Professional Documents
Culture Documents
BG 35/2012
ACKNOWLEDGEMENTS
BSRIA wishes to thank the following members of the steering group for
their contributions:
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system,
or transmitted in any form or by any means electronic or mechanical including photocopying,
recording or otherwise without prior written permission of the publisher.
©BSRIA January 2012 ISBN 978 0 86022 706 9 Printed by ImageData Ltd
This guide is aimed at those who have the responsibility for maintaining
buildings. It outlines the benefits of having good knowledge of the assets
in a building and how, with a greater understanding of their condition,
they can be maintained in a more efficient and economical way.
The focus of this guide is building services. However, the guidance may
also apply to the fabric and structure of buildings, and other assets such as
process equipment. In addition to guidance, checklists are provided in
the appendices. Blank checklists in Microsoft Word format are attached
to this pdf, and can also be downloaded from the BSRIA website:
www.bsria.co.uk/goto/csc.
© BSRIA BG 35/2012
CONTENTS
6 SURVEY TOOLKIT 33
6.1 Introduction 33
6.2 Overview and pre-survey checks 33
6.3 Common defects 34
6.4 Factors affecting the economic life of plant 39
REFERENCES 44
APPENDICES
APPENDIX A: PRE-SURVEY CHECKLIST 40
APPENDIX B: GENERIC PLANT ASSESSMENT CHECKLIST 41
APPENDIX C: EXAMPLE SPREADSHEET 43
TABLES
Table 1: Equipment requiring specialist surveys 10
Table 2: Two-tier and three-tier data-recording 24
Table 3: Surveyor’s equipment and tools 26
Table 4: RICS classification of repair priorities 32
Table 5: Physical condition 34
Table 6: Operation and maintenance 34
Table 7: Operation and maintenance history 35
Table 8: Health and safety 35
Table 9: LV electrical installations – general power 36
Table 10: LV electrical installations – lighting 36
Table 11: Boilers, heating and hot water systems 37
Table 12: Ventilation and air conditioning systems 37
Table 13: Refrigeration systems 38
Table 14: Control systems 38
Table 15: Lift installations 38
Table 16: The economic life of plant 39
FIGURES
Figure 1 Building structure 11
Figure 2 Mechanical pump 11
Figure 3 Pressure vessel 12
Figure 4 Electrical control panel 12
Figure 5 Identifiable power source 25
Figure 6 Deterioration caused by arcing possibly due to excessive
neutral currents caused by harmonics 30
© BSRIA BG 35/2012
THE VALUE OF ASSET DATA 1
“The collection of data about the condition of a building, part of a building, estate
or portfolio, assessing how that condition compares to a pre-determined standard,
to identify any actions necessary to achieve that standard now, and maintain it
there over a specified time horizon, the purpose being to support management
decision making.”
Asset register
Watchpoint
One of the main objectives of any condition survey is to develop a
Condition surveys should
be repeated at regular reliable asset register along with a database on the overall condition of
intervals to enable a plant and associated systems. Both the asset register and the condition
review of the asset appraisal will help the maintenance and facility management staff plan for
condition, build a history their future maintenance, replacement and refurbishment needs. They
of the plant and system will also enable the continual support of the business needs giving due
and update the future
maintenance and financial
regard to:
programmes.
• functional suitability and performance
• physical and operational condition
• safety and statutory requirements
• energy and environmental performance.
[ 2]
BS 3811 defines a condition appraisal as:
© BSRIA BG 35/2012
THE VALUE OF ASSET DATA 1
1.4 BENEFITS IN A condition survey can be used to evaluate maintainable assets. The
CONTRACTED application of a building survey to collect the data will provide a robust
MAINTENANCE
and consistent basis to award a maintenance contract. The data provided
will enable consistent pricing, improve the contractors’ mobilisation and
ensure contractor management teams can forecast, plan, and resource
appropriately and consistently. It will also provide baseline data for
analysis and subsequent improvement strategies to be developed.
