Professional Documents
Culture Documents
along the length of the right keel at aisle level, which forms the return duct. The cabin airflow directs more air to the left side of
the cabin to accommodate the air loss when the passenger door is open.
B. Pressurization Control
The pressurization system provides a comfortable cabin air pressure from ground level to an altitude of 41,000 feet. The system
functions by regulating the outflow of air from the cabin through the outflow valves. The system is designed to maintain safe
structural pressure limits, while requiring minimal attention from the flight crew. Refer to Figure 3.
The inflow system provides a continuous source of bleed air to pressurize the pressure vessel. The pressurization system
regulates the outflow of air from the pressure vessel to maintain cockpit and cabin pressurization. The cabin pressurization
controller operates the outflow valves by providing a control signal that modulates the position of the outflow valves.
C. Baggage Compartment Heating
The optional baggage compartment heating system uses heat from the bleed air lines to warm the compartment. The system
replaces segments of the bleed air inflow tubes with finned tube heat exchangers and a plenum. Air is drawn from the baggage
compartment and circulated through the plenum, across the heat exchangers, and returned to a distribution duct along the top of
the baggage compartment. Refer to Figure 4.
D. Heating
The cockpit and cabin are heated using bleed air that is cooled. Each zone, cabin and cockpit, operates independently of the
other. The cockpit is heated by bleed air from the left engine and the cabin is heated by bleed air from the right engine. Bleed
air is cooled by the inflow system located in the upper aft fuselage. The inflow system temperature modulating valves control the
mix of bleed air from the engine and cooled bleed air from the heat exchanger. After the bleed air is mixed to the proper
temperature, the warm air is ducted into the air distribution system. The distribution system routes the air to the cockpit and
cabin downstream of each zone blower. In the cabin, bleed air for heating and pressurization is only distributed to the left and
right sidewall ducts. Warm air is emitted upward through long narrow slots between the sidewall and armrest.
Warm air is also emitted downward towards the floor for foot warming and from the left sidewall towards the passenger door.
In the cockpit, warm air outlets are provided at the aft end of the pilot's and copilot's circuit breaker sidewall consoles. The air
from these outlets sweeps upward and forward along the cockpit side windshields. Warm air is also ducted to the front
windshields for defrosting and to the foot warmer outlets forward of the rudder pedals. The temperature control system controls
the inflow system. Refer to Temperature Control, in Chapter 21-60-00, for information regarding the inflow system and heat
system temperature control. Refer to the Distribution System, in Chapter 21-20-00, for information regarding the cockpit, cabin,
and aft fuselage distribution ducts.
E. Cooling
The compressor motor module is located in the aft avionics bay. The module consists of a variable displacement compressor, a
28 VDC motor, a drive belt, compressor and motor pulleys, an hour meter, and various mounting brackets and hardware. The
28 VDC motor allows the compressor to operate on auxiliary power prior to engine start for cooling on the ground. An
evaporator and blower are located in the cockpit and aft cabin to provide zone cooling. Each zone has its own solenoid
operated shutoff valve to control the flow of refrigerant. Air filters are installed in the recirculation air return. All air outlets in the
system emit cold air. Eyeball outlets are provided in the overhead panel at all seat locations and the cockpit. Two additional
outlets are located in the instrument panel. Refer to Figure 5.
F. Temperature Control
The temperature control system uses bleed air to heat the cockpit and cabin. Bleed air is also used for pressurization, air
ventilation, engine inlet and wing anti-icing, and windshield defrost. The temperature control switches, CKPT and CABIN
AUTO/MAN TEMP, provide a selectable temperature range of approximately 65° F to 85° F for all normal operational in-flight
temperatures. Refer to Figure 6.
5. Components
A. Distribution
The distribution system consists of the components used to duct and distribute air to the cockpit and cabin environmental
systems including the heating, cooling, and pressurization systems. Refer to Figure 2. The distribution system includes the
following components:
• Bleed Air Source Select Switch
• Control Relays
• Cockpit Bleed Air Flapper Check Valve
• Cockpit Alternate Air Valve
• Air Outlet
• Cabin Bleed Air Flapper Check Valve
B. Pressurization Control
The pressurization control system maintains cabin air pressure at a comfortable level regardless of outside altitude. This is
achieved by feeding a constant supply of bleed air from the engines and regulating the amount of air that is permitted to escape
through the outflow valves. A pressurization controller regulates the outflow of air from the primary and secondary outflow valves.
Refer to Figure 3.
