ENGINEERS LIMITED


MUMBAI

AS SHOWN
14/04/2022

CV
24/09/2022

RF SP PKR

RK TCE.12137B - CV -3000-DWG-30002 P1
TCE.12137B - CV -3000-DWG-30007 ZONE-2 FOR SINGLE & DOUBLE CIRCUIT OHL NETWORK
TYPICAL PILE DETAIL FOR FOUR POLE STRUCTURE OF

TP CENTRAL ODISHA
DISTRIBUTION LIMITED
TYPICAL PILE DETAIL FOR FOUR POLE STRUCTURE OF
ZONE-2 FOR SINGLE & DOUBLE CIRCUIT OHL NETWORK

CONSULTING ENGINEERS LIMITED


MUMBAI

AS SHOWN
14/04/2022

CV
24/09/2022

RF SP PKR

RK TCE.12137B - CV -3000-DWG-30007 P1
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

RAIL
QUANTITIES FOR ONE FOUNDATION (WITHOUT OILPIT)
SR NO. DESCRIPTION LENGTH WIDTH HEIGHT TOTAL QTY. UNITS QUANTITIES FOR OIL PIT
1 EXCAVATION 3.4 3.2 1.425 15.504 Cu.M SR NO. DESCRIPTION LENGTH WIDTH HEIGHT TOTAL QTY. UNITS

2 RCC M20 RAFT 2.8 2.6 0.3 2.184 Cu.M 1 EXCAVATION 2*(4.25*0.325+3.2*0.425) 0.475 2.6 Cu.M
3 RCC M20 PEDESTAL 2.4 2 1.97 9.456 Cu.M 2 RCC M20 RAFT 13.3 0.125 0.7 1.16375 Cu.M
4 PCC M10 2.95 2.75 0.1 0.81125 Cu.M 3 RCC M20 PEDESTAL 0.125 0.675 Cu.M
5 SHUTTERING RAFT 10.8 0.3 3.24 Cu.M 4 PCC M10 0.075 0.609 Cu.M
5 SHUTTERING RCC OUTSIDE 13.8 0.7 9.66 Sq.m
6 SHUTTERING PEDESTAL 8.8 1.97 17.336 Cu.M Sq.m
6 SHUTTERING RCC INSIDE 12.8 0.575 7.36
7 SHUTTERING PCC BASE 11.4 0.1 1.14 Cu.M 7 SHUTTERING PCC 14.4 0.075 1.08 Sq.m
8 REFILLING 6.7 Cu.M 8 REINFORCEMENT STEEL 156.57 Kg.
9 REINFORCEMENT STEEL 474.38 Kg REINFORCEMENT DETAIL
LENGTH OF BAR INCLUDING TOTAL UNIT TOTAL
DIA OF NO OF DEVELOPMENT LENGTH,
SR NO. DESCRIPTION BAR RODS HOOKS & LAPS LENGTH WEIGHT WEIGHT
SR NO. DESCRIPTION LENGTH WIDTH HEIGHT TOTAL QTY. UNITS (kg/mtr) (Kg.)
1 BASE PLATE (6NO.S) 0.2 0.2 0.001 18.84 kg 1 WALL (HORIZONTAL RING) 12 4 0.15 13.3 0.15 13.6 0.89 48.42
2 RAIL-52Kg/mtr (2 Nos) 208 kg 2 WALL (VERTICAL) 12 68 0.075 0.6 0.075 0.75 0.89 45.39
FOUNDATION BOLT (4 Nos) kg 3 BASE OUTSIDE PEDESTAL (L) 12 8 0 3.125 0 3.125 0.89 22.25
3 1.44
REINFORCEMENT DETAIL 4 BASE OUTSIDE PEDESTAL (B) 12 6 0 3.525 0 3.525 0.89 18.82
LENGTH OF BAR INCLUDING UNIT TOTAL
NO OF DEVELOPMENT LENGTH,
SR NO. DESCRIPTION DIA OF BAR TOTAL QTY. WEIGHT WEIGHT
RODS HOOKS & LAPS 5 BASE WITHIN PEDESTAL (L) 12 21 0 0.3125 0 0.3125 0.89 5.84
(kg/mtr) (Kg.)
1 RAFT (L) 12 29 0.3 2.52 0.3 3.12 0.89 80.53 6 BASE WITHIN PEDESTAL (B) 12 25 0 0.7125 0 0.7125 0.89 15.85
2 RAFT (B) 12 27 0.3 2.72 0.3 3.32 0.89 79.78 156.57
3 PEDESTAL (VERTICAL) 12 57 0.15 2.19 0.075 2.415 0.89 122.51
PEDESTAL (HORIZONTAL
4 TOP COVER) (L) 12 16 0.3 1.92 0.3 2.52 0.89 35.88
PEDESTAL (HORIZONTAL
5 TOP COVER) (B) 12 14 0.3 2.72 0.3 3.32 0.89 41.37
6 PEDESTAL (HORIZONTAL RING) 12 14 0.15 8.48 0.15 8.78 0.89 109.4
7 BASE PLATE ROD 12 24 0 0.2 0.03 0.23 0.89 4.91
474.38
1.