2 LEVEL OF SURVEY
2.1 DEFINING THE Before embarking on a condition survey it is necessary to establish its
TASK purpose and scope, and the nature of information required from the
survey.
All condition surveys are concerned with asset condition. However, the
extent to which the surveys are carried out and the information required
from them vary depending on the reason for the survey and the available
resource.
2.2 FREQUENCY OF The frequency at which surveys need to be carried out can be
SURVEY determined by taking into account the following:
© BSRIA BG 35/2012
LEVEL OF SURVEY 2
2.4 SIMPLE TESTS Where information is not available from operation and maintenance
AND INSPECTIONS records, it may be necessary for the surveyor to carry out some simple
tests and measurements on environmental conditions and plant
performance. These measurements might include:
2.5 SPECIALIST Specialist surveys are necessary where the technology involved or the
SURVEYS more specialist aspects of the item of plant or system to be surveyed
demand it.
The use of specific measuring tools requires the use of trained surveyors.
Table 1 lists some of the plant or systems that require specialist surveys
requiring specific skills and knowledge.
2.6 PLANT AND The scope of the survey should include examination of some or all of
INSTALLATION the following aspects:
ATTRIBUTES THAT
SHOULD BE • functional suitability
EXAMINED
• operational integrity
• physical condition
• compliance with legal and health and safety requirements
• conditions affecting operation and maintenance
• economic life and obsolescence.
© BSRIA BG 35/2012
LEVEL OF SURVEY 2
2.7 FUNCTIONAL These are the elements of the survey that relate to the assessed suitability
SUITABILITY AND of plant to serve the business function and are important attributes of the
OPERATIONAL
INTEGRITY plant which can affect client business profitability.
Figure 3 Pipework
2.8 PHYSICAL The physical condition of building services plant can be observed
CONDITION through visual inspections and by other methods of non-destructive
testing.
© BSRIA BG 35/2012
LEVEL OF SURVEY 2
2.9 COMPLIANCE Asset conditions must comply with legal and health and safety
WITH LEGAL AND requirements. There is a vast amount of UK legislation that impacts on
HEALTH AND
SAFETY the building services plant and installations. For example The Health and
REQUIREMENTS Safety at Work Act 1974 and its supporting regulations have requirements
for plant and installations to be operated and maintained in safe
conditions and without detriment to health. They also have
requirements for conditions such as cleanliness of ductwork, adequacy
and level of task lighting and safety of electrical installations.
Note that the above list is not exhaustive and that different legislation
may be applicable in different parts of the UK. All UK legislation can be
accessed at www.legislation.gov.uk, and a detailed schedule of legislation
affecting building services can be found in the BSRIA Legislation and
Compliance Online Database which can be accessed through the BSRIA
website.
2.10 CONDITIONS The ability to operate and maintain building services without hindrance
AFFECTING as well as minimising downtime in the case of a failure can be extremely
OPERATION AND
MAINTENANCE important to business activities. The surveyor should note such
conditions that will cause downtime of critical plant items beyond
acceptable levels. Aspects of plant and installation configurations that can
seriously affect the ability to maintain and reduce downtime include:
• access to critical equipment
− personnel access
− ease of carrying tools and materials
− access for plant and equipment (such as lifts and hoists)
• space for doing the work
− ergonomics
− manoeuvring space for persons
− space for removing and replacing components such as boiler tubes
• built-in features for safe maintenance
− guards
− lockable switchgear
• information on operation and maintenance
− operation and maintenance manuals
− record drawings
− asset register
− planned preventive maintenance records
− health and safety file.
2.11 THE REASONS The survey, subject to the requirements of the brief, should identify
FOR plant that could become obsolete due to any of the reasons below.
OBSOLESCENCE
Physical obsolescence
Physical obsolescence happens when the physical condition of an item is
no longer acceptable. Abuse and vandalism can also cause an item to be
discarded before the end of its economic life.