The pressurization control system consists of the components used to control the pressure within the fuselage including the
following:
• Cabin Pressurization Controller
• Secondary Outflow Valve
• Pressurization Mode Switch
• Cabin Pressure Annunciators
• Primary Outflow Valve
• Cabin Altitude High Switch
• Ambient Static Pressure Ports
• Cabin Altitude and Pressure Differential Indicator
C. Heating
The cockpit and cabin are heated using bleed air that is cooled in the aft fuselage inflow system. The bleed air is ducted into the
cabin and cockpit distribution system. The temperature control system controls the inflow system and senses the cabin and
cockpit temperatures. Refer to Chapter 21-60-00, TEMPERATURE CONTROL, for information regarding the cockpit and cabin
heat. Refer to Figure 6.
D. Baggage Compartment Heating
The optional baggage compartment heating system consists of the components which supply heated air to the baggage
compartment (Refer to Figure 4) .including the following:
• Aft Baggage Heating Tube Elements
• Baggage Heat Switch
• Baggage Heat Blower
• Baggage Blower Controller
• Aft Baggage Heat Relay
E. Cooling
The cooling system is a vapor cycle refrigerant type. An electric motor/compressor module and a condenser are installed in the
aft fuselage. The motor/compressor module supplies refrigerant to separate cockpit and cabin evaporators. The two zones
(cockpit and cabin) have separate blowers, controls, and sensors. Refer to Figure 5.
The cooling system consists of the following components:
• Compressor Motor Module
• Load Shed Controller
• Condenser Blower
• High Pressure Cutout Switch
• Low OAT Temperature Cutout Switch
• Service Ports
• Cockpit Evaporator
• Expansion Valves (Cockpit /Cabin)
• Solenoid Operated Shutoff Valves (Cockpit/Cabin)
• Cockpit Blower
• Soft Start Module
• Condenser
• Receiver Dryer
• Low Pressure Cutout Switch
• A/C Over Pressure Reset Switch
• A/C Under Pressure Reset Switch
• Cabin Evaporator
• Evaporator Filters (Cockpit/Cabin)
• Cockpit/Cabin Blower Switch
• Cabin Blower
F. Temperature Control
The temperature control system consists of the components which are used to maintain the cockpit and cabin air temperature.
The temperature control system controls the flow of bleed air heat from the inflow modulating valves and cooled air from the
vapor cycle system. The temperature control system can be operated in the auto or manual mode. The airplane is divided into
two zones, cockpit and cabin, for temperature control. Each zone operates independently with separate controls, sensors, and
equipment. Refer to Figure 6.
The temperature control system consists of the following components:
• Heat Exchanger Blower
• Cockpit Ram Air Heat Exchanger
• Auto/Manual Temperature Switches (CKPT/CABIN)
• Inflow System Temperature Modulating Valves
• Cockpit Zone Temperature Sensor
• Vent Duct Temperature Sensors (Cockpit/Cabin)
• Vent Duct Overtemperature Thermal Switches (Cockpit/Cabin)
• Temperature Controllers (Cockpit/Cabin)
• Cabin Ram Air Heat Exchanger
• Cabin Temperature Control (Armrest)
• Temperature Control Cockpit/Cabin Switch
• Bleed Air Duct Temperature Sensors (Cockpit/Cabin)
• Cabin Zone Temperature Sensor
• Bleed Air Duct Overtemperature Thermal Switches (Cockpit/Cabin)
closed. The valves supply bleed air to the inflow modulating valves and heat exchangers. The cockpit alternate air valve
connects the right (cabin) bleed air inflow lines to the left (cockpit) bleed air inflow lines. The cockpit alternate air valve allows
bleed air inflow from the right engine to be diverted to the cockpit distribution system.
The bleed air control relays are located on the forward side of the cockpit pedestal. The bleed air control relays are energized
by the bleed air source select switch. The relays control the operation of the left and right bi-level flow control valves and the
cockpit alternate air valve.
The cabin bleed air flapper check valve is installed in the outlet port of the cabin thermal isolator in the cabin inflow line. The
cockpit bleed air flapper check valve is located aft of the cockpit alternate air valve in the cockpit inflow line. The flapper check
valves prevent bleed air from flowing back through the cabin and cockpit inflow systems. A second cockpit bleed air flapper
check valve is located in the bleed air line downstream of the cockpit bleed air line fuselage penetration. This cockpit check
valve helps retain cabin pressurization in the event of a bleed air line leak. Refer to Figure 2.
B. Cockpit Distribution System
The cockpit distribution system provides cooled conditioned air, recirculated air, and bleed air heat to the cockpit. Inlet air to the
blower is drawn thru a grill located at the step between the cabin and cockpit. The cockpit blower draws air through the
evaporator and discharges into the fan outlet duct which splits into left and right ducts. During cooling system operation, the
recirculated air is cooled by the evaporator and discharged through the left and right ducts to all the cockpit air outlets, the foot
warmers, and the windshield defrost duct. During heating system operation, bleed air is supplied to the left duct providing
heated air for the windshield defrost ducts, cockpit foot warmers, and side console air outlets. The right duct will supply
recirculated air to the instrument panel and the overhead ducts. Refer to Figure 3.