TATA POWER
m10 (1:3:6)
CENTRAL ODISHA DISTRIBUTION LTD.
Soling

TITLE:- SRASTANTH MOHANTY, E&Q


PREPARED BY: PONRAJ G A , E&Q
Foundation for 3.15/5MVA
power transformer APPROVED BY: K.C.BHARDWAJ, E&Q

ISSUED BY: P GARG, E&Q


8. Soling of 225 mm thick to be done prior to PCC
SCALE : NTS ISSUE DT: 16/12/2022 DRAWING NO:TPCODL-SID-CIV-0001
PO/RO/SCHEME No. STANDARD
Rev No.00
ERMS NO. Eff. Date

C OD

T P
C OD 33kV L C OD

T P
T P
CABLE
33kV L 33kV L
CABLE CABLE

G.L G.L G.L G.L G.L G.L


1. All Dimensions are in mm.
BACK FILLED WITH
BACK FILLED WITH EXCAVATED EARTH
EXCAVATED EARTH 2. The orientation of R.C.C. Cable cover to be followed
WARNING TAPE as mentioned in the drawing .
WARNING TAPE

3. The desired minimum clearances for the cables in ground


OFC CABLE WITH as follows:
OFC CABLE WITH HDPE PIPE (40MM)

1250
1250

1250
HDPE PIPE (40MM) Power cable to control cable : 0.20 m.
Power cables to communication cable : 0.30 m.

370

370
HDPE/HUME PIPE
370

HDPE/HUME PIPE Power cables to gas/water : 0.30 m.


(200mm DIA)
(200mm DIA)

100

100
100
33kV CABLE 33kV CABLE
4. Minimum recommended bending radius for 33 kV
is follows:
during laying : 15D

75
75

75
100
Adjacent to joint or termination : 15D
100 100 100 75 250 75
1000 600
1800
5. The sufficient longitudinal distance to be maintained
SECTION ON ORDINARY ROAD MULTIPLE CIRCUIT between two adjacent cable joints.
SECTION ON ORDINARY ROAD DOUBLE CIRCUIT SECTION ON ORDINARY ROAD
(OPEN CUT WITH PIPE) (OPEN CUT WITH PIPE) SINGLE CIRCUIT (OPEN CUT WITH PIPE)
6.The same section (including tiles & warning tape) is applicable
for cable joint bay also. RFID ball marker shall be installed
on each joint.

1. IS 1255: 1983 as per latest amendment.


2. Central Electricity Authority (Measures relating to Safety and
Electric Supply) Regulations, 2010 (latest amendment)

3. Route marker DWG - TPCODL-HVD-0014

C OD 4. Identification tag - TPCODL-HVD-0015

T P
L
C OD C OD 33kV
CABLE

T P
T P

33kV L 33kV L
CABLE CABLE 5.Warning tape - TPCODL-HVD-0016
G.L G.L G.L G.L
G.L G.L BACK FILLED WITH
BACK FILLED WITH EXCAVATED EARTH 6.Precast concrete cable cover - TPCODL-HVD-0017
EXCAVATED EARTH
WARNING TAPE
WARNING TAPE
The utmost care shall be taken to avoid the contamination of the physical and biological
OFC CABLE WITH components of the earth/atmosphere system (such as leakage of SF6 gas, Spillage of
HDPE PIPE (40MM) Transformer oil, scrapping of plastic/electronic material etc.) to such an extent that normal

1250
1250

environmental processes are adversely affected.


RCC CABLE COVER
1250

RCC CABLE COVER

300
300
300

OFC CABLE WITH


HDPE PIPE (40MM) 33kV CABLE 1. All safety precautions i.e. usage of PPE's etc. need to be taken care during the
installation/construction.

150
150

100
33kV CABLE 2. Barricades shall be used if found necessary.
150

SAND 3. Warning board to be provided if necessary for safety measures.


4.Statitutory measures to be taken for pandemic like covid-19 or others.
SAND

75
75
75

137 200 200 200 137 137 200 137


137 200 200 200 200 200 200 200 137 1000 600
1800

02-12-2022 00

SECTION FOR MULTIPLE CIRCUIT CABLE SECTION FOR SINGLE CIRCUIT


SECTION FOR DOUBLE CIRCUIT CABLE
LAYING ALONG THE ROAD CABLE LAYING ALONG THE ROAD
LAYING ALONG THE ROAD
TATA POWER CENTRAL ODISHA
DISTRIBUTION LIMITED

PREPARED BY: YR/PGA


33kV CABLE LAYING DRAWING IN EXCAVATED TRENCH
APPROVED BY: KB

ISSUED BY: PG

NTS 1 OF 1 TPCODL-SID-EHV-0001 00
12 11 10 9 8 7 6 5 4 3 2 1

From Isolator
1CX300 sqmm
H 3000 Insulated Conductor H
A) High Voltage Cabinet
*B) Incoming Terminal
*C) Outgoing Terminal
D) Interrupting Pole
F) High Voltage cabinet earthing points
G) Low voltage control cabinet