Economic obsolescence
The economic life of an item of plant or system is the number of years
beyond which the item of plant will not represent a cost effective option
in providing the required function.
Functional obsolescence
An item is functionally obsolete when its function is no longer required.
Equipment that is not needed to support the business requirements
should be treated as functionally obsolete.
© BSRIA BG 35/2012
LEVEL OF SURVEY 2
Technological obsolescence
New technologies are being continually expanded into the building
services industry. The willingness to include this modern technology can
make existing equipment obsolete.
3.1 SETTING The operational and maintenance conditions of certain assets are often
PRIORITIES more important to businesses than those of others. The deterioration of
certain assets may also carry significant core business risks, health and
safety risks, penalties including the depreciation of asset value and non-
compliance with legislation that could affect business success.
a) critical services - services that are crucial and have a direct impact
on the core business of the organisation, those which affect health and
safety or compliance with legal requirements (for example, electrical
services for essential computer operation, task lighting)
b) essential services - services that significantly contribute to and have
a short term impact on the core business activities (for example,
heating where there are no other means of providing heating)
c) important services - services that are less significant but could have
long term impact on it to the core business activities (for example,
ventilation of certain areas)
d) desirable services - services that have no direct bearing on core
business activities but are desirable to the organisation (for example,
decorative lighting).
© BSRIA BG 35/2012
HOW TO DO A CONDITION SURVEY 3
3.2 SAMPLING Where there are similar installations working under similar conditions
(for example, services in a number of similar dwellings) it is economical
Watchpoint to carry out sample surveys. This consists of carrying out a survey of a
Where the cost of failure representative sample of installations and extrapolating the results to
is high it is not advisable draw conclusion about all installations. This is a cost-effective way of
to base surveys on
sampling techniques.
assessing future maintenance needs for planning budgets.
3.3 CO-ORDINATION Building fabric, services and other surveys may be carried out by
WITH OTHER different surveyors because of the different skill sets and experience
INSPECTIONS
required.
3.4 STARTING A condition survey of building services plant and installations requires an
assessment of their ability to perform and their visible physical condition.
It requires an approach that combines information from a variety of
sources including:
The extent to which all the survey activities are included in a single
exercise depends on the client’s requirements, budget and the ability of
an organisation to take up all the constituent activities. It is important
that the brief for the condition survey should clearly describe the extent
to which these activities are to be covered.
3.5 USE OF IN-HOUSE In-house operation and maintenance staff are an invaluable source of
STAFF RESOURCES information. They carry vital knowledge of plant and installation
conditions, their operational status and maintenance problems.
Wherever possible maintenance staff should be attached to the survey
team.
3.6 SELECTING AND Condition surveys, or parts of them, may be carried out by in-house
COMMISSIONING A maintenance staff, contractors or consultants with sufficient competence.
SURVEYOR
Different work tasks (for example, specialist tests) can be contracted to
different parties and co-ordinated by the persons leading the survey (for
example a lead consultant or the client’s maintenance advisor).
3.7 GATHERING The gathering of generic and technical information about the assets that
INFORMATION need to be examined is a pre-requisite to the condition survey process.
© BSRIA BG 35/2012
HOW TO DO A CONDITION SURVEY 3
The extent to which the required data is available from existing records
varies from one organisation to another. An asset register or other forms
of comprehensive asset records may not exist and asset information may
need to be built up while carrying out the survey.
3.8 DATA CAPTURE A significant part of a condition survey is examining plant and recording
DURING condition information. Surveyors spend considerable time on site
CONDITION
SURVEYS gathering and recording condition data. An important pre-requisite of
the survey process is to determine the extent to which data is collected.
Consideration should be given to:
The way this data is collected, recorded and stored can affect the cost, the
outcome of the survey and the use of data at a future time.
