Application:
Construction:
3. Outer sheath: Cross linked polyethylene XLPE - Halogen free thermoplastic STANDARDS
compound HFFR-UV with Anti-Rodent and Anti-Termite additive.
International EN 50289-4-17;
Main characteristics: EN 50618; IEC 60228;
IEC 60332-1-2; IEC 60684-2;
Used for interconnection wiring of grounded and ungrounded photovoltaic power
IEC 60754-1; IEC 60754-2;
system. Low emission dense smoke and halogen free. Resistance to sunlight. Flame
IEC 61034-2
retardant. Resistance to attack by rodents and termites.
National NTP-IEC 60228
Cross section:
Marking:
Packing:
Colour:
Insulation: Natural.
International standards
Halogen free Rated Voltage Uo/U Cable flexibility U.V resistance Gases corrosivity Smoke density Flame retardant Water proof
IEC 60754-1 (Um) Class 5 IEC 60228 EN 50289-4-17 Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 AD7 according to
1,5/1,5 (1,8) kV CC method A, for Corrosivity IEC UNE-EN
- 1,0/1,0 (1,2) kV 720h 60754-2 50525-2-21
CA
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 10/11/23 www.nexans.pe Page 1 / 4
FOTOVOLT N(S)2X2X 1,0/1,0 kV(AC); 1,5/1,5 kV Contact
(DC); Anti-Rodent and Anti-Termite additive Local Sales
ventas.peru@nexans.com
EN 60811-501: Electric and optical fibre cables - Test methods for non-metallic
materials - Part 501: Mechanical tests - Tests for determining the mechanical
properties of insulating and sheathing compounds.
IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable -
Procedure for 1 kW pre-mixed flame.
IEC 60754-1: Test on gases evolved during combustion of materials from cables. Part
1: Determination of the halogen acid gas content.
IEC 60754-2: Test on gases evolved during combustion of materials from cables. Part
2: Determination of acidity (by pH measurement) and conductivity.
CHARACTERISTICS
Construction characteristics
Conductor material Tinned annealed copper
Insulating material Halogen free flame retardant XLPE
Outer sheath Thermoset Halogen Free, Flame retardant, UV
Resistant - Anti-Rodent / Anti-Termite
Halogen free IEC 60754-1
Sheath colour Black
Dimensional characteristics
Minimum insulation thickness 0.7 mm
Minimum outer sheath thickness 0.8 mm
Electrical characteristics
Rated Voltage Uo/U (Um) 1,5/1,5 (1,8) kV CC - 1,0/1,0 (1,2) kV CA
Dielectric strength 6.5 kV
Time of application Dielectric strength core to screen DC 5 min.
Mechanical characteristics
Cable flexibility Class 5 IEC 60228
Usage characteristics
U.V resistance EN 50289-4-17 method A, for 720h
Halogen free Rated Voltage Uo/U Cable flexibility U.V resistance Gases corrosivity Smoke density Flame retardant Water proof
IEC 60754-1 (Um) Class 5 IEC 60228 EN 50289-4-17 Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 AD7 according to
1,5/1,5 (1,8) kV CC method A, for Corrosivity IEC UNE-EN
- 1,0/1,0 (1,2) kV 720h 60754-2 50525-2-21
CA
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 10/11/23 www.nexans.pe Page 2 / 4
FOTOVOLT N(S)2X2X 1,0/1,0 kV(AC); 1,5/1,5 kV Contact
(DC); Anti-Rodent and Anti-Termite additive Local Sales
ventas.peru@nexans.com
Usage characteristics
Gases corrosivity Low pH Corrosivity IEC 60754-2
Smoke density Low IEC 61034-2
Flame retardant IEC 60332-1-2; FT1
Ozone resistance EN 50396:2005
Water proof AD7 according to UNE-EN 50525-2-21
Rodent protection ARS (Anti rodent sheath)
Resistant to termites Yes
Minimum operating temperature -40 °C
Maximum operating temperature 90 °C
Overload maximum core temperature 130 °C
Short-circuit max. conductor temperature 250 °C
DIMENSIONAL DATA
Cross Conductor Min. insulation Min. outer sheath Diam. over Approx.
section diam. thick. thick. sheath weight
[mm²] [mm] [mm] [mm] [mm] [kg/km]
4 2.5 0.7 0.8 5.6 55
6 3.0 0.7 0.8 6.2 74
10 4.0 0.7 0.8 7.1 115
ELECTRICAL DATA
Cross section Max. DC Resist. Cond. 20°C Perm. current rat. air 60°C Nominal capacitance
[mm²] [Ohm/km] [A] [pF/m]
4 5.09 55 312.0
6 3.39 70 343.0
10 1.95 98 436.0
PRODUCT LIST
Nexans Ref. Country Name Conductor cross- Conductor Diameter over
Ref. section diameter Sheath
[mm²] [mm] [mm]
FOTOVOLT N(S)2X2X 1 kV
P00034484-0 - 4 2.5 5.6
4 mm2 FB
= Make to order, = In stock,
Halogen free Rated Voltage Uo/U Cable flexibility U.V resistance Gases corrosivity Smoke density Flame retardant Water proof
IEC 60754-1 (Um) Class 5 IEC 60228 EN 50289-4-17 Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 AD7 according to
1,5/1,5 (1,8) kV CC method A, for Corrosivity IEC UNE-EN
- 1,0/1,0 (1,2) kV 720h 60754-2 50525-2-21
CA
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 10/11/23 www.nexans.pe Page 3 / 4
FOTOVOLT N(S)2X2X 1,0/1,0 kV(AC); 1,5/1,5 kV Contact
(DC); Anti-Rodent and Anti-Termite additive Local Sales
ventas.peru@nexans.com
R=Dxf
R: Bending radius when installed (mm)
D: Diameter over sheath or over insulation (when it has not sheath) (mm)
Halogen free Rated Voltage Uo/U Cable flexibility U.V resistance Gases corrosivity Smoke density Flame retardant Water proof
IEC 60754-1 (Um) Class 5 IEC 60228 EN 50289-4-17 Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 AD7 according to
1,5/1,5 (1,8) kV CC method A, for Corrosivity IEC UNE-EN
- 1,0/1,0 (1,2) kV 720h 60754-2 50525-2-21
CA
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 10/11/23 www.nexans.pe Page 4 / 4