Professional Documents
Culture Documents
ETI-APRIL-198449
Designer’s Notebook
the secondary winding of the transformer Inductor Design ly in the winding and these can be deter-
is a function of the power supply output mined using a similar method to that used
voltage (5 V), the duty cycle of the swit- The operating conditions of the magnetic
core in the inductor are significantly dif- to calculate the transformer winding
ches SW1 , SW2, and the voltage dropped losses. Example: For the Philips
across the rectifiers and resistance of the ferent from those of the switching mode
transformer. The core must withstand a EC35/17/10 core with a minimum air gap
output inductor Ll , Disregarding the cir- of 0.9 mm, 4 turns are required to give an
cuit losses initially, the transformer out- DC magnetizing field, without saturation.
For this reason, an air gap is commonly inductance of 1.6 microhenries. The win-
put voltage can be found by balancing the ding losses can be written as I,fr*.Fa.Rr,c
volt-second products for the output in- introduced into a magnetic circuit. This
can be either in the form of a single gap where:
ductor in the minimum input supply con- &rf is the RMS current flowing in the in-
dition, when the duty cycle is 0.9. introduced, say, in the centre pole of an
‘E’ core, or can be a distributed gap ductor winding.
throughout the core material. The distri- Fa is a resistance multiplier to account for
(v,-v,)=(v,+v,)(1 -6’ buted gap solution presents a lower high frequency operation.
radiated magnetic field. When a gapped Rnc is the DC resistance of the winding.
where V, is the transformer output core is used, the magnetic flux is sorted The high frequency impedance of the
voltage. mainly in the gap. There are small flux ex- winding is a minimum for a conductor of
V, is the supply output voltage =5v cursions as the load current ramps up and thickness 0.57 mm. Making the winding
is the duty cycle =0.9 down. As an example, consider the design with copper strip of thickness 0.5 mm and
Vr is the rectifier forward drop =lV of an output filter inductor to be used width 20 mm gives a 100°C AC winding
with the 50 kHz transformer previously resistance of 0.58 mR. The winding loss is
designed. The operating frequency will be OW93, resulting in an inductor tempera-
v, = 5V7 100 kHz. The maximum output current is ture rise above ambient of 18 °C when ful-
homemade-circuits.com 40 A and the minimum output current for ly loaded.
To this figure must be added the circuit continuous current flow in the inductor is
losses, Vr + I,.Rr_, where I, is the rated 4A. Drive Transformer Design
output current, and RL is the series Step 1. Calculate inductance value re- Various approaches to the design can be
resistance of Ll and the circuit wiring. quired, and the energy storage capability made, though the choice is frequently
A minimum output voltage of 7 V required. Example: The minimum voltage restricted by the operating conditions and
can be used. The minimum input voltage applied to the inductor by the transformer the drive requirements of the semiconduc-
‘is 139 V, so the transformer turns ratio is secondary winding is 5V7 with a 0.9 duty tor switch. Thyristors and power MOS-
20: 1. Assuming a primary winding of 40 cycle. The current in the inductor can be FETS can be driven by pulse trans-
turns (marginally below the minimum, re- allowed to rise by 8 A maximum during formers. The length of the trigger pulse
sulting in a slightly higher peak flux densi- this time, if the current flow is to remain and the circuit impedance are designed to
ty, B, which can be tolerated in this exam- continuous when the output loading is comprehend the drive requirements of the
ple), each secondary winding comprises minimum, i.e. 4A. worst case drive. Bipolar transistors re-
two turns. quire a continuous base current supply
Step 4. Transformer winding design. The (VI, min - V,) = L min. &$$ which often results in a larger transformer
correct design of the transformer windings core being needed. The need for a wide
will result in a reproducible and efficient where VINmin is the voltage applied to the variation in switch duty cycle often results
transformer design. The conductor size inductor = 5V7 in the drive supplied to the switching
and placement can have a significant ef- V, is the output supply voltage = 5V device being compromised; the forward
fect on winding losses in a high frequency Lmin is the minimum inductance value base current supplied during long duty-
design. Example: The primary winding It, is the peak to peak inductor current cycle opeation may be the bare minimum
consists of 40 turns of 0.85 mm diameter =8A to maintain the transistor in saturation.
wire, which can be wound in two layers fo is the operating frequency = 100 kHz At short duty-cycles, the base current sup-
each comprising 20 turns. The available max is the switch duty cycle =0.9 plied can be far in excess of the device re-
winding breadth on the transformer core lmin = 1.6 microhenries quirements, compromising its switching
is approximately 20 mm after an allow- performance. This effect is less severe
The energy storage capability is L.I,2 when power MOSFETS are used as the
ance of 4 mm at either end for isolation. where I,,, is the peak current flowing in the
The secondary consists of two windings, switches, since they do no exhibit storage
inductor = 44 A, so L.I,* = 3.1 mJ. time effects.
