EARTHING, BONDING AND

LIGHTNING PROTECTION
ÉDITION 2019
Lightning
Protection

MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com 45


LIGHTNING PROTECTION

General overview principle of a Lightning Protection System (LPS)


Case of an installation with lightning rod (general overview of the installation)

Category Product range

Air Terminal and holders Lightning rods, ESE, air terminal and support

Down conductor 50mm² min conductor

Conductors fasteners Conductor holdfast, plots, square clamps, staple

Protection and signalling Anti-vandal guards, signal panel

Control and maintenance Lightning strike counter, test joint, earth pit

Earth electrode Conductor, earth rods, Crows foot clamp, exothermic welding

Standard Information

Norme NF EN 62305 (Protection against lightning: Physical damage to structures and life hazard)

46 MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com


LIGHTNING PROTECTION

General overview principle of a Lightning Protection System (LPS)


Case of an installation with lightning rod (detail of the installation)

Down conductor
Conductor fastener

Lightning strike counter

Test joint

Anti-vandal metal guard

Standard Information
For the lightning protection equipments manufacturers

The international and european EN IEC 62561 : standard: Lightning


Protection System Components, specifies the requirements to apply
when manufacturing lightning protection components.

The standard is composed of the following parts:


EN IEC 62561-1 : Connection components
EN IEC 62561-2 : Conductors and earth electrodes
EN IEC 62561-3 : Isolating spark gaps
EN IEC 62561-4 : Conductors fasteners
EN IEC 62561-5 : Earth electrode inspection housing and seals
EN IEC 62561-6 : Lightning strike counters (LSC)

To obtain the certifications of its products according to 62561-1 and 2,


MALTEP succesfully worked in association with the ELEMKO laboratory
(Accreditation : 3051.01).
MALTEP Certificate of Conformity

100kA, 10/350μsec. Static mechanical bench (1) Overview of samples after the
Impulse current generator (1) humid sulphurous atmosphere testing

(1) Source : ELEMKO, All rights reserved - 2017

MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com 47


LIGHTNING PROTECTION

Lightning rods
According to IEC EN62561-2

Designation Part Number


(Kg)

Stainless steel lightning rod,


length of 1.50m,
2.50 1 PTS-150/30I
provided with a stainless steel collar to
connect it with 30x2mm tape conductor

Stainless steel lightning rod,


length of 2m,
3.20 1 PTS-200/30I
provided with a stainless steel collar to
connect it with 30x2mm tape conductor

Stainless steel lightning rod,


length of 2.5m,
3.90 1 PTS-250/30I
provided with a stainless steel collar to
connect it with 30x2mm tape conductor

Stainless steel mast extension N°1, 30mm dia.,


3 1 MR-1I
Length of 2m

Stainless steel mast extension N°2, 42mm dia.,


4.7 1 MR-2I
Length of 2m

Stainless steel mast extension N°3, 42mm dia.,


5 1 MR-3I
Length of 2m

Hot-dip galvanized steel bracket with a wall


offset of 220mm. Tightening range from 27 1.45 1 PFD
to 55mm in dia. Stainless steel bolts

Hot-dip galvanized steel bracket with a wall


offset of 220mm. Tightening range from 27 1.40 1 CDC
to 55mm in dia. Stainless steel bolts

Stainless steel bracket for mounting on


114mm diameter pipe. Lightning rod
1.20 1 PLD114
diameter range from 27 to 55 mm.
Stainless steel bolts

Stainless steel bracket for mounting on


114mm diameter pipe. Lightning rod
1.20 1 PLD114/18
diameter range from 18 to 20 mm.
Stainless steel bolts

Stainless steel clamp for connection of 30mm


0.30 1 COS2E
flat conductor on lightning rod or mast.

Clamp for lightning rod


According to IEC EN62561-2

Designation Part Number


(Kg)

Stainless steel clamp for a 30mm diameter


0.14 1 COSP-250/30I
lightning rod with 30x2mm down conductor

48 MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com


LIGHTNING PROTECTION

Lightning rod base

Designation Part Number


(Kg)

Lightning rod base to mount a lightning rod


onto steel surfaces
0.85 1 EMBM16I
Threaded base in M6x70mm

Stainless steel body and bolts

Free standing air terminal support

Designation Part Number


(Kg)

Designed to mount lightning rod on roof top


7 1 TPM
Hot-dip galvanized steel body with stainless
steel bolts

Lightning air terminal and mouting accesories


According to IEC EN62561-2

Designation Part Number


(Kg)