2085 ±10
H) Low voltage cabinet earthing points

2200
J) Manual Trip Handle ABB SCOPE
K) Interlock Releasing lever
Q
L) Composite Cable

350 ±5
G M) PT mounting arrangment G
From OH Line N) Incoming Surge arresters
1CX300 sqmm P) Outgoing surge arresters

580
700
Insulated Conductor Q) Isolator
From PT R)Isolator Handle
1CX95 sqmm 760 760 T) Handle Holding Clamp
Insulated N
S)Pole for Recloser Mounting CUSTOMER SCOPE

2300

1950 ±10
Conductor B
D To Outgoing 825 435 *Incoming and outgoing terminals shall be based on
F C Insulated conductor. F

M Note:
From Surge arrester
1Cx95 Sqmm Pole as per Customer drawing No.

470 ±5
Insulated conductor SUP-2010015-JOIST-11-TATA POWER-GA
J Not in ABB Scope.
P
1305
PE1- HV+LV+PT
11000

A
PE2-SA

6825 ±10
7000
K
PE3-ISOLATOR
E T E
394 394
528 ±10
~500

4700

530
4230 ±10

3700
Y
R

D D
Z
G
1770 ±10

1385 ±10
1400

L
S

Ground Ground Ground


C level level level C
1800

1800
3000

50
25 12.5
2 Holes
M8

16
B B

PE-1 PE-2 PE-3 Earthing Pad Details Y1:2 F


(HV)
Material Weight
Not applicable kg
H Surface code Surface
mm²
Type Derived from Drawing status
PE1 PE3 Draft
PE2 Revision EC No. Responsible Title Scale
M8
Earthing Bolt
A.006 INABB GA-DOUBLE POLE MOUNTED OVR- 1:50
Location Date Name
15 (U+I) Language

A XXX Drawn IN-NAS 2021/01/28 P.Jadhav Subtitle EN A


Perforated Earthing Pipe Checked . . . OVR-15 SITE INSTALLATION Format
Z1:2
Standard Tolerances for Machining and Forming PROPRIETARY AND SECRET INFORMATION
Coord. punching N.C.Mach. The information contained in this document is to be kept strictly confidential.
and unfold JS11 Any unauthorized use, reproduction, distribution or disclosure is strictly Earthing Connection Diagram Electrode 3 mtr long Approved . . . ASSEMBLY A2
. mX c . v .
forbidden. ABB reserves all rights.
Earthing Bolt Details ABB Switzerland Ltd Drawing No. Sheet No.

2REA054559A0003
ISO 2768 T.1 Lengths and Angle f Thread Quality Tolerance
ISO 2768 T.2 Geometrical Tolerances H. KX L . "6g-6H" ISO 965 © Copyright 2019 ABB. All rights reserved. IP Class 0 Group Technology Management 2/2
12 11 10 9 8 7 6 5 4 3 2 1
CONSULTING ENGINEERS LIMITED
MUMBAI
CONSULTING ENGINEERS LIMITED
MUMBAI
TATA POWER CENTRAL
ODISHA DISTRIBUTION LTD.

33 KV DOUBLE CIRCUIT 13MTR.


H-POLE

PONRAJ G A 09-08-2022
JEEVAN SANGRAM 09-08-2022
KHAJAN BHARDWAJ 09-08-2022
POURUSH GARG 09-08-2022 A1

DRAWING NO : TPCODL-HVD-0009
1-HOLE DIA - 26MM

33 KV Double Circuit 14MTR.H-POLE

PONRAJ G A 09-08-2022
JEEVAN SANGRAM 09-08-2022
KHAJAN BHARDWAJ 09-08-2022
POURUSH GARG 09-08-2022
A1

DRAWING NO : TPCODL-HVD-0010
Notes:
1. This particular circuit arrangement only applicable for H pole with
100X270 lacing plate. For H pole with 200X270 Lacing plate different
drawing shall be used.
2. Incase of any discrepancy in dimension and level between drawing.
the contractor shall seek the clarification before proceeding.
3. Any required hole as per drawing need to be done at site.

1-HOLE DIA - 26MM

33 KV Double Circuit 14MTR.H-POLE


with lacing plate 100X270

PONRAJ G A 22-02-2023
SRASTANTH MOHANTY 22-02-2023
KHAJAN BHARDWAJ 22-02-2023
POURUSH GARG 22-02-2023
A1

DRAWING NO : TPCODL-HVD-0014
80,63

33 KV Double Circuit 14MTR.H-POLE


DP STRUCTURE

PONRAJ G A 15-02-2023
SRASTANTH MOHANTY 15-02-2023
KHAJAN BHARDWAJ 15-02-2023
POURUSH GARG 15-02-2023
A1

DRAWING NO : TPCODL-HVD-0012
33 KV Double Circuit 14MTR.H-POLE
DP STRUCTURE

PONRAJ G A 15-02-2023
SRASTANTH MOHANTY 15-02-2023
KHAJAN BHARDWAJ 15-02-2023
POURUSH GARG 15-02-2023
A1

DRAWING NO : TPCODL-HVD-0012
BOM OF 33KV SINGLE POLE WITH V CROSSARM
ITEM WT WT/ ITEM TOTAL WT.
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
NO (KG/MTR) (KG) (KG)
150x150/ 380.6 /
1 RSJ POLE/ WPB 160 JOIST 13000 1 34.6 / 30.44 449.8/ 395.72
160x152 334.84
2 33KV CROSS ARM 100x50x6 CHANNEL 2071 1 9.56 19.799 19.799
3 FLAT FOR V 65x6 FLAT 65 4 3.06 0.199 0.796
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

