Professional Documents
Culture Documents
Technical Data
General specifications
Switching element function NAMUR, NC
Rated operating distance sn 1.5 mm
Installation flush
Output polarity NAMUR
Assured operating distance sa 0 ... 1.215 mm
Reduction factor rAl 0.22
Reduction factor rCu 0.19
Reduction factor r304 0.65
Nominal ratings
Nominal voltage Uo 8.2 V (Ri approx. 1 kΩ)
Switching frequency f 0 ... 5000 Hz
Hysteresis H 1 ... 10 typ. 5 %
Suitable for 2:1 technology yes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detected ≥ 3 mA
Measuring plate detected ≤ 1 mA
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
0102 Connection type cable PVC , 2 m
Core cross-section 0.14 mm2
Housing material Stainless steel 1.4305 / AISI 303
Sensing face PBT
Model Number Degree of protection IP67
General information
NJ1,5-6,5-N Use in the hazardous area see instruction manuals
Category 1G; 2G; 1D
Compliance with standards and directives
Features Standard conformity
• 1.5 mm flush NAMUR EN 60947-5-6:2000
• Usable up to SIL2 acc. to IEC 61508 IEC 60947-5-6:1999
Standards EN 60947-5-2:2007
IEC 60947-5-2:2007
Accessories Approvals and certificates
BF 6,5 UL approval cULus Listed, General Purpose
Mounting flange, 6.5 mm
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Dimensions
Ø 6,5
22
Release date: 2014-08-01 12:19 Date of issue: 2014-08-01 106350_eng.xml
Electrical Connection
BN
L+
BU
L-
1
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@de.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
Inductive sensor NJ1,5-6,5-N
ATEX 1G
Instruction Manual electrical apparatus for hazardous areas
Device category 1G for use in hazardous areas with gas, vapour and mist
EC-Type Examination Certificate PTB 00 ATEX 2048 X
CE marking 0102
Maintenance No changes can be made to apparatus, which are operated in hazardous areas.
Repairs to these apparatus are not possible.
Specific conditions
Protection from mechanical danger When used in the temperature range below -20 °C the sensor should be protected
from knocks by the provision of an additional housing.
Electrostatic charging Electrostatic charges on the metal housing components must be avoided. Danger-
ous electrostatic charges on the metal housing components can be avoided by incor-
porating these components in the equipotential bonding.
2
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@de.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
Inductive sensor NJ1,5-6,5-N
ATEX 2G
Instruction Manual electrical apparatus for hazardous areas
Device category 2G for use in hazardous areas with gas, vapour and mist
EC-Type Examination Certificate PTB 00 ATEX 2048 X
CE marking 0102
Electrostatic charging Electrostatic charges must be avoided on the mechanical housing components.
Dangerous electrostatic charges on the mechanical housing components can be
avoided by incorporating these in the equipotential bonding.
Release date: 2014-08-01 12:19 Date of issue: 2014-08-01 106350_eng.xml
3
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@de.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
Inductive sensor NJ1,5-6,5-N
ATEX 1D
Instruction Manual electrical apparatus for hazardous areas
4
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group USA: +1 330 486 0001 Germany: +49 621 776 4411 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@de.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com