Stainless steel air terminal, threaded base in


0.56 1 PCA318I
M10 with a dia. of 18mm, length of 300mm

Stainless steel air terminal, threaded base in


0.94 1 PCA518I
M10 with a dia. of 18mm, length of 500mm

Stainless steel air terminal, threaded base in


1.90 1 PCA1018I
M10 with a dia. of 18mm, length of 1000mm

Stainless steel threaded M10 rod


0.08 1 TPCIx
with waterproof washers and nuts

Stainless steel straight angle plate


0.20 1 PEPIx
with M10 bolts

Stainless steel squared plate with M10


0.08 1 PPCIx
central stud and bolts

Stainless steel square clamp for ribbon up to


30mm width. M10 central stud for mounting 0.25 1 SPCAI-M10
onto the air terminal

MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com 49


LIGHTNING PROTECTION

Heavy duty square clamps


According to IEC EN62561-2

Range (mm) Part


Material Bolts
round/round round/flat flat/flat (Kg) Number

4xM8 stainless steel bolts model

Tinned copper - 30 / 30 M8x25 0,31 50 RCR302

Stainless steel - D8-12 / 30 30 / 30 M8x25 0.23 50 RCI302

Stainless steel - D8-12/30 30/30 M8x40 0.30 10 RCI302/40

Stainless steel - - 30 / 30 M8x25 0.23 50 RCIP302

Stainless steel D8-12/D8-12 D8-12/30 30 / 30 M8x25 0.24 50 RCI8302

Hot-dip
galvanized - - 30/30 M8x25 0.24 50 RCRG302
steel

Stainless steel clamp for round conductor or earth point

Designation Part Number


(Kg)
Stainless steel clamp to connect in cross
or parallel two round conductors 0.95 25 MVI8-10
with a diameter from 8 to 10mm

Copper clamp for round conductor or earth point

Designation Part Number


(Kg)
Copper clamp to connect in cross or parallel two
round conductors with a diameter 0.95 25 MVCU8-10
from 8 to 10mm

50 MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com


LIGHTNING PROTECTION
Find out more about our 30x2mm
tinned copper tape and our whole Square Clamps
down conductors product range According to IEC EN62561-1
according to IEC EN62561-2 at page 15
of this catalogue..
Conductor capacity (mm)
Part
Material Bolts
(Kg) Number
round/round round/flat flat/flat

4xM6 stainless steel bolts with threaded base plate model

Copper D8-10 / D8-10 D8-10 / 30 30 / 30 M6x20 0.13 50 RC302

Hot-dip
D8-10 / D8-10 D8-10 / 30 30 / 30 M6x20 0.12 50 RCG302
galvanized steel

4xM6 stainless steel bolts model

Tinned copper D8-10 / D8-10 D8-10 / 30 30 / 30 M6x20 0.14 50 RCE302

Tinned copper D8-10 / D8-10 D8-10 / 30 30 / 30 M6x20 0.14 50 RI8302

Stainless steel - D8-10 / 30 30 / 30 M6x20 0.13 50 RI302

Stainless steel - 30 / 30 M6x20 0.12 50 RIP302

MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com 51


LIGHTNING PROTECTION

Iron cast inspection pit


According to IEC EN62561-5, for heavy duty use

Designation Part Number


(Kg)

Iron cast inspection pit with earthing


marking on its lid 8 1 RF250
250x250x110mm in dimensions

"Crows foot" clamp


According to IEC EN62561-1 (100kA)

Designation Part Number


(Kg)
Tinned copper heavy duty clamp to make
"crows foot" connection using 30x2
to 30x3.5mm tape conductor 0.60 1 P0302
Tightening done using 4xM8 stainless
steel bolts

On-demand fully assembled crows foot conductor

We manufacture on-demand crows foot conductors using exothermic welding.


You can directly unroll them on-site and save time and money.

For quotation request, please provide us with:


- Type of conductor to be welded (30x2 or 30x3.5mm)
- The required length of each conductors to be welded

Sealing tape

The sealing tape is used to protect both


outdoor and underground connections. 0.70 1 RUBPROT50
Dimension: 10 meter x 50mm in width

Protective spark gap

Designation Part Number


(Kg)
Nominal discharge current (8/20μsec): 25kA
Alternative trigger voltage (50Hz): 10kV
Lightning peak voltage at 100% (1.2/50μs): 25kV 0.26 1 ECLMAT
30x3.5mm outputs in stainless steel with two
oblongs holes of 11x13mm, length between axes
of 115mm

Down conductor warning sign


According to IEC EN 62305-3

Désignation Référence
Kg

Signalling plate "Terre Paratonnerre"