4 POLE TOP BRACKET 100x50x6 CHANNEL 120 1 9.56 1.147 1.147


5 DANGER BOARD 200x6 FLAT 250 1 9.42 2.355 2.355
BACK CLAMP FOR
6 25x3 FLAT 510 1 0.59 0.301 0.301
DANGER BOARD
TOTAL WT EXCEPT
24.397
POLE

NUT & BOLTS REQUIRED


NUT & LENGTH POLE TOP DANGER STAY TOTAL UNIT WT
V CROSS ARM EARTHING TOTAL WT. (Kg)
BOLTS (mm) BRACKET BOARD CLAMP (No) (Kg)

M16 50 2 1 3 0.134 0.402


M16 120 3 3 0.229 0.687
M16 200 # 0.331 #####
M8 50 2 2 0.026 0.052

FLAT
M16 12 0.014 0.168
WASHER

SPRING
M16 12 0.009 0.108
WASHER

FLAT
M8 4 0.005 0.020
WASHER

SPRING
M8 4 0.002 0.008
WASHER

TOTAL WEIGHT 1.445

DANGER
11000 VOLTS
11000

DANGER
11000 VOLTS
11000
All Dimensions are in MM and Weights are in KG unless Specified.
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
33KV LINE SINGLE POLE WITH V PHIROJ UTTARAY, E&Q
CHECKED BY:
CROSS ARM (with 13mtr. 150x150 RSJ or K.C.BHARDWAJ,E&Q
APPROVED BY: P GARG, E&Q
WPB 160)
ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0001 REV NO:
BOM OF 180 DEGREE CUT POINT SINGLE POLE
ITEM WT WT/ ITEM TOTAL WT.
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
NO (KG/MTR) (KG) (KG)
150x150/ 380.6 /
1 RSJ POLE/ WPB 160 JOIST 13000 1 34.6 / 30.44 449.8/ 395.72
160x152 334.84
18x24mm Slot 18mm Hole for STRAIGT CROSS ARM
2 100x50x6 CHANNEL 1700 2 9.56 16.252 32.504
HOLE for Fixing H/W Fittings 3
BOTTOM
FISH PLATE 50x6 FLAT 280 8 2.36 0.661 5.286
50.0000

Nuts 4
STRAISGT CROSS ARM
100x50x6 CHANNEL 306 2 9.56 2.925 5.851
TOP
5 DANGER BOARD 200x6 FLAT 250 1 9.42 2.355 2.355
BACK CLAMP FOR
1no 18mm HOLE 6 25x3 FLAT 510 1 0.59 0.301 0.301
DANGER BOARD
7 STAY CLAMP 50x8 FLAT 551 1 3.14 1.730 1.730
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

TOTAL WT EXCEPT
48.027
POLE

NUT & BOLTS REQUIRED


STRAISGT
NUT & LENGTH STRAIGT CROSS FISH DANGER STAY TOTAL UNIT WT
CROSS ARM EARTHING TOTAL WT. (Kg)
BOLTS (mm) ARM BOTTOM PLATE BOARD CLAMP (No) (Kg)
Ø26.0000

TOP
Fish Plate
50 x 6 x 250mm

M16 50 1 1 0.134 0.134


Joist Pole
150 x 150 x 11.8mm Chhanel

M16 90 0 3 3 0.188 0.564

M16 150 4 4 0.270 1.080


30°- 4 M16 200 4 3 7 0.331 2.317

M8 70 2 2 0.033 0.066

FLAT
M16 30 0.014 0.420
WASHER

SPRING
M16 30 0.009 0.270
WASHER

2-18x24mm SLOT
HOLE 2-26mm HOLE 2-18x24 SLOT M8
FLAT
4 0.005 0.020
FOR 33KV GI PIN HOLE WASHER
FOR FISH PLATE
FOR FISH PLATE
SPRING
M8 4 0.002 0.008
WASHER
18mm HOLE 18x24 SLOT HOLE 18x24 SLOT
FOR CENTER BOLT TOTAL WEIGHT 4.879
FOR SIDE BOLT HOLE
FOR SIDE BOLT

