You are on page 1of 8

Application Note Y99AB-4

Issue Date August 20, 2008

Y99AB-4 BASO® Test Kit

64119-1D
Adapter Assembly Definitions
44549-4 Automatic Pilot - A device employed with gas burning
Lead Assembly
equipment, which automatically shuts off the gas supply
44549-7 to the burner being served by either direct or indirect
Lead Assembly
means when the pilot flame is extinguished. The pilot
burner may or may not be constructed integrally with the
10
0
300
20
500
30
700

40
90
0
MILLIAMPS
0-500 device.
10
DC MILLIVOLTS 50
0-1000 0-50
0

Closed Circuit - Millivoltage measured with the BASO


PE NN-BA SO CONTRO LS
MILLIVOLTS
JOHNSON CO NTROLS , INC
WATERTO WN, WI., U.S.A

ADJUST control attached to the thermocouple.


MILLIVOLTS
MILLIAMPS
Couple Lead - The thermocouple, current carrying
conductors, and attaching nut.
Dropout - The point, defined by a millivolt or milliampere
TCN10-4 reading, at which the electromagnet releases the
Thermocouple Nut
armature.
40073-4
Lead Nut Milliampere - One thousandth of an ampere.
31543-3 Abbreviation mA used to check BASO control dropout.
Thermocouple
Terminal Nut Millivolt - One thousandth of a volt. Abbreviation mV
used to measure thermocouple output.
Figure 1: Y99AB-4 Test Kit
Open Circuit - Millivoltage measured without the BASO
control attached to the thermocouple.
Description
The Y99AB-4 Test Kit combines four test functions Power Unit - Electromagnet unit that is internally
to enable service contractors to test BASO® controls connected to the seat of the gas valve and cuts off the
and thermocouples in the field. These four functions gas when pilot flame fails. Also called a power unit
are: assembly or hood.

• Millivoltmeter with 0 to 50 and 0 to 1000 ranges Reset Button - The button that is manually depressed to
for checking the open and closed circuit place the BASO control in operation.
millivoltage of thermocouple leads. Thermocouple - The pair of dissimilar metallic elements
• Performance Tester with a source of power for joined to produce a millivoltage when the junctions are at
holding open BASO power units while taking different temperatures.
open circuit millivolt readings of the
thermocouple when the main burner is in
operation.
• Milliammeter with a 0 to 500 (50 on scale)
range for checking the current dropout range of
BASO power unit assemblies. (There are
10 milliamperes for each division on the dial.)
• Continuity Tester for detecting a broken or
open circuit.

© 2008 BASO Gas Products 1


Part No. BASO-AN-Y99AB, Rev. — www.baso.com
General Instructions
When using the test kit, insert the plugs securely Note: When taking an open circuit millivolt reading on
and squarely into the jacks. The thermocouple a junction block thermocouple, the junction block
adapters and nuts must be clean and tight. Any terminal must be shorted (see Figure 4). This will isolate
meter fluctuation caused by the movement of these the thermocouple from the high limit.
parts may be due to loose connections. Poor 500 MILLIAMPS
300 20 700
connections cause false readings. Three “D” size 100 10
0
30
40 90
0
50
0-500

batteries are required. DC MILLIVOTS


PENN -BASO C ONT ROLS

0-1000 0-50
MILLIVOLTS

! WARNING: Risk of Fire or Explosion.


ADJUST

MILLIAMPS
In order to test the thermocouple under actual
MILLIVOLTS
flame conditions, it is necessary to hold the BASO
power unit open with the DC power pack provided
with the test kit. This eliminates the safety function 44549-8
provided by the BASO power unit. Care must be
exercised during this test to ensure that gas is not
permitted to flow to the main burner.
Red Black

! CAUTION: Risk of Equipment Damage.


Thermocouple
Lead
This meter is designed and calibrated for
Figure 2: Open Circuit Millivolt Reading Connection
Direct Current (DC) voltages up to 1000 millivolts
Diagram
only. Any attempt to measure Alternating Current
(AC) voltage or DC voltage over 1000 millivolts will Approximately
damage the meter.
12.7 mm (1/2 in.)