0,02 1 SIGTERPARA1
Black on yellow background
W
NE

Signalling pictogram for lightning protection


instalation according to the IEC EN 62305-3 and
0.06 1 SIGTERPARA2
NF X 08-0003-1 on hazard pictograms. Aluminum
UV-and rain-proof silkscreened

52 MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com


LIGHTNING PROTECTION

Lightning flash counter


According to IEC EN62561-1
W
NE

Designation Part Number


(Kg)

Detects and counts lightning strikes


IP65 protection for outdoor installation
IMAX sup. to 100kA (8/20μs) 0.37 1 CF302-EVO
For mounting on down conductor
Tape from 25x2 to 30x3,5mm or
Round with a diameter from 8 to 10 mm

Test joint
According to IEC EN62561-1 (100kA)

Designation Part Number


(Kg)

Tinned copper alloy body with stainless


steel bolts
For use with tape conductor up to 30mm
0.47 1 JC302
wide x 2 to 4mm thick
Supplied with hexagonal wrench, dowel
screw and anchor for mounting

PVC base with conductive connection


elements in galvanized steel
For use with galvanized steel tape conductor
with a width of 30mm or/and galvanized 0.33 1 JCG30-D8-12
steel round with a dia. from 8 to 12 mm or
galvanized steel cable ranging from 50 to
95mm² max.

Anti-vandal metal guard for down tape conductor

Designation Part Number


(Kg)

Hot-dip galvanized anti-vandal metal


guard of length 2m for down tape conductor
1.20 1 FOP302
of width 30mm. Provided with its stainless
steel wall plugs (x3)

Stainless steel anti-vandal metal guard of


length 2m for down tape conductor of width
1.20 1 FOP302I
30mm. Provided with its stainless steel wall
plugs (x3)

Stainless steel wall plugs 0.04 1 BFOP

Anti-vandal metal guard for round tape conductor

Designation Part Number


(Kg)

Hot-dip galvanized anti-vandal metal guard


of length 2m for down round conductor of
1.00 1 FOP8
dia. 8 to 10mm. Provided with its stainless
steel wall plugs (x3)

MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com 53


LIGHTNING PROTECTION

Stainless steel push in clips for 6 to 8mm dia. round conductors

Designation Part Number


(Kg)
Stainless steel push in clips for 6 to
8mm dia. round conductors with
a wall offset of 20mm 0.014 50 G820I
M6 Threaded base
Stainless steel push in clips for 6 to
8mm dia. round conductors
with a wall offset of 30mm 0.023 50 G830I
M6 Threaded base
Plastic push in clips for 6 to 8mm dia.
round conductors with a wall
offset of 16mm 0.008 50 SI6816
M6 Threaded base
Plastic push in clips for 6 to 8mm dia.
round conductors with a wall
offset of 36mm 0.015 50 SI6836
M6 Threaded base

"RUBERALU" Bitumen felt roll

Designation Part Number


(Kg/100)

Bitumen felt roll to be heated to


mount tape conductor on flat roof 0.50 10 RUB302
Dimensions: 200x45x4mm

Holdfast for conductors on flat roof

Designation Part Number


(Kg)
Pyramidal shape, case and bottom part in
plastic, filled with concrete. Provided with a
conductor holder and 2xM6 stainless steel
bolts for tightening tape conductor of 30x2, 1 20 PLOP302
30x3.5mm or round with a dia. of 8mm
Dimensions: 140x140x80mm

Pyramidal shape, case in plastic, provided


without bottom part and concrete. Provided
with a conductor holder and 2xM6 stainless
steel bolts for tightening tape conductor of 0.08 20 PLOPVIDSF
30x2, 30x3.5mm or round with a dia. of 8mm
Dimensions: 140x140x80mm

Pyramidal shape, case and bottom part in


plastic, filled with concrete, provided with
two threaded M6 holes and with conductor 1 20 PLOPNU
holder
Dimensions: 140x140x80mm

Holdfast for flat or round conductors onto flat roof

Designation Part Number


(Kg)

Holdfast for flat conductor with a


cross section from 30x2 to 30x5mm²
or round conductor with a cross 0.04 20 PLOTSI302
section of 8mm.Delivered with
two M6 stainless steel screw

54 MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com


LIGHTNING PROTECTION
Holdfast for flat conductor with a
cross section from 30x2 to 30x5mm²
or round conductor with a cross Insulated clips for tape conductors of 30x2mm
section of 8mm. Delivered with two Manufactured in UV resistant plastic material, stainless steel harware.
M6 stainless steel screw.