DANGER
11000 VOLTS
11000

18mm HOLE
FOR SIDE BOLT

DANGER
11000 VOLTS
11000
All Dimensions are in MM and Weights are in KG unless Specified.
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
33KV LINE SINGLE POLE WITH 180 PHIROJ UTTARAY, E&Q
CHECKED BY:
DEGREE CUT POINT(13mtr. 150x150 K.C.BHARDWAJ,E&Q
APPROVED BY: P GARG, E&Q
RSJ/WPB 160)
ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0002 REV NO:
BOM OF 90 DEGREE CUT POINT SINGLE POLE
18x24mm Slot 18mm Hole for ITEM
NO
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
WT
(KG/MTR)
WT/ ITEM
(KG)
TOTAL WT.
(KG)
HOLE for Fixing H/W Fittings 1 RSJ POLE/ WPB 160
150x150/
160x152
JOIST 13000 1 34.6 / 30.44
380.6 /
334.84
449.8/ 395.72
Nuts 2
STRAIGT CROSS ARM
100x50x6 CHANNEL 1700 4 9.56 16.252 65.008
BOTTOM
3 FISH PLATE 50x6 FLAT 280 16 2.36 0.661 10.573
STRAISGT CROSS ARM
4 100x50x6 CHANNEL 306 4 9.56 2.925 11.701
1no 18mm HOLE TOP
5 DANGER BOARD 200x6 FLAT 250 1 9.42 2.355 2.355
BACK CLAMP FOR
6 25x3 FLAT 510 1 0.59 0.301 0.301
DANGER BOARD
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

7 STAY CLAMP 50x8 FLAT 551 1 3.14 1.730 1.730


TOTAL WT EXCEPT
91.668
POLE

Ø26.0000
NUT & BOLTS REQUIRED
STRAISGT
NUT & LENGTH STRAIGT CROSS FISH DANGER STAY TOTAL UNIT WT
CROSS ARM EARTHING TOTAL WT. (Kg)
(mm) (No) (Kg)
Fish Plate
50 x 6 x 250mm

BOLTS ARM BOTTOM PLATE BOARD CLAMP


Joist Pole
150 x 150 x 11.8mm Chhanel

TOP
M16 50 1 1 0.134 0.134
M16 90 3 3 0.188 0.564
M16 150 16 16 0.270 4.320
M16 200 8 6 14 0.331 4.634
M8 70 2 2 0.033 0.066

FLAT
M16 68 0.014 0.952
WASHER

SPRING
M16 68 0.009 0.612
WASHER

FLAT
M8 4 0.005 0.020
WASHER

SPRING
M8 4 0.002 0.008
WASHER

TOTAL WEIGHT 11.310


2-18x24mm SLOT
HOLE 2-26mm HOLE 2-18x24 SLOT
FOR FISH PLATE FOR 33KV GI PIN HOLE
FOR FISH PLATE

18mm HOLE 18x24 SLOT HOLE 18x24 SLOT


FOR CENTER BOLT
FOR SIDE BOLT HOLE
FOR SIDE BOLT

DANGER
11000 VOLTS
11000

DANGER
All Dimensions are in MM and Weights are in KG unless Specified.

11000 VOLTS
11000
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
33KV LINE SINGLE POLE WITH 90 PHIROJ UTTARAY, E&Q
CHECKED BY:
DEGREE CUT POINT(13mtr. 150x150 K.C.BHARDWAJ,E&Q
APPROVED BY: P GARG, E&Q
RSJ/WPB 160)
ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0003 REV NO:
BOM OF GI ITEMS OF 33KV 13MTR INLINE DOUBLE POLE(FOR SPACE CONSTRAINT)
ITEM WT WT/ ITEM TOTAL WT.
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
NO (KG/MTR) (KG) (KG)
150x150/ 449.8/
1 RSJ POLE/ WPB 160 JOIST 13000 2 34.6 / 30.44 899.6/ 791.44
160x152 395.72
2 DP TOP CHANNEL 100x50x6 CHANNEL 3250 2 9.56 31.070 62.140
3 FISH PLATE 50x6 FLAT 280 6 2.36 0.661 3.965
4 CROSS BRACING 75x40x4.8 CHANNEL 1960 5 7.14 13.994 69.972
5 CROSS BRACING 50X50x6 ANGLE 3432 4 4.50 15.444 61.776
6 DANGER BOARD 200x6 FLAT 250 2 9.42 2.355 4.710
BACK CLAMP FOR DANGER
7 25x3 FLAT 510 2 0.59 0.301 0.602
BOARD
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

8 STAY CLAMP 50x8 FLAT 551 2 3.14 1.730 3.460


9 PIPE EARTHING PIPE 3000 2 0.00 0.000 0.000
TOTAL WT EXCEPT
206.625
POLE

NUT & BOLTS REQUIRED


CROSS CROSS
NUT & LENGTH FISH DANGER STAY TOTAL UNIT WT
DP TOP CHANNEL BRACING BRACING EARTHING TOTAL WT. (Kg)
BOLTS (mm) PLATE BOARD CLAMP (No) (Kg)
CHANNEL ANGLE
M16 50 10 2 12 0.134 1.608
M16 90 6 6 0.161 0.966
M16 200 4 3 16 23 0.331 7.613
M8 70 0 4 4 0.033 0.132

FLAT
M16 82 0.014 1.148
WASHER

SPRING
M16 82 0.009 0.738
WASHER

FLAT
M8 8 0.005 0.040
WASHER

SPRING
M8 8 0.002 0.016
WASHER

TOTAL WEIGHT 12.261

DANGER
11000 VOLTS
11000
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
33KV LINE DP USING 13 MTR 150X150 PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ,E&Q
RSJ/WPB 160(FOR SPACE CONSTRAINT
APPROVED BY: P GARG, E&Q
CASES)
ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0004 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

GUARD WIRE

CROSS-LACING

20
0

3300
150 150
1.