3.9 DATA The basic information about the assets provides a basis for collecting data
REQUIREMENTS about the plant condition. Core data such as equipment type and
location is static and does not change in the short term. Once in a
database, data only requires checking and updating. Basic asset
information includes:
• asset identity/reference
• description of the asset
• location
• date of installation
• functional requirements
• importance to client business
• acceptable maintenance condition.
Watchpoint
Too often the inclusion Property and plant data should be accessible to the maintenance staff as
of new information into
an integral part of their role within the building. However, some
as-built drawings is
omitted from the work organisations maintain fragmented information about their assets. A
arising from surveys. As recent BSRIA guide on Building Manuals provides a template to gather
these drawings are used together all of the important information, which could be a
by maintenance staff in recommendation to the occupier after the survey is completed.
carrying out this work it
is imperative that these Computer based asset registers may contain information in a format that
are updated along with
the O&M’s.
can be downloaded to a computer based system used for collecting
condition data.
3.10 ASSET TRACKING Building an asset register and recording core information required for
AND BARCODING condition surveys becomes an easier task with barcoding or radio
frequency identification (RFID) devices and asset tracking systems.
In the past asset registers were paper documents which seldom got
updated as doing so was an unwieldy task. Technology that captures asset
information should be built in at the initial construction stage.
With the use of technology, asset tracking and maintaining asset registers
becomes a much easier task.
© BSRIA BG 35/2012
HOW TO DO A CONDITION SURVEY 3
3.11 CONDITION DATA The task associated with condition recording is to assess plant and
installation conditions against a reference standard of acceptability. The
information recorded is usually a statement about plant symptoms from
which the likelihood of failure or non-compliance can be evaluated.
This information will help the surveyor to justify the findings in the
report.
3.12 DATA STRUCTURE The level at which data is collected is important and will depend on the
purpose of the survey and the size, complexity and nature of engineering
systems.
3.13 METHOD OF DATA The method of collection should provide easy and quick means of
COLLECTION collecting data, validating it and transferring the relevant information to
permanent records held elsewhere.
1. paper-based
2. hand-held technology.
Hand-held technology
Hand-held technology has the advantage of holding electronic
information that can be referenced while being used to capture data.
Using hand-held technology greatly reduces the processing time required
and speeds up the reporting process.
3.14 IDENTIFICATION An asset coding structure should be agreed. Each element of the code has to
OF ASSETS be clearly understood and recognised by everyone who is likely to use it.
For a clear understanding of the asset there must be clarity in all aspects -
not only what it is, but where it is installed. This ensures that everyone is
discussing the same asset.
© BSRIA BG 35/2012
HOW TO DO A CONDITION SURVEY 3
Giving 134/001/CHW/NRV/054
Giving MNB/B01/PR01/LTHW/CPP/001
3.15 SCOPE OF Generic tasks that form a part of a full condition appraisal include:
CONDITION
SURVEYS • external examination of plant items and installations
• evaluation of the performance of plant and installations
• evaluation of the operation and maintenance conditions of plant and
installations
• carrying out specialist inspections and internal examinations
• co-ordinating information from inspections and tests carried out
previously
• co-ordinating information from other sources
• evaluation of compliance with health and safety and legal
requirements
• analysis of condition data and information
• identifying future maintenance requirements, their priorities and time
scales
• identifying funds required to carry out this work
• developing a knowledge base of the condition of plant and
installations.
[1]
The publication Stock Condition Surveys states that the scope of the
condition survey should be driven by the client’s objectives in
commissioning the survey in the first place. It also goes on to say that
there is no ‘standard package’ for condition surveys. A detailed briefing
process is required to establish the exact purpose for which the
information is to be used before the condition survey is finalised.
3.16 GENERAL TOOLS The surveyor needs to carry (or have access to) equipment and tools to
AND EQUIPMENT give access to plant, installations and test/measuring instruments for
specific tests and measurements. A list of general equipment and tools is
provided below.
