TPO 7x.xx
Outdoor current transformers
Description Parameters
The TPO 7x.xx transformers are designed as single-or-multiple turn Rated primary currents 1)
[A] 10 ÷ 3000
transformers, with one transformer ratio, and, if necessary, with the Primary current reconnectable [A] 20-40 ÷ 600-1200
possibility to be reconnectable on the primary or secondary side. Rated secondary currents 2)
[A] 5; 1
Rated frequency [Hz] 50; 60
The number of secondary windings ranges from 1 to 4 (usu- Highest voltage for equipment [kV] up to 40.5
ally 2) depending on parameters (such as the accuracy class, Rated power-frequency withstand [kV] up to 90
short-circuit current, overcurrent factor, burden…). voltage (r.m.s.), 1 min.
Rated lightning impulse withstand [kV] up to 200
The secondary windings are used for measurement or pro- voltage (peak)
tection purposes, or for special use (testing windings, „PX” Rated short – time thermal current, [kA] 100
class). One terminal of each secondary winding used, and 1 sec.
one terminal of the unused, short-circuited, winding must be Max. rated burden/classes 3)
[VA/cl] 3 ÷ 60/ 0,2; 0,2S; 0,5; 0,5S;
earthed during the transformer operation. 1; 3; 5P; 10P
Temperature class E
The transformer body is fixed by using four screws. For ease Ambient temperature [°C] -60...+55
of handling and assembly the transformer is supplied with Reconnectable primary or secondary
suspension lugs. 1)
Different primary currents can be supplied to special order.
2)
It is possible to combine different values in one transformer.
3)
Other classes are available on request.
The secondary winding is led out into a cast secondary termi-
nal board covered with a sealable cover.
weight: approx. 90 kg
TPO 70.12
creepage distance: 1600 mm
2 TPO 7x.xx
TPO 71.11-76.11 weight: approx. 90 kg
creepage distance: 1600 mm
TPO 7 x . x x 36/70/170 kV
38.5/80/180 kV
0...up to 600 A multi-turn 1...non-reconnectable on primary side
2...reconnectable on primary side 40.5/95/200 kV
1...up to 400 A one-turn
2...up to 600 A one-turn
3...up to 1250 A one-turn
4...up to 1500 A one-turn
5...up to 2000 A one-turn ... design
6...up to 3000 A one-turn
S1 S2 1S1 1S2 2S1 2S2 1S1 1S2 2S1 2S2 3S1 3S2
(k) (l) (1k) (1l) (2k) (2l) (1k) (1l) (2k) (2l) (3k) (3l)
P1 C1 C2 P2
P1 (K) P2 (L) P1 (K) P2 (L) (Ka) (Kb) (La) (Lb)
S1 S2 S3 1S1 1S2 1S3 2S1 2S2 2S3 1S1 1S2 2S1 2S2
(k) (l1) (l2) (1k) (1l1) (1l2) (2k) (2l1) (2l2) (1k) (1l) (2k) (2l)
d) S
ingle-core design, reconnectable e) D
ouble-core design, reconnectable f) D
ouble-core design, reconnectable
on the secondary side on the secondary side on the primary side
TPO 7x.xx 3
For more information please contact: We reserve the right to make technical changes or modify the contents of this