Professional Documents
Culture Documents
1MRG004961
Exercise 4 - Negative sequence feature
Copyright
This document and parts thereof must not be reproduced or copied without
written permission from ABB, and the contents thereof must not be imparted to
a third party, nor used for any unauthorized purpose.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
This exercise is based on the configuration in figure 1, i.e., a three winding transformer protection. NB new
transformer and CT-data.
Transformer Data:
100 / 100 / 10 MVA
132 / 66 / 11 kV
437 / 875 / 525 A
YNyn0d1
140 kV Bus
RET670
140kV/110V Meter.
CV MMXU
300/1
11 kV Bus W1 87N IdN/I 87T 3Id/I
W3 W2 REF PDIF T3W PDIF
600/1
Meter. Mont.
CV MMXU DRP RDRE
Function Function
configured not configured
Figure 1: A protection application for a three winding transformer in single breaker arrangement
Figure 1 shows all included functionality in the configuration. Function blocks in black are configured and the
rest indicate possible additions.
Prerequisite
Exercise 1 is finished and the IED is ready for testing (configuration, parameters, signal matrix
and eventually the graphical display is written into the IED).
Analog inputs
1. Move to TRM_6I_6U
No changes.
We can ignore the 3rd winding since we will only test W1-W2.
IdMin is increased to make room for the negative sequence protection below the characteristic.
NegSeqDiffEn is the parameter we will shift Off On during the test
IDL1MAG: .......... A
IDL2MAG: .......... A
IDL3MAG: .......... A
IDNSMAG: .......... A
IDNSMAG: .......... A
Primary currents
HV-side:
IL1HVSec = 656 Ð0°
IL2HVSec = 542 Ð232.78°
IL3HVSec = 542 Ð127.22°
MV-side:
IL1MVSec = 1312 Ð0°
IL2MVSec = 1196 Ð236.73°
IL3MVSec = 1196 Ð123.27°
The MV-side:
IL1MVSec = 1.312 Ð0°
IL2MVSec = 1.196 Ð236.73°
IL3MVSec = 1.196 Ð123.27°
The unrestrained negative sequence differential protection is tripping since the internal/external fault
discriminator has declared the fault as internal. The wave-form and harmonic check is bypassed.
IDL1MAG: .......... A
IDL2MAG: .......... A
IDL3MAG: .......... A
IDNSMAG: .......... A
IDNSMAG: .......... A
Primary currents
HV-side:
IL1HVSec = 311 Ð0°
IL2HVSec = 219 Ð240°
IL3HVSec = 219 Ð120°
MV-side:
IL1MVSec = 346 Ð180°
IL2MVSec = 437 Ð60°
IL3MVSec = 437 Ð300°
The MV-side:
IL1MVSec = 346 Ð180°
IL2MVSec = 437 Ð60°
IL3MVSec = 437 Ð300°
The sensitive negative sequence protection is tripping independent of the differential protection.