Professional Documents
Culture Documents
Submitted to –
Dr. SEEMA AGARWAL Submitted by –
(Assistant Professor) Sagar kumar jain
Electrical Eng. Department 20/334
RTU, Kota Batch- B-5
Contents
1. Introduction
220/132kV Gss Mandawar
2. Power Transformer
3. Instrument Transformer
4. Lighting Arraster
5. Electrical Isolator
6. Circuit Breakers
7. Electrical Insulator
8. Miscellaneous Equipment
Introduction
■ RVPNL is a company of Rajasthan State
Electricity Board(RSEB) established by
government of rajasthan. The Aim of RVPNL is
to provide reliable transmission service to
customers.
o Bus bar
o Circuit breaker
o Lightning Arresters
o Isolator
1. Power Transformer-
They are used to step up and step down voltages
greater than 33kv and upto 400kv. They are maintained to have very high
efficiency so that minimum power is lost during the transmission process.
They are bigger in size as compared to distribution transformers.
220/132 kV,100 MVA POWER TrF-I&II
% Impedance– 11.7426%
220/132 kV, 100 MVA, TRF –II (Make–TELK )
% Impedance– 11.80%
2. Instrument Transformer-
The line in a station operated at high voltage and carry current of
a 1000 amp. The measuring instrument and protective devices are designed for low voltage
(110V) and current (5 amp). Therefore, they will not work satisfactory if mounted directly on
the power lines. The meter is always connected to the secondary circuit.
Types-
a) Current Transformer-
Current transformer is an instrument which is used for protection and
metering of high values of current. C.T’s secondary is connected to relay to protect the
system against overcurrent.
b) Potential Transformer-
The potential transformer are a parallel- connected
type an instrument transformer which employed to transmit the voltage from a
higher value to a lower output. This transformer step down the voltage to a safe
limit value which can be easily measured by the ordinary low voltage
instrument like a voltmeter, wattmeter and watt-hour meters, etc.
CURRENT TRANSFORMER
Manufacturer BHEL
Highest System Voltage 145kV
Frequency 50HZ
Rated Current Factor per 25kV/S
Time
Rated Primary Current 800A
Turn Ratio 400:1
CAPACITIVE VOLTAGE
TRANSFORMER
Manufacturer BHEL
Rated Voltage Factor per Time 1.5/s
Highest System Voltage 145KV
Primary Voltage 76.21KV
Frequency 50Hz
INSULAT
OR
BUS BAR
Current lag must be decreased so that power factor of the system may be improved. This
is ensured by using a capacitor that nullifies the inductive effect. This is generally
achieved by using a static capacitor in series or shunt with the electrical power system. For
better maintenance and effectiveness, a group of capacitor units are used
CONTROL ROOM