© BSRIA BG 35/2012
HOW TO DO A CONDITION SURVEY 3
3.17 DUCTWORK AND The cleanliness of both ductwork and pipework is extremely important
PIPEWORK and must be considered as part of any complete survey. A valid condition
CLEANLINESS
assessment sometimes requires invasive examination.
Ductwork
Discolouration around intake and supply grilles can give a general guide
as to the cleanliness of the ductwork. However, the use of boroscopes
and mirrors can greatly enhance the inspection of the ductwork
supported with the use of swabs and analysis. The use of cameras, both
still and video, can support the eventual report made on duct cleanliness
and assist in the decision on whether or not to clean.
Pipework
The cleanliness of pipework can be assessed by chemical analysis. The
surveyor should have access to records on dosing and bacteriological
contamination. If laboratory results indicate high levels of metal in the
water, inspection of internal pipe surfaces should be carried out. If there
are high levels of contamination or evidence of pseudomonas, it may be
necessary to replace pipework.
4 NON-DESTRUCTIVE TESTING
4.1 GENERAL The purpose of this section is to provide a general overview of some
non-destructive techniques commonly used to evaluate the condition of
plant and installations. Where it is intended to use such techniques,
further advice should be sought from a specialist in the field.
Thermal imaging can also be used to detect heat losses from building
fabric and pipes, air leakage, leaks in chimneys and flues and leaks from
underground mains.
© BSRIA BG 35/2012
NON-DESTRUCTIVE TESTING 4
4.3 POWER QUALITY There is concern in the industry about the quality of electrical power
SURVEYS systems used to run buildings. The increased usage of IT and other
electronic equipment has exacerbated power quality problems such as
Harmonic Distortion.
The harmonics that are prevalent in this type of system can combine in
amplitude in the neutral conductor to a value greater than that of the
phase current even under well balanced load conditions.
Acoustic emission
The vibration within a piece of rotating equipment such as a pump or a
fan creates stress within the materials from which they are made, caused
by friction, cavitation and impacts. These emit high-frequency sound
which can be measured to give an overall condition of the plant.
The time taken to carry out the test is short. Repeated tests are an
accurate, cost effective and practical way of obtaining operating
information.
4.5 ULTRASONIC Ultrasonic methods use sound waves of short wavelength and high
FLAW DETECTION frequency (ultrasound) to detect flaws or measure material thickness.
AND THICKNESS
GAUGING Pulsed beams of ultrasound are used, via a hand-held transducer placed
on the object to be tested. Any defects reflect the sound back to the
transducer. Flaw size, distance and reflectivity can be interpreted. This is
a complex task and specialist skills are required to do this work.
© BSRIA BG 35/2012
NON-DESTRUCTIVE TESTING 4
4.6 EDDY CURRENT Eddy current testing is an electromagnetic technique and can only be
TESTING
used on conductive materials. Its applications include crack detection,
detection of flaws, size variations, or material variation.
When the eddy currents in the specimen are distorted by the presence of
flaws or material variations, the impedance in the coil is altered. This
change is measured and displayed in a manner that indicates the type of
flaw or material condition.
4.7 LEAK DETECTION Leak detection methods can be used to determine the integrity of
METHODS materials and joints in pipework, ductwork and pressure systems.
5 GRADING
5.1 THE USE OF It is essential that a level of uniformity is employed for key information
RANKING SYSTEMS and observations, such as asset condition and maintenance priorities.
5.2 GRADING ASSET The following is a grading system used to identify information about the
CONDITION condition of assets and for evaluating future facilities plans and
maintenance strategies. A uniform system for grading asset condition can
accurately identify assets that should be monitored more frequently.
Such a grading system can be used to specify the level to which the
condition of the plant should be improved, for example from a current
condition “C” to the required condition “B”. The following system is
recommended but can be modified to suit the particular situation.