Designation Part Number


(Kg)

Insulated plastic clip for tape


conductors from 30x2 to 30x4mm our
round conductors of 6 to 8mm dia. 0.025 100 SI302
Base designed with an oblong hole
to ease mounting

Insulated plastic clip for tape


conductors from 30x2 to 30x4mm our
0.022 50 SI6302
round conductors of 6 to 8mm dia.
designed with a M6 threaded base

Insulated plastic clip for tape


conductors from 30x2 to 30x4mm
our round conductors of 6 to 8mm 0.024 50 SICH8302
dia. designed with a 8x40mm screw
anchor

Copper alloy holder for 30mm tape conductors

Designation Part Number


(Kg)
Copper alloy clips for tape conductor
up to 30mm in width and a thickness
0.10 25 SLT-30
from 2 to 6mm max. The base is M8
threaded

Hot-dip galvanized steel staple

Designation Part Number


(Kg/100)
Hot-dip galvanized steel staple to 100
attach flat conductors with a width 2 ou CG302
up to 30mm onto wall surface on a
30mm depth 500

Lead screw anchors for staples 0.5 100 CHP530

Plastic screw anchors for staples 0.05 100 C8

Stainless steel clip for flat conductor

Designation Part Number


(Kg/100)
Stainless steel push_in clip for tape
conductor with a width of 30mm 100
and a thickness from 2 to 3 mm, the 0.250 ou CL302
central hole is 4.2mm for mounting 500
with screws or rivets (not provided)

Aluminium/steel Rivet with a dia. of


0.05 100 CL-RIV4x12
4x12.5 for steel push-in clip

Waterproof washer for push-in clip 0.01 100 CL-JO

MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com 55


EARLY STREAMER EMISSION (ESE) AIR TERMINAL

Early streamer emission (ESE) air terminal


Early streamer emission (ESE) terminal with 60μsec. triggering advance time (Δt).
The strike tip and the high voltage control section are made of stainless steel. The ESE significantly
reduce the charge particles ionization process in comparison with standard standard lightning
rods. With a total length of 2150mm, its high voltage control section is 1500mm. It is delivered
with its collar for an easy mounting on either a 30mm tape or a 8mm dia. round conductor. The
ESE complies with the NCF17-102:2011 standard

Designation Dimensions Part Number


(Kg)

Stainless steel ESE terminal 28mm dia. x 2.15m 3,5 1 PDA60

Stainless steel mast extension to elevate


the ESE air terminal above 2m (total height dia. 33 mm x 2 m 4 1 PDA-MR2M
of 4.15m)

Stainless steel mast extension to elevate


the ESE air terminal above 3m (total height 33mm dia. x 3m 6 1 PDA-MR3M
of 5.15m)

Stainless steel mast extension to elevate


40mm dia. x 2m and
the ESE air terminal above 5m (total height 12 1 PDA-MR5M
33mm x 3m
of 7.15m)

Mounting:
The ESE is installed at a height of 2m min. above the highest structure presents in the protected
area. The mounting is straightforward using our mast brackets, mast extension or free-standing
air terminal support.

Features:
The protection radius according to NFC 17-102:2011 depends on the height and the level of
protection to be reached:

H (m) 2 3 4 5 6 10 15 20 30 45 60

Protection level I 32 48 63 79 79 79 80 80 80 80 80

Protection level II 34 52 69 86 87 88 89 89 90 90 90

Protection level III 39 58 78 97 97 99 101 102 104 105 105

Protection level IV 43 64 86 107 107 109 111 113 116 119 120

Protection radius for installations classified for the protection of the environment (ICPE):

H (m) 2 3 4 5 6 10 15 20 30 45 60

Protection level I 19 23 37 47 47 47 48 48 48 48 48

Protection level II 20 31 41 52 52 53 53 53 54 54 54

Protection level III 23 35 47 58 58 59 60 61 62 63 63

Protection level IV 26 38 52 64 64 65 65 68 70 71 72

Guy wire kit for air terminal on extension mast


With its PVC coated 25m steel cable of dia. 5mm and accessories, make up to 4 guy ropes of
approx. 5m

Designation Part Number


(Kg/100)

Guy wire kit 5 1 PDA-KITHAUB

56 MALTEP - Tel : + 33 (0)3 89 86 44 40 - Fax : + 33 (0)3 89 86 44 41 - www.maltep.com - contact@maltep.com


MALTEP reserves the right to change at any time the product specifications given for information purposes only.
Photos and illustrations are not contractual.