DANGER
11000 VOLTS
11000

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
33KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: K.C.BHARDWAJ,E&Q
DOUBLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160) ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0005 REV NO:
SHEET: 1 OF 2
BOM OF GI ITEMS OF 33KV ROAD CROSSING ON DOUBLE POLE
ITEM WT WT/ ITEM TOTAL WT.
DESCRIPTION (mm) SECTION MATERIALS LENGTH (mm) QTY (Nos)
NO (KG/MTR) (KG) (KG)
150x150/ 449.8/ 1799.2/
1 RSJ POLE/ WPB 160 JOIST 13000 4 34.6 / 30.44
160x152 395.72 1582.88
2 DP TOP CHANNEL 100x50x6 CHANNEL 3150 4 9.56 30.114 120.456
3 FISH PLATE 50x6 FLAT 280 12 2.36 0.661 7.930
4 CHANNEL FOR GUARDING 75x40x4.8 CHANNEL 3700 4 7.14 26.418 105.672
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

5 CROSS BRACING 75x40x4.8 CHANNEL 1960 8 7.14 13.994 111.955


6 CROSS BRACING 50X50x6 ANGLE 3432 8 4.50 15.444 123.552
7 DANGER BOARD 200x6 FLAT 250 4 9.42 2.355 9.420
BACK CLAMP FOR DANGER
8 25x3 FLAT 510 4 0.59 0.301 1.204
BOARD
9 STAY CLAMP 50x8 FLAT 551 4 3.14 1.730 6.921
EYE HOOK(Along with
10 2nuts,1 flat & spring washer M16 ROD 305 4 1.57 0.479 1.915
each)
10 8 SWG WIRE 42000 1 0.13 5.502 5.502
11 10 SWG WIRE 22200 1 0.08 1.820 1.820
12 PIPE EARTHING PIPE 3000 4 0.00 0.000 0.000
TOTAL WT EXCEPT
496.347
POLE

NUT & BOLTS REQUIRED


CROSS CROSS GUARDING UNIT WT
NUT & LENGTH FISH DANGER STAY TOTAL
DP TOP CHANNEL BRACING BRACING CROSS EARTHING TOTAL WT. (Kg)
BOLTS (mm) PLATE BOARD CLAMP (No) (Kg)
CHANNEL ANGLE ARM
M16 50 20 4 24 0.134 3.216
M16 90 12 12 0.161 1.932
M16 200 8 32 12 52 0.331 17.212
M8 70 0 8 8 0.033 0.264

FLAT
M16 176 0.014 2.464
WASHER

SPRING
M16 176 0.009 1.584
WASHER

FLAT
M8 16 0.005 0.080
WASHER

SPRING
M8 16 0.002 0.032
WASHER

TOTAL WEIGHT 26.784


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
33KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: K.C.BHARDWAJ,E&Q
DOUBLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160) ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-HVD-0005 REV NO:
SHEET: 2 OF 2
POLE STRUCTURE
33KV LINE WITH RSJ 150X150 SINGLE

TP CENTRAL ODISHA
DISTRIBUTION LIMITED
33KV LINE WITH RSJ 150X150 SINGLE
POLE STRUCTURE

CONSULTING ENGINEERS LIMITED


MUMBAI

AS SHOWN 20/04/2021

EL 20/04/2021

RF

SS -
POLE STRUCTURE
33KV LINE WITH WPB 160X152 SINGLE
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
33KV LINE WITH WPB 160X152 SINGLE
POLE STRUCTURE
CONSULTING ENGINEERS LIMITED
MUMBAI
AS SHOWN 20/04/2021
EL 20/04/2021
RF
SS -
2.5%
NOTES :-

BILL OF MATERIALS

Layout1, CESU, CESU


Layout2, CESU, CESU
NOTES :-

BILL OF MATERIALS

Layout1, CESU, CESU


Layout2, CESU, CESU
WPB 160 DOUBLE POLE STRUCTURE
11KV DTR MOUNTING WITH RSJ 150X150/
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
11KV DTR MOUNTING WITH RSJ 150X150/
WPB 160 DOUBLE POLE STRUCTURE
CONSULTING ENGINEERS LIMITED
MUMBAI
AS SHOWN 03/04/2021
EL 03/04/2021
RF
SS -
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000

DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000

All Dimensions are in MM and Weights are in KG unless Specified.


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE DP WITH AB SWITCH


(with 11mtr. 150x150 RSJ or WPB 160)
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000

DANGER
11000 VOLTS
11000
All Dimensions are in MM and Weights are in KG unless Specified.
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE DP WITHOUT AB SWITCH


(with 11mtr. 150x150 RSJ or WPB 160)
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000

DANGER
11000 VOLTS
11000

All Dimensions are in MM and Weights are in KG unless Specified.