C. Cabin Distribution System
The cabin distribution system provides cooled conditioned air, recirculated air, and bleed air heat to the cabin. The cabin
distribution system consists of two sidewall and two overhead source ducts supplying the air outlets. The sidewall ducts emit air
downward to the lower sidewalls for foot warming and upward along the upper sidewalls through slots between the sidewall
panel and armrest. The left sidewall duct also provides warm air directed across the cabin door. The overhead source duct
supplies air to the overhead air outlets which may be directed and regulated from the full open to closed position by the
passengers. The sidewall air supply can be cooled and heated as necessary, while the overhead supply ducts provide
cooled/recirculated air only. The return air is through the area below the floor along the length of the right keel at aisle level,
which forms the return duct. During heating system operation, bleed air is plumbed into the trifurcate duct from the empennage
and distributed to the sidewall ducts to provide heated air to the lower cabin. During cooling system operation, the return air is
cooled by the evaporator and discharged into the overhead source duct. Refer to Figure 4.
4. Components
A. The distribution system consists of the components used to distribute air for the cockpit and cabin heating, cooling, and
pressurization systems including the following:
• Bleed Air Source Select Switch
• Cockpit Bleed Air Flapper Check Valve
• Bleed Air Control Relays
• Bi-Level Flow Control Valve
• Cabin Bleed Air Flapper Check Valve
• Air Outlets
• Cockpit Alternate Air Valve
B. Bleed Air Source Selection Switch
The bleed air source select switch is a six-position, rotary switch with three banks that controls both bi-level flow control valves
and the cockpit alternate air valve. The bleed air source select switch is located in the ENVIRONMENTAL section of the right
inboard subpanel. The bleed air source select switch allows the crew to select the source and amount of the bleed air. The
switch has the following positions: OFF, L, NORM, R, HIGH, CKPT ALTN. In the NORM position, bleed air from the right engine
is provided to the cabin and bleed air from the left engine is provided to the cockpit. The bleed air flows through the normally
open bi-level flow control valves to the modulating valves at the low flow rate.
When the switch is in the HIGH position, bleed air flows through the bi-level flow control valves at the high flow rate to provide
maximum heating. In the L ENG position, the left bi-level flow control valve opens to the HIGH flow stage and the right bi-level
flow control valve is closed. In the R ENG position, the right bi-level flow control valve opens to the HIGH flow stage and the left
bi-level flow control valve is closed. When the switch is in the CKPT ALTN position, the cockpit alternate air valve diverts right
engine bleed air at the high flow rate to the cockpit and shuts off the left bi-level flow control valve. Refer to Figure 5 and Figure
8.
valve. When the source select switch is rotated to either the left (L) or right (R) engine position, 28 VDC energizes the L or R
BLEED AIR CONTROL VALVE HI RELAY (21K2, Left; 21K5, Right). The relay is closed and provides 28 VDC to the high flow
solenoid on the selected bi-level flow control valve. The opposite bi-level control valve receives 28 VDC through the L or R
BLEED AIR CONTROL OFF RELAY (21K1, Left; 21K4, Right) to energize the valve closed.
DISTRIBUTION - ADJUSTMENT/TEST
1. Bleed Air System Operational Check
A. Test Setup Procedures
(1) Perform the ENGINE GROUND OPERATING PROCEDURES (Ref. 71-00-00, 601).
B. Operational Check
Table 501. Adjustment/Test (Procedure 0T or Procedure 0NT)
ACTION RESULT
1. Set the battery switch to BAT.
2. Open the following circuit breakers on the Aft
Circuit Breaker Panel:
• CAB BLWR (21CB17)
• CKPT BLWR (21CB20)
11. At the pilots circuit breaker panel, open the R Low bleed air inflow is expelled at cabin ducting while circuit
BLEED VALVE circuit breaker. breaker is open.
Cockpit ducting inflow ceases while circuit breaker is open.
12. At the pilots circuit breaker panel, close the R
BLEED VALVE circuit breaker.
13. Set the BLEED AIR switch to OFF. Bleed air inflow expelled at cabin and cockpit ducting ceases.
16. Turn CKPT temperature switch to INC to initiate Monitor air outlets in the cockpit. Make sure airflow at the
bleed air circulation to the cockpit distribution windshield defrost outlet and side consoles remains ambient.
system.
17. Open the pilot and copilot foot warmer outlets. Monitor the foot warmer outlets. Make sure airflow at the foot
warmer outlets remains ambient.
18. Set the CABIN BLOWER switch to HI. Airflow at the cabin air outlets should increase.
19. Turn the CABIN temperature switch to INC to Monitor the lower air outlets in the cabin. Make sure airflow at
initiate warm air circulation to the cabin. the outlets remains ambient. (Does not warm).
