Output Circuits - TB5 & TB7

MRP-2002 Series Instruction Manual — P/N 53049:E6 1/26/2017

Special Application Power


Basic System Connections In this example NAC Output Circuits #1, #3, & #4, Style Y (Class B) (Supervised,
Power-Limited, Class 2) NAC Output Circuit #2 (Releasing) is Style Y (Class B)
(Supervised, Nonpower-Limited, Class 1) 3.0 amp max. per circuit. (See Style Z
illustrated near right edge of board.) Initiating Device Circuits
4.7Kohm, ½ watt End-of-Line Resistor PN 71252 IDCs 1 through 6, Style B (Class B) (Supervised,
Output Circuit #1 Output Circuit Power-Limited, Class 2) (See Style D illustrated
near right edge of board.)
NAC #3 NAC 4.7Kohm, ½ watt End-of-Line Resistor PN 71252
polarized Input IDC Dummy load all unused circuits
bell Circuit #1 3 Programmable Relays
Input IDC Input IDC Nonsupervised relay contacts
with 4.7KΩ, ½ watt End-of-Line
Supervisory Waterflow
Contact Ratings resistors

Main Circuit Board


smoke Circuit #5 Circuit #6
2.0 amps @ 30 VDC (resistive)
polarized detector 0.5 amp @ 30 VAC (resistive)
strobe Normally Style Z (Class A) NAC
Open Contacts shown below in normal
pull Waterflow
station Normally Devices or condition (AC power with no alarm,
polarized Open Pressure trouble, or supervisory activity) Style D (Class A) IDC
horn heat Tamper Switches
Output or A Fail Safe Trouble relay
detector Pressure switches to the NC position
Circuit #2
Releasing Switches during trouble conditions and
under loss of all power.
Important! Removing Ground Fault Disable manual Output (*Factory default relay programming)
Jumper JP43 voids UL/NFPA Style/Class abort Circuit
release
indentifications for circuits. Remove jumper switch #4 Alarm* Trouble* Supervisory*

JP43 only with the approval of the local AHJ 2 2 6 6


(Authority Having Jurisdiction).

Special Application TB6


DC Power Outputs 24 VDC) ZONE
6
A A A A
Nonsupervised, power-limited circuits
Supervise with a power supervision relay Class A Converter Module Cut this jumper to
EOLR-1 enable Supervisory
Remove jumper JP43 to Relay when 4XTMF TB4/
TB6
Resettable Power - 24 VDC filtered, disable Ground Fault module is installed
1/6 2 3 4 5
power-limited, Class 2 (0.5 amp Detection circuit (only with
maximum) to smoke detectors (IDC). 4 approval of AHJ)
Supervise with power supervision { 3
relay EOLR-1.
SW1
Push switch down to
Nonresettable or Resettable Power { 2 upgrade software Kiss-off LED
Jumper selectable by JP31, 24 VDC 1
filtered, power-limited, Class 2 (0.5 amp
maximum). Supervise with power Auxiliary
supvervision relay EOLR-1. Nonresettable Trouble Input
Power suitable for powering smoke
detectors.
Configure TB9, Terminals 1 & 2 as Cut this jumper to supervise CAC-5X
Resettable or Nonresettable Power. the 4XTMF module when
Class A Converter Module
• Resettable Power - jumper JP31 pins 2 installed (see J4 & J5)
&3
• Nonresettable Power - jumper JP31 pins
1 & 2 (as shown) ANN-SEC
option card connector

For more specific UL wiring


information, refer to page 30.

rp2002layout.wmf
Power Supply Connector

Battery
24 VDC, supervised,
11

nonpower-limited
26 Amp Hour maximum