Open Circuit Millivolt Readings


Refer to Figure 8 through Figure 10 for typical
thermocouple-operated gas valve,
electrically-operated gas valve, and safety shutoff
device connection diagrams.
Perform the following procedure for taking open
circuit millivolt readings.
Figure 3: Normal Pilot Flame
1. Shut off the gas supply at the main manual
Shorting Wire
shutoff valve.
2. Disconnect the thermocouple from the BASO
control.
3. Attach the test cable lead 44549-8 to the
thermocouple. Connect the red clip to the
copper tubing of the thermocouple and the black
clip to the terminal at the end of the
thermocouple (see Figure 2).
High
4. Set the slide switch on the meter to the 0-50 or Limit
0-1000 position. Switch

5. Re-establish pilot flame. Figure 4: Junction Block Thermocouple


6. The millivolt reading should agree with the
values listed in Table 1 with a normal pilot flame
(see Figure 3).

2 Y99AB-4 BASO Test Kit Application Note


Table 1: Thermocouple Output
Thermocouple Turndown mV Range Minimum Fixed Load
Lead Adapter Voltage
Normal Not Less Than
K14 4 mV 20-28 15 8
K15 4 mV 20-28 15 8
K16 4 mV 25-35 17 8
K19 4 mV 25-35 17 8

Fixed Load Millivolt Readings


Perform the following procedure for taking fixed load 300 20 500
10 0 10 30
700
00
MILLIAMPS
0-500
40 9
millivolt readings: 0

DC MILLIVOLTS
50

PENN-BASO CONTROLS

1. Disconnect the thermocouple from the BASO 0-1000 0-50


MILLIVOLTS
control and attach the adapter assembly ADJUST
(64119-1D) to the thermocouple.
MILLIAMPS
2. Attach the test cable lead 44549-8 to the
MILLIVOLTS
adapter assembly. Connect the red clip to the
copper tubing of the adapter assembly and the
black clip to the control end of the adapter 44549-8
assembly (see Figure 5).
3. Set the slide switch on the meter to the 0-50 or
0-1000 position.
Shorting Red Black
4. Reestablish pilot flame. Jumper Clip

5. The millivolt reading should agree with the


values listed in Table 1 with a normal pilot flame
(see Figure 3). Thermocouple 64119-1D
Lead Adapter
Note: When taking a fixed load millivolt reading Assembly
on a junction block thermocouple, the junction
block terminal must be shorted (see Figure 4). Figure 5: Fixed Load Millivolt Reading Connection
Diagram

Y99AB-4 BASO Test Kit Application Note 3


Dropout Testing Table 2: Milliampere Dropout Range
Refer to Figure 8 through Figure 10 for typical BASO Control mA Range of Power
thermocouple-operated gas valve, Part Number Unit Assembly
electrically-operated gas valve, and safety shutoff
device connection diagrams. Low High
Perform the following procedure using the H15A_, H15C_, H15D_, H15H_ 100 300
milliammeter for dropout testing. H15E_, H15F_ 60 150
1. Shut off the gas at the main manual shutoff H17_A 100 300
valve. H17_B 50 165
2. Disconnect the thermocouple lead from the H19A_ 100 300
BASO control.
H19ME 45 165
3. Connect the test cable lead 44549-7 to the H19L_, H19N_, H19R_, H19T_ 100 300
milliamperes jack on the test kit meter, connect
the other end to the BASO control H43AA, H43BA, H43GA 100 300
(see Figure 6). H43AB, H43BB 50 165
4. Set the slide switch on the meter to the 0-500 G92 (All models except 100 300
(50 on scale) position. G92CAA-19 and G92CBA-10)
5. Turn the adjust knob on the meter clockwise to G92CAA-19 and G92CBA-10 100 200
the full scale deflection of the needle. Reset the G93 100 300
control by pressing in the reset button on the
G292 100 300
control firmly.
L61LL 75 200
6. Turn the adjust knob on the meter
counterclockwise slowly until the BASO control L62AA 100 300
power unit releases. The milliampere reading at L62GB 100 300
the moment of release is the dropout point of the
BASO power unit. Take two more readings by
the same process, and average the readings.
The milliampere dropout point must lie within the
high and low range listed in Table 2.
7. Pilot and main burner should extinguish within a
few seconds. If flames do not extinguish, refer to
the Troubleshooting section.
500 700 MILLIAMPS
300 0-500
20 30 90
0
10 10
40 0
DC MILLIVOLTS 50
0-1000 0-50
0