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE SINGLE POLE WITH V


CROSS ARM (with 11mtr. 150x150 RSJ or
WPB 160)
18x24mm Slot HOLE for
Fixing Nuts 18mm HOLE for HW fittings
1no
18mm
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

HOLE

30°- 4

DANGER
11000 VOLTS
11000

DANGER
11000 VOLTS
11000

18x24mm SLOT
HOLE 22mm HOLE FOR 18x24 SLOT
FOR FISH PLATE 11KV GI PIN HOLE
FOR FISH PLATE

18mm HOLE 18x24 SLOT HOLE 18x24 SLOT


FOR CENTER BOLT
FOR SIDE BOLT HOLE
FOR SIDE BOLT
All Dimensions are in MM and Weights are in KG unless Specified.
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE SINGLE POLE CUT POINT 180


DEGREE(with 11mtr. 150x150 RSJ or WPB
160)
18x24mm Slot HOLE for
Fixing Nuts
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

18mm HOLE for HW fittings

1no 18mm HOLE

Ø26.0000

DANGER
11000 VOLTS
DANGER
11000
11000
VOLTS 11000

18x24mm SLOT HOLE 22mm HOLE FOR 18x24 SLOT HOLE


FOR FISH PLATE 11KV GI PIN FOR FISH PLATE

18mm HOLE 18x24 SLOT HOLE 18x24 SLOT HOLE


All Dimensions are in MM and Weights are in KG unless Specified.

FOR SIDE BOLT FOR CENTER BOLT FOR SIDE BOLT


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV LINE SINGLE POLE CUT POINT 90


DEGREE(with 11mtr. 150x150 RSJ or WPB
160)
1. All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

11000
11000
DANGER
VOLTS
11000
11000
DANGER
VOLTS

All Dimensions are in MM and Weights are in KG unless Specified.


11000
11000

EXISTING 9MTR 11KV LINE


DANGER
VOLTS

11KV INTERPOSING LINE DP FOR


TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

BOTTOM CROSS ARM


75x40x4.8mm CHANNEL

DANGER
11000 VOLTS
DANGER
11000
11000
VOLTS
11000

TOP CROSS ARM


75x40x4.8mm CHANNEL

All Dimensions are in MM and Weights are in KG unless Specified.


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

11KV INTERPOSING POLE HAVING


CANTELEVER ARRANGEMENT FOR
9MTR EXISTING 11KV LINE
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000

DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000

All Dimensions are in MM and Weights are in KG unless Specified.


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE DP WITH AB SWITCH PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
(with 11mtr. 150x150 RSJ or WPB 160)
APPROVED BY: P GARG, E&Q

ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0001 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000

DANGER
11000 VOLTS
11000
All Dimensions are in MM and Weights are in KG unless Specified.
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE DP WITHOUT AB SWITCH PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
(with 11mtr. 150x150 RSJ or WPB 160)
APPROVED BY: P GARG, E&Q

ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO:TPCODL-MVD-0002 REV NO:


All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000

DANGER
11000 VOLTS
11000

All Dimensions are in MM and Weights are in KG unless Specified.


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE SINGLE POLE WITH V PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
CROSS ARM (with 11mtr. 150x150 RSJ or
WPB 160) APPROVED BY: P GARG, E&Q

ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO:TPCODL-MVD-0003 REV NO:


18x24mm Slot HOLE for
Fixing Nuts 18mm HOLE for HW fittings
1no
18mm
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

HOLE

30°- 4

DANGER
11000 VOLTS
11000

DANGER
11000 VOLTS
11000

18x24mm SLOT
HOLE 22mm HOLE FOR 18x24 SLOT
FOR FISH PLATE 11KV GI PIN HOLE
FOR FISH PLATE

18mm HOLE 18x24 SLOT HOLE 18x24 SLOT


FOR CENTER BOLT
FOR SIDE BOLT HOLE
FOR SIDE BOLT
All Dimensions are in MM and Weights are in KG unless Specified.
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE SINGLE POLE CUT POINT 180 PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
DEGREE(with 11mtr. 150x150 RSJ or WPB
160) APPROVED BY: P GARG, E&Q

ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO:TPCODL-MVD-0004 REV NO:


18x24mm Slot HOLE for
Fixing Nuts
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

18mm HOLE for HW fittings

1no 18mm HOLE

Ø26.0000

DANGER
11000 VOLTS
DANGER
11000
11000
VOLTS 11000

18x24mm SLOT HOLE 22mm HOLE FOR 18x24 SLOT HOLE


FOR FISH PLATE 11KV GI PIN FOR FISH PLATE

18mm HOLE 18x24 SLOT HOLE 18x24 SLOT HOLE


All Dimensions are in MM and Weights are in KG unless Specified.

FOR SIDE BOLT FOR CENTER BOLT FOR SIDE BOLT


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE SINGLE POLE CUT POINT 90 PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
DEGREE(with 11mtr. 150x150 RSJ or WPB
160) APPROVED BY: P GARG, E&Q

ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO:TPCODL-MVD-0005 REV NO:


All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000

DANGER DANGER
11000 VOLTS 11000 VOLTS
11000 11000

All Dimensions are in MM and Weights are in KG unless Specified.