Priority 1 Health and safety (such as compliance with stature and/or duty)
Priority 2 Neglect that might lead to damage or reversion
Priority 3 Neglect that might affect current rental income
Priority 4 Necessary to maintain in ‘repair’
© BSRIA BG 35/2012
SURVEY TOOLKIT 6
6 SURVEY TOOLKIT
6.1 INTRODUCTION The purpose of this section is to provide direction to some checks that
may be included in condition surveys. The items listed have been based
on common defects and other issues relating to plant and installation
conditions that could give rise to future maintenance requirements.
They have been derived from case studies, discussion with clients and
maintenance organisations, site visits and BSRIA studies on durability.
The aim is to provide an aide mémoire to generic checks and common
defects. It should not be regarded as comprehensive.
6.2 OVERVIEW AND Before the start of the survey, certain essential information needs to be
PRE-SURVEY available and other necessary arrangements need to be in place. These
CHECKS
include:
6.3 COMMON Table 5 – Table 15 list the common defects or problems of a generic
DEFECTS nature related to building services.
Defect
Signs of deterioration, in particular premature deterioration. The root cause of the
deterioration should be identified where possible
Damage or missing equipment and components, such as lagging or vapour barriers
Jammed isolation (including safety isolation) devices such as valves
Incorrect parts
Disconnected parts or components
Water leaks/pooling of water
Poor drainage
Inadequate testing and commissioning points
Commissioning points in the wrong place
Inadequate protection, for example lack of protection against weather damage
Undue damage or deterioration to plant
Environmental factors that can adversely affect plant such as pollutants, dust, high
temperature and high humidity
Signs of mishandling or abuse of plant items
Unusual operational conditions such as smells, noise, vibration, leaks and excessive
surface temperature
Adverse internal conditions. Where possible check internal condition by removing
access covers, and sections of lagging
Watchpoint Defect
The conditions affecting Lack of good quality, comprehensive record drawings and O&M manuals including the
plant operation and health and safety file
maintenance are crucial
to service delivery. If Inadequate personnel access to plant rooms
plant cannot easily be Inadequate access for plant, equipment and materials such as lifting gear
operated or maintained
to provide the services Inadequate access for maintenance such as withdrawal of boiler tubes
required for them, Unavailability of spares
modifications may need
to be carried out. Lack of personal protective equipment
Inadequate means of isolation, locking off and barriers
Lack of redundant or standby plant to maintain service needs during maintenance
shut-downs
© BSRIA BG 35/2012
SURVEY TOOLKIT 6
Watchpoint Defect
The operations and Consistent maintenance problems recorded in maintenance log books
maintenance records
should be examined and High maintenance costs
maintenance staff should Excessive energy consumption
be consulted to identify
conditions that signal the Trends of plant deterioration, for example an increase in vibration
need for repairs or Electrical loads that exceed the safe capacity of the supply
replacements.
Defects reported as part of specialist examinations
Defect
Unavailability of emergency equipment in plant rooms, for example alarms,
emergency telephones, panic buttons, and emergency isolation devices
Lack of safety equipment in plant rooms, such as rubber matting in front of electrical
switch panels
Inadequate means of escape from plant rooms
Lack of first aid equipment
Inadequate safety signs and posters
Inadequate warning and danger notices
Inadequate guards and barriers, particularly in the case of rotating and moving
machinery
Lack of means of local isolation for maintenance, particularly in the case of remotely
controlled machinery
Inadequate security of plant rooms
Presence of hazardous substances in plant rooms without adequate precautions, for
example unsecured gas bottles
Hazards in plant rooms due to lack of headroom, holes, and trenches without
adequate identification such as warning tapes and protection.
