LIGHTNING PROTECTION
ÉDITION 2019
Lightning
Protection
Air Terminal and holders Lightning rods, ESE, air terminal and support
Control and maintenance Lightning strike counter, test joint, earth pit
Earth electrode Conductor, earth rods, Crows foot clamp, exothermic welding
Standard Information
Norme NF EN 62305 (Protection against lightning: Physical damage to structures and life hazard)
Down conductor
Conductor fastener
Test joint
Standard Information
For the lightning protection equipments manufacturers
100kA, 10/350μsec. Static mechanical bench (1) Overview of samples after the
Impulse current generator (1) humid sulphurous atmosphere testing
Lightning rods
According to IEC EN62561-2
Hot-dip
galvanized - - 30/30 M8x25 0.24 50 RCRG302
steel
Hot-dip
D8-10 / D8-10 D8-10 / 30 30 / 30 M6x20 0.12 50 RCG302
galvanized steel
Sealing tape
Désignation Référence
Kg
Test joint
According to IEC EN62561-1 (100kA)
Mounting:
The ESE is installed at a height of 2m min. above the highest structure presents in the protected
area. The mounting is straightforward using our mast brackets, mast extension or free-standing
air terminal support.
Features:
The protection radius according to NFC 17-102:2011 depends on the height and the level of
protection to be reached:
H (m) 2 3 4 5 6 10 15 20 30 45 60
Protection level I 32 48 63 79 79 79 80 80 80 80 80
Protection level II 34 52 69 86 87 88 89 89 90 90 90
Protection level IV 43 64 86 107 107 109 111 113 116 119 120
Protection radius for installations classified for the protection of the environment (ICPE):
H (m) 2 3 4 5 6 10 15 20 30 45 60
Protection level I 19 23 37 47 47 47 48 48 48 48 48
Protection level II 20 31 41 52 52 53 53 53 54 54 54
Protection level IV 26 38 52 64 64 65 65 68 70 71 72