You are on page 1of 1

X-VOLT®

FR-N20XA8E-AR
Medium Voltage aluminium cable,
XLPE insulation, halogen free.
ACCORDING TO: NF C 33-226

Eca
APPLICATION CHARACTERISTICS
X-VOLT® FR-N20XA8E-AR Medium Voltage aluminium cables for Electrical performance
the electricity transmission and distribution. Halogen free. Medium Voltage: 12/20 (24) kV
· Distribution networks. 18/30 (36) kV
Thermal performance
CONSTRUCTION Maximum conductor temperature: 90°C.
Maximum short-circuit temperature: 250°C (max 5 s)
Conductor Minimum service temperature: -15°C.
Aluminium, class 2, according to NF-EN 60228 and IEC 60228. Fire performance
Flame non-propagation according to NF C 32-070 C2.
Conductor screen
Reaction to fire CPR: Eca according to EN 50575.
Screen over the conductor, made of thermosetting semiconductor
material. Mechanical performance
Insulation Minimum bending radius: 13x cable diameter.
Cross-linked polyethylene (XLPE). Impact resistance: AG4 Extra High Severity (≤ 20J).
Insulation screen
Environmental performance
Screen over the insulation, made of thermosetting and strippable
UV Resistant according to NF EN 50483.
semiconductor material.
Water resistance: AD8 Submersion.
Longitudinal sealing
Swelling powder. Installation conditions
Open Air.
Metallic screen Buried.
Longitudinal aluminium foil with polymer laminate bonded to the outer In conduit.
sheath.
Outer sheath
Polyolefin.
Black colour.

STANDARDS / COMPLIANCE

According to
NF C 33-226

Standards and approvals


CE / RoHS / EDF

CPR (Construction Products Regulation)


Eca

sales@topcable.com | www.topcable.com Top Cable reserves the right to carry out any modification to the data sheets whatsoever without
© 2022 Top Cable - Version 5 - 04.10.2022 | Issued by DVC giving previous notice. All renders, specifications and particulars of weights, size and dimensions
contained in this documentation is indicative only and shall not be binding on Top Cable.

You might also like