Generally unsafe plant rooms, for example slippery floors, uneven floors and steep
ramps
Undue noise in plant rooms
Undue noise in other areas emanating from building services plant
Inadequate guards and rails against falling, for example on roof areas, access gantries
and platforms
Inadequate heating, ventilating and lighting in plant rooms
Use of plant rooms as storage areas
Defect
Redundant cables and switchgear
Inadequate identification and labelling of switchgear, distribution boards and circuits
Inadequate display of warning and danger notices
Inadequate mechanical protection of cable systems
Inadequate protection of cable systems against other causes of damage and
deterioration such as heat and chemicals
Cables and conductors exposed due to damage, corrosion, and missing covers
Inadequate means of isolation
Inadequate means of locking off after isolation (where required)
Inadequate means of emergency switching
Inadequate or damaged barriers or enclosures
Inappropriate circuit protective devices for example rewirable fuses where there
should be HRC fuses or MCBs
Lack of barriers against unauthorised tampering
Broken or disconnected earthing systems
Damaged flexible conduits
Inadequate main incoming power supply
Inadequate power supply to specific areas
Overloading of circuits
Insufficient number of socket outlets resulting in safety hazards such as trailing cables
Improper segregation of cables
Defect
Inadequate lighting levels
Inappropriate luminaires for the type of work carried out for example those which
cause glare on computer screens
Switching arrangements unacceptable to the client
Inadequate emergency lighting. Guidance is found in British Standard BS 5266 -
Emergency Lighting. Part 1[ 11]
© BSRIA BG 35/2012
SURVEY TOOLKIT 6
Defect
Redundant plant and pipework
Inadequate identification of pipework systems
Inadequate boiler capacity or inadequate supply of heat to particular areas
(complaints from occupiers or operational records may indicate possible shortages)
Back-end corrosion of the boiler
Boiler section cracks
Restricted flow due to waterside fouling
Air-side fouling caused by poor combustion
Inadequate supply of combustion air to the boiler house
Inadequate hot water capacity and supply points
Inability of the hot water system to achieve hot water storage and supply
12
temperature requirements stated in HS(G) 70[ ]
Inadequate arrangements for pasteurising calorifiers
Presence of dead legs in domestic hot water pipework configuration
Unsafe hot water temperature for the type of occupant
Unlagged pipework causing undue heat emission in specific areas or causing danger to
occupants
Incorrect type of heat emitters for the type of occupant, for example high radiator
surface temperatures in homes for the elderly, or emitters with sharp edges where
persons could harm themselves
Obstruction to heat distribution from heat emitters for example radiators obstructed
by furniture
Inadequate barriers against unauthorised tampering and operation
Defect
Noise and vibration in fans
Dampers not operational or disconnected from actuators
Differential pressure devices removed or not having fluid in them
Leaking ductwork or air-handling units
Incorrect positioning of main air intake and outlet points, for example allowing the
possibility of cross contamination
Dirty or blocked main air intake and outlet louvres
Dirty or broken filters
Incorrectly sized fan systems, for example as a result of areas no longer being served
by the system
Ventilation control devices such as flow control devices working incorrectly
Dirty or mouldy AHU housings
Water side and air side fouling of heat exchangers
Water stagnation in drip trays
Damaged fins and coils in heater/cooler batteries
Blocked humidifier nozzles and scaling of steam humidifiers
Dirty ductwork systems
Defect
Supply and extract grilles blocked by furniture
Poor drainage of condensate from fan coil units and free-standing air conditioning
units
Excessive or inadequate air movement in conditioned spaces
Incorrect balancing - particularly after changes to systems
Positive and negative pressure areas not being maintained as expected
Air leakage at doors or windows
Use of portable/temporary heaters in conditioned space.
Defect
Incorrect positioning of sensors
Excessive hunting of actuators leading to increased wear
Disconnected controls such as actuators
Poor ventilation of control panels
Timeswitches set incorrectly
Set points set incorrectly
Damaged sensor casings
No calibration records of sensors
Manual overrides not removed
Defect
Lack of emergency instructions
Lack of emergency equipment
Inadequate lift shaft lighting and ventilation
© BSRIA BG 35/2012
SURVEY TOOLKIT 6
6.4 FACTORS There is no definitive way of determining the economic life of an item
AFFECTING THE of plant. It can, however, be estimated. Published figures provide a
ECONOMIC LIFE [ 13] [14]
OF PLANT starting point. BS ISO 15686-1 and CIBSE Guide M recommend a
factored approach. Some factors which affect the economic life of plant
are given in Table 16.