each of two turns. The conductor for
these windings is in strip form, being 8 Step 2. Select a suitable inductor core and As an example, consider the design of
mm in width and 0.625 mm thick. The determine the air gap required (if it is not drive transformers for power MOSFETS
windings are wound side by side on the a distributed gap material). The majority when used as the switches in the 50 kHz
former. Electrostatic screens and isolation of magnetic core manufacturers provide switching mode power supply. A single
are wound between primary and secon- selection charts/guides for this purpose. transformer with two primary and two
dary windings. Worst case windings losses Example: Philips core EC35/17/10 with a isolated secondary windings could be us-
arise at maximum loading. Primary win- 0.9 mm air gap will meet the energy ed. A disadvantage of this approach,
ding loss is 3W4 maximum, and the secon- storage requirement (equivalent to the however, is the absence of negative gate
dary winding loss 1W25 watts maximum. Mullard FX3720). bias to turn off the MOSFETS at any duty
When added to the transformer core Step 3. Calculate the number of turns re- cycle other than the maximum of 0.5,
losses of 1 W8, the worst case transformer quired and determine the inductor losses. which would give poor noise immunity in
loss is 6W45 at a core temperature of The core data gives an effective normal operation. Instead, separate
100°C. The transformer is capable of permeability or an AL value (inductance transformers are used and the magnetizing
operating in ambient temperatures up to per turn of the coil) for gapped cores, energy stored in the transformer core dur-
35 °C without additional heatsinking. which enables the number of turns to be ing the conduction phases is used to assist
(Core data and ratings are drawn from the calculated and rounded up to the nearest turn-off. The transformer design is similar
manufacturer’s literature). half turn. The inductor losses are primari- to’ that required for a single-ended for-
SO-APRIL-1984-ET1
ward converter (Fig. 3b). the core = 25.1 mm’ Because of handling difficulties, a 0.2 mm
Step 1. Select a suitable magnetic material nti, is the minimum number of primary wire may be preferred. The winding area
and core size. Example: The operating re- turns homemade-circuits.com consumed is approximately 20% of the
quency is 50 kHz and the average current Hence nmin = 30 turns total winding area of the transformer.
flow in the windings will be low. A core The magnetizing inductance, with n, the Assuming that the drive transformer has a
material with a high permeability is number of turns equal to nmin is given by: 1:l turns ratio, giving a ±15 V gate drive
desirable to maintain a low level of to the power MOSFET, the winding area
magnetizing current. Winding area is a is adequate, after an allowance for isola-
significant factor in determining the core where: v A tion spacing has been made.
size and will depend on the isolation LM is the magnetizing inductance in Step 4. Calculate the minimum permitted
voltage rating desired. For this application millihenries drive pulse for safe turn-off. Example:
consider the Philips core P1418 in 3B7 AL i s t h e i n d u c t a n c e f a c t o r i n Because this design relies on the
material, with an AL value of 2,200 nanohenries/lOOO turns = 2,200 transformer magnetizing energy to switch
mH/lOOO turns and a total winding area of Hence L, = 2.0 mH off the power MOSFET, a minimum drive
9.4’mm*. The magnetizing current at maximum pulse must be defined whereby the
Step 2. Calculate the number of turns re- duty cycle is: magnetizing energy equals the worst case
quired for the primary winding and the V,, . 6 max turn-off energy for the MOSFET. Turn-
magnetizing inductance and current. Ex- I, = = 67.5 mA off energy requirements for the MOSFET
ample: To avoid core saturation when = Qo. A V where Qo is the maximum
L, fo
operating at maximum duty cycle, with a gate charge figure.
supply voltage of 15 V, the minimum Step 3. Check that the winding area on the
ferrite core is adequate. Example: To AV is the gate voltage swing =30V
number of turns required in the primary Magnetizing energy in the transformer
winding is given by: calculate the winding area required for the
primary winding, we must first estimate = (VrN . to,min)2/LM
V,, . 6 max& = % Ae. nmin the average current flow. The current re-
quired to drive the power MOSFET where t,,min is the duration of the
where V,N is the supply voltage = 15v IRF720, which would be used in this ap- minimum drive pulse. Equating these
6 max is the maximum duty cycle = 0.45 plication, at 50 kHz, is low compared to figures, assuming Qo = 17 nC for the
f, is the operating frequency = 50 kHz the magnetizing current (1.7 mA averaged IRF720 device, gives a minimum drive
B is the peak magnetic flux density in the over a switching cycle). So, the average pulse of t,,min = 2.15 microseconds,
core = 180mT magnetizing current level can be assumed. which represents a minimum duty cycle,
Ae is the magnetic cross sectional area of A suitable wire gauge is 0.1 mm diameter. at 50 kHz, of 0.22. ETI