You are on page 1of 1

Enter the Values in the

IEC Curve Selected


Ip Setting
Tp Setting

Boxes Only
Data
Units
Entry
0.90 Amps
0.35 sec

Injected Current

10

Choose the Curve

Normal Inverse
1

9 Amps

Current to be Injected
Calculated Tripping Time for 10 times Current

IEC Curve Selected


IEp Setting
TEp Setting

4 times

1.04 Secs

Data
Units
Entry
0.85 Amps
0.40 sec

Injected Current

10

Choose the Curve

Normal Inverse
1

Current to be Injected
Calculated Tripping Time for 10 times Current

4 times
8.5 Amps
1.188 Secs