Professional Documents
Culture Documents
Instrument Transformers
Current Transformers
Outdoor Oil filled Current Transformers are used for measurement and protective application, together with
equipment such as meters and relays. Their role in electrical system is of primary importance as they are
means of “Stepping Down” the current of a system to measurable values, such as 5A or 1A. The Current
Transformers are available in live tank as well as dead tank. The Current Transformer can be provide with
several metering and protection winding of desired accuracy class, knee point voltage at the desired exciting
current and winding resistance.
The secondary winding of Current Transformer is prepared by winding
number of Ampere turns with copper conductor suitably insulated on high
grade non aging CRGO silicon steel toroidal core. Major insulation of uniform
thickness is applied on the toroidal core with winding prepared Kraft
insulating paper and tapings. This insulation is capacitively graded for voltage
control to ensure uniform electrified distribution and adequate safety.
We provide range of Current Transformers offered upto 33KV that makes these
transformers suitable for high-end requirement of various applications.
TECHNICAL SPECIFICATIONS
Product Name 33 KV 22 KV 11 KV
Type Outdoor, Oil Cooled Outdoor, Oil Cooled Outdoor, Oil Cooled
Design Live Tank / Dead Tank Live Tank / Dead Tank Live Tank / Dead Tank
Class of Accuracy Metering - Upto 0.2s Metering - Upto 0.2s Metering - Upto 0.2s
Protection - 5P to 15P, PS Protection - 5P to 15P, PS Protection - 5P to 15P, PS
11 kV
<5 <5
1 Amp or 5 Amp
Potential Transformers
Potential Transformers are used to transform High Voltage system to low measurable value. The
basic constructions of inductive Potential transformers have number of primary turns of super
enameled copper of high conductivity on a former using automatic winding machine with insulation
of various form and sizes with inter layer is provided suitable for oil impregnated paper. The high
voltage winding is placed on the low voltage winding and assembled over a closed iron core
maintained at ground potential.
The Potential Transformer can be provided with several metering and protection winding. It can be
designed to provide any desired voltage output from the secondary winding. The secondary tap can
be used to obtain multi ratio secondary voltage output. The high voltage lead is brought to the
bottom tank. Uniform potential gradient is obtained along with bushing by means of contoured
electrodes. High quality Kraft paper is used. The paper insulation is dried under heat and vacuum
and then impregnated with oil to achieve the excellent insulation as well as aging properties. The
fully assembled Potential Transformers are dried and oil filled under vacuum in evacuated heating
chamber.
TECHNICAL SPECIFICATIONS
Product Name 33 kV 22 kV 11 kV
Highest / Rated System Voltage 36kV / 33kV 26kV / 22kV 12kV / 11kV
Class of Accuracy Metering - 0.2 to 1.0 Metering - 0.2 to 1.0 Metering - 0.2 to 1.0
Protection - 3P to 6P Protection - 3P to 6P Protection - 3P to 6P
Rated Burden 10 VA to 100 VA 10 VA to 100 VA 10 VA to 100 VA
Resin Cast HT CT/PT AND LTCT
"Energy Tec" manufactures indoor type epoxy resin cast current and voltage transformers for stepping down
the current and voltage to measure value. The standard values of secondary current are 1 amp or 5 amps with
different class of accuracy and burden. Similarly the standard voltages are 110V and 110 / 3 V with different
class of accuracy. The high voltage range is on the primary side for current and voltage Transformer start from
11KV, 22KV and 33KV.
The constructional feature of the Current Transformer is build with CRGO lamination in the shape of torodical
core and then wound with insulated sheet thick enough to meet the requirement of system voltage. After
complete insulation with primary and secondary winding, it is casted with epoxy resin in prefabricated mould.
The voltage transformer depending upon single phase one unit or 3 phase single unit are wound with insulated
sheet appropriate thickness as per system voltage requirement. The voltage transformer coil primary and
secondary epoxy resin casted. The entire curing of casting instrument transformers is done in HOT CURE
SYSTEM with full Vacuum before mixing and after drying.
TECHNICAL SPECIFICATIONS
Product Name Resin Cast Potential Transformer Resin Cast Current Transformer Low Tension Current Transformer
Type Indoor Dry Type Indoor Dry Type Indoor Tape Wound/Cast Resin
Design Single/Three Phase Wound Type Ring Type/Wound Type
Reference Standard IS-3156 / IEC-60044-2 IS-2705 / IEC-60044-1 IS-2705 / IEC-60044-1
Highest / Rated System Voltage 12kV to 36kV / 11kv to 33kV 12kV to 36kV / 11kV to 33kV 0.66kV
Short Time Current — 25kA for 1 Sec 100 times for 1 Sec
Energy Tec was established in 2011, by Techno Crafts having rich experience in
the field of design and manufacturing of Electrical Equipments. Our Products
are extensively type tested at Central Power Research Institute, Bangalore
and Bhopal.
We have a full fledged manufacturing unit spread over 10,000 sq ft area , well equipped with latest production and
testing equipments, located in prime area near to the city, which is well connected by all means of transport. All
fabrication works are done in-house with our full fledged fabrication shop to ensure manufacture of leak proof tanks.
All Windings and insulation are done in controlled atmosphere to ensure that the main elements are free from dust.
Testing & QC Facilities are available in the Stage and Final Inspection with latest Testing Equipments calibrated and
certified by NABL accredited Laboratory.
Allied Spares