• Damage caused at the installation stage can reduce the life of some equipment such as
finned heat exchangers, and room air conditioning units
• Installations on rooftops with exposure to wind, rain and snow could deteriorate
prematurely
• Susceptibility to damage, abuse and vandalism could reduce the life of plant
Quality and standard of maintenance
• The adequacy of planned maintenance
• Excessive operation can affect plant items, particularly moving and rotating equipment
System compatibility
• Compatibly of different materials installed in a system, for example in a water system
copper installed upstream of steel pipes can cause serious corrosion
Document reference:
Project title:
Project number:
Revision control:
Revision Description Originator Date Approved by Date
Document distribution:
Recipient name Recipient title Date of issue Revision
Pre-survey checks
Initial and
Tick if
Item relevant
date when Notes or comments
completed
© BSRIA BG 35/2012
APPENDIX B
Manufacturer: Type/model:
Comment:
Pre-survey checks
Initial and
Item Tick if relevant date when Notes or comments
completed
No
Not
checked
Not
applicable
Are there any undue water leaks, pooling of water or signs Yes
of poor drainage? No
Not
checked
Not
applicable
Not
checked
Not
applicable
Initial and
Item Tick if relevant date when Notes or comments
completed
Not
checked
Not
applicable
No
Not
checked
Not
applicable
Not
checked
Not
applicable
Not
checked
Not
applicable
No
Not
checked
Not
applicable
© BSRIA BG 35/2012
APPENDIX C
REFERENCES
1 Stock Condition Surveys - A Guidance Note, RICS. 2005. ISBN 978 184219 227 6
2 BS 3811:1993. Glossary of Terms used in Terotechnology. ISBN 0 58022 484 8 (proposed for
withdrawal)
4 Special Report 249. Legislation Non - Compliance and Condition Appraisal Systems. BMI 1996.
ISBN 978 1900 85853 6
6 BSRIA AG. 17/97. Safe Thermal Imaging of Electrical Systems (Up to and Including 1000V a.c.. 1997.
ISBN 0 86022 470 8
7 BSRIA FMS 5/99. Guidance and the Standard Specification for Thermal Imaging of LV Electrical
Installations. ISBN 0 86022 516 X
8 BSRIA FMS 6/99. Guidance and the Standard Specification for Thermal Imaging Testing of Non-
Electrical Building Services Installations. ISBN 0 86022 540 2
9 BSRIA BG 39/2011. Thermal Imaging of Building Fabric. ISBN 978 86022 705 2
11 BS 5266:1999. Emergency Lighting. Part 1: Code of Practice for the Emergency Lighting of Premises Other
than Cinemas and Certain Other Specified Premises used for Entertainment. ISBN 0 58033 044 3 (Now
withdrawn)
nd
12 HSG (70). The Control of Legionellosis Including Legionnaires’ Disease. 2 Edition. HSE Books 1993.
ISBN 0 717 604519 (Replaced in 2000)
13 BS ISO 15686-1:2011. Buildings and Constructed Assets. Service Life Planning: General Principles and
Framework. ISBN 978 0 580 60675 5
14 CIBSE Guide M – Maintenance Engineering and Management. 2008. ISBN 978 1 903 28793 4
© BSRIA BG 35/2012
BSRIA ⳮ the built
environment experts
BSRIA gives you confidence in design, added value in
manufacture, competitive advantage in marketing,
profitable construction, and efficient buildings
Testing Troubleshooting
Modelling Information
Research Training
Consultancy Publications