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV INTERPOSING LINE DP FOR PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
EXISTING 9MTR 11KV LINE
APPROVED BY: P GARG, E&Q

ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO:TPCODL-MVD-0007 REV NO:


All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

BOTTOM CROSS ARM


75x40x4.8mm CHANNEL

DANGER
11000 VOLTS
DANGER
11000
11000
VOLTS
11000

TOP CROSS ARM


75x40x4.8mm CHANNEL

All Dimensions are in MM and Weights are in KG unless Specified.


1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV INTERPOSING POLE HAVING PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
CANTELEVER ARRANGEMENT FOR
9MTR EXISTING 11KV LINE APPROVED BY: P GARG, E&Q

ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO:TPCODL-MVD-0006 REV NO:


DOUBLE POLE STRUCTURE
11KV LINE WITH RSJ 150X150/WPB 160
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
11KV LINE WITH RSJ 150X150/WPB 160
DOUBLE POLE STRUCTURE
CONSULTING ENGINEERS LIMITED
MUMBAI
AS SHOWN 03/04/2021
EL 03/04/2021
RF
SS -
AB SWITCH DOUBLE POLE STRUCTURE
11KV LINE WITH RSJ 150X150/WPB 160 WITHOUT
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
11KV LINE WITH RSJ 150X150/WPB 160 WITHOUT
AB SWITCH DOUBLE POLE STRUCTURE
CONSULTING ENGINEERS LIMITED
MUMBAI
AS SHOWN 03/04/2021
EL 03/04/2021
RF
SS -
POLE STRUCTURE
11KV LINE WITH RSJ 150X150 SINGLE
TP CENTRAL ODISHA
DISTRIBUTION LIMITED
11KV LINE WITH RSJ 150X150 SINGLE
POLE STRUCTURE
CONSULTING ENGINEERS LIMITED
MUMBAI
AS SHOWN 31/03/2021
EL 31/03/2021
RF
SS -
TCE.--- POLE STRUCTURE
11KV LINE WITH WPB 160X152 SINGLE

TP CENTRAL ODISHA
DISTRIBUTION LIMITED
11KV LINE WITH WPB 160X152 SINGLE
POLE STRUCTURE

CONSULTING ENGINEERS LIMITED


MUMBAI

AS SHOWN 31/03/2021

EL 31/03/2021

RF

SS TCE.--------------------------------- -
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

PIN OR STRAIN INSULATOR

20
0

1800
150 150
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
11KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: PHIROJ UTTARAY, E&Q
K.C.BHARDWAJ, E&Q
SINGLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160)
ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS DRAWING NO: TPCODL-MVD-0009 REV NO:
ISSUE DT: 05/07/2021
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
11KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: PHIROJ UTTARAY, E&Q
K.C.BHARDWAJ, E&Q
SINGLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160)
ISSUED BY: PARVEEN VERMA,COS
SCALE : NTS DRAWING NO: TPCODL-MVD-0009 REV NO:
ISSUE DT: 05/07/2021
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
20 11000 VOLTS
0 11000
1.

3000 TATA POWER


150 150 CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
11KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: K.C.BHARDWAJ, E&Q
DOUBLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160) ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0010 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
11KV LINE PROTECTIVE GUARDING DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
ACROSS MAJOR ROAD CROSSINGS ON CHECKED BY: K.C.BHARDWAJ, E&Q
DOUBLE POLE(USING 13MTR APPROVED BY: P GARG, E&Q
150RSJ/WPB 160) ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0010 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
11KV LINE DP USING 13 MTR 150X150 DRAWN BY: J SANGRAM, E&Q
PHIROJ UTTARAY, E&Q
RSJ/WPB 160(FOR SPECIAL CASE OF CHECKED BY: K.C.BHARDWAJ, E&Q
HEIGHT REQUIREMENT AND SPACE APPROVED BY: P GARG, E&Q
CONSTRAINT ) ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0011 REV NO:
All Dimensions are in MM & Weights in KG unless Specified 2. All items are GI ( as per TS )

DANGER
11000 VOLTS
11000
1.

TATA POWER
CENTRAL ODISHA DISTRIBUTION LTD.

TITLE:- NAME
DRAWN BY: J SANGRAM, E&Q
11KV LINE DP USING 11 MTR 150X150 PHIROJ UTTARAY, E&Q
CHECKED BY: K.C.BHARDWAJ, E&Q
RSJ/WPB 160(FOR SPACE CONSTRAINT
APPROVED BY: P GARG, E&Q
CASES)
ISSUED BY: PARVEEN VERMA,COS

SCALE : NTS ISSUE DT: 05/07/2021 DRAWING NO: TPCODL-MVD-0012 REV NO:
2.5%
F09(PEG-P-102)
Rev No.00
Eff. Date 01.04.2019

02

01
dd.mm.yyyy 00 XXXXXXXXXXXXXXXXXXXXXXX

TATA POWER DELHI DISTRIBUTION LIMITED

XX
XX
ANNEXURE
XX
XX

XXX 0 OF 0 (ALPHA NUMERIC) 00