PENN-BASO CONTROLS
MILLIVOLTS
JOHNSON CONTROLS, INC
44549-7
WATERTOWN, WI., U.S.A

ADJUST

MILLIVOLTS
MILLIAMPS

Reset
Button

44549-8
H17
Gas Valve

Figure 6: Dropout Testing Connection Diagram

4 Y99AB-4 BASO Test Kit Application Note


Continuity Testing Closed Circuit Test
Perform the following procedure for closed circuit testing.
! CAUTION: Risk of Equipment Damage. 1. Disconnect the thermocouple from the BASO
Turn off the power to the appliance. When the control.
meter is being used as a continuity tester, it should 2. Attach the adapter assembly (64119-1D) to the
never be put across line voltage potential. control and thermocouple.
Perform the following procedure for continuity 3. Remove the shorting jumper clip from the adapter
testing. assembly.
1. Connect the test cable lead 44549-4 to the 4. Set the slide switch on the meter to the 0-50
milliampere jack on the test kit meter. position.
2. Set the slide switch on the meter to the 0-500 5. Attach the test cable lead 44549-8. Connect the red
(50 on scale) position. clip to the copper tubing of the thermocouple and the
black clip to the adapter block terminal
3. Connect the red and black alligator clips
(see Figure 7).
together; turn the adjust knob clockwise until the
needle is above 500 (50 on scale). If unable to 6. Depress the reset button on the BASO control and
get a reading of 500, check the alligator clip light the pilot using a safe lighting procedure. Hold
connection or replace the batteries. the reset button in for approximately 60 seconds or
until the output is high enough to hold the energized
4. Test for open circuits by touching or connecting
valve.
the alligator clips to terminals or points in the
circuit. 7. Observe output. The millivolt reading should agree
with the values listed in Table 1.
300 20 500 70 0 MILLIAMPS
30
100 1 0
40 9
00 0-500
0 50
DC M ILLIVOLTS
PENN-B ASO CONTROLS

0-1000 0-50
MILLIVOLTS

ADJUST

MILLIAMPS

MILLIVOLTS

44549-8

Black

Reset
Button
Red

Thermocouple
Lead H19
High Pressure
Gas Valve

Figure 7: Closed Circuit Test Connection Diagram

Y99AB-4 BASO Test Kit Application Note 5


44549-7

Reset
Button

44549-8

“A”
Valve
Pilot Burner
Gas Line Red Black

Thermocouple
Lead

Figure 8: Typical Thermocouple-operated Gas Valve Connection Diagram


Power
Source Thermostat

“B” Transformer
Valve BASO
Power
Shutoff
Unit
Valve Reset
Button
44549-7

BASO
Magnetic
Operator
44549-8

Red Black
Pilot Burner
Gas Line

Thermocouple
Lead

Figure 9: Typical Electrically-operated Gas Valve Connection Diagram

6 Y99AB-4 BASO Test Kit Application Note


“L” Series
Control
Power
Source Thermostat

Transformer

Shutoff
Valve
“B” 44549-7
Valve

44549-8

Red Black

Pilot Burner
Gas Line

Thermocouple
Lead

Figure 10: Typical Safety Shutoff Device Connection Diagram

Y99AB-4 BASO Test Kit Application Note 7


Troubleshooting
The following table indicates symptoms and corrective actions.
Table 3: Troubleshooting Symptoms and Corrective Actions
Symptom Possible Cause Corrective Action
Pilot burner outage, varying Excessive draft Baffle secondary air or shield pilot burner.
performance, or poor mV output. Recirculation of flue products Check venting and main orifice sizing and
correct where necessary.
Excessive temperature Check main burner input and correct if
necessary.
Improper pilot flame size or Check gas pressure, clean pilot burner,
characteristic and adjust flame.
Defective thermocouple Perform the Open Circuit Millivolt Readings
procedure.
Weak holding BASO power unit Perform the Dropout Testing procedure.
Pilot burner burning, manual valve Defective thermostat Perform the Continuity Testing procedure.
(if included) turned to the “On” Defective operator Check for operator input voltage. If present,
position, thermostat calling for replace the valve. If not, check voltage
heat. Main burner does not come source.
on.
Thermostat not calling for heat, or Shorted thermostat circuit Perform the Continuity Testing procedure.
turned down, manual valve (if Foreign particles lodged between Replace the valve.
included) in the “On” position. Main the valve seat
burner does not shut off.
No burner flame or flame does not Thermocouple out of position Reposition thermocouple properly.
stay on. Thermocouple lead dirty or loose Clean and tighten thermocouple lead
connection.
Defective thermocouple Perform the Open Circuit Millivolt Readings
procedure.
Defective BASO power unit Perform the Dropout Testing procedure.
Defective orifice Clean or replace orifice.
Unusually strong drafts Baffle secondary air or shield burner.

1007 South 12th Street


PO Box 170
Watertown, WI 53094 www.baso.com
1-877-227-6427 (1-877-BASOGAS) Printed in U.S.A.

8 Y99AB-4 BASO Test Kit Application Note

You might also like