NOTE:
If the air conditioning compressor begins to operate, turn the CKPT temperature switch to INC until the
compressor shuts down.
43. Monitor the pilot and copilot foot warmer outlets. Make sure air temperature at the foot warmer outlets does not
warm and returns to ambient.
44. Turn the CABIN temperature switch to DEC to Monitor the lower air outlets in the cabin. Make sure airflow at
reduce the bleed air temperature to the cabin. the outlets does not warm and returns ambient.
NOTE:
If the air conditioning compressor begins to operate, turn the CABIN temperature switch to INC until the
compressor shuts down.
45. Close the following circuit breakers on the Aft
Circuit Breaker panel:
• CAB BLWR (21CB17)
• CKPT BLWR (21CB20)
C. Follow On Procedures
(1) Perform the ENGINE SHUTDOWN procedure (Ref. 71-00-00, 601).
Figure 401 : Sheet 1 : Cockpit Bleed Air Flapper Check Valve Installation
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
Figure 401 : Sheet 1 : Cabin Bleed Air Flapper Check Valve Installation
(10) Make sure foot warmer cable (15) is in closed (OFF) position (Ref. Figure 401, Detail E, Sheet 2 of 2).
(11) Install foot warmer cable (15) and clamp (16), to bracket (17) with screw (13) and washer (14) (Ref. Figure 401, Detail C,
Sheet 1 of 2).
(12) Install foot warmer cable (15) to link hinge (20) with foot warmer pin (18) using washers (19) and nuts (21), then tighten
(Ref. Figure 401, Detail C, Sheet 1 of 2). Maintain clearances as shown in Figure 401, DetailsE and F, Sheet 2 of 2.
Adjust as required.
(13) Use a suitable tool to bend and lock foot warmer cable (15) end to an angle of 50° upward.
NOTE: If interference is found between foot warmer cable (15) connection and operation of the rudder foot
pedal, remove and re-install connection using alternative method shown in Figure 401, Detail D, Sheet 1
of 2.
(14) Perform a functional test on foot warmer control cable (15). Make sure hardware does not interfere with rudder pedals
when fully extended.
(15) Apply a light coat of lubricating oil (02-002, Table 401) to the foot warmer hinge pin (18).
(16) Perform CREW SEAT INSTALLATION procedure and install pilot's seat (Ref. 25-10-01, 401).
(17) Perform MAIN BATTERY CONNECTING procedure (Ref. 24-30-00, 301) and remove all caution tags.
C. Follow On Procedures
(1) Make sure work area is clean and clear of tools and other equipment.
Depressurization mode which positions both outflow valves to the full open position. When the throttles are moved to 80% N1 or
greater, the system enters the Pre-Pressurization mode. In this mode, the cabin is pressurized slightly and the door seal pressurizes
to avoid pressure bumps during takeoff. When the airplane lifts off, the Weight-on-Wheels invalid signal (open) from the L GND
SAFETY RELAY No. 1 (32K4) is applied to the pressurization controller. If the pressurization mode switch (21S2) is in the AUTO
position, the pressurization system will enter the auto schedule mode.
The primary outflow valve is electronically controlled and pneumatically positioned. Pneumatic pressure provided to the valve is
passed through an integral ejector. The ejector provides a vacuum to a servomotor-controlled pressure regulator and to the normally
closed vacuum solenoid valve. The controller will provide a voltage (-12 VDC to 12 VDC DC) to the servo motor which will change
the pressure regulator setting. This regulated pressure is applied to the outflow valve chamber to open or close the valve. If the
regulated pressure is less than the cabin pressure, the valve will open. If the pressure is equal to or higher than the cabin pressure, an
internal spring will close the valve. A potentiometer senses the position of the regulating valve and provides feedback to the
controller. The controller provides voltage to the potentiometer (typically 5 VDC differential between the "top" and "bottom") and it
monitors the return "wiper" voltage (0 to 5 VDC). A removable filter is located under the primary outflow valve cover to filter the small
amount of cabin air that is flowing through the internal pressure regulator.
The primary outflow valve is interconnected pneumatically with the secondary outflow valve to control the valve position and regulate
cabin airflow. Both valves have independent maximum cabin differential pressure protection and cabin altitude limiting devices. The
cabin differential pressure limiting device is set to 8.3 ±0.1 PSID. Ambient air pressure is used by the maximum differential limiters
to open the outflow valves, if required. The altitude limit regulators incorporated into both outflow valves will limit the cabin altitude to
13,500 ± 1,500 feet.
The vacuum solenoid in the primary outflow is normally closed (de-energized) in flight. Vacuum from the ejector will pass through the
valve when it is energized open to pull the outflow valves open. It will be energized when the airplane is on the ground to prevent the
cabin from pressurizing. The solenoid valve is an integral part and is not field serviceable. Power to the vacuum solenoid is
interrupted when any of the following conditions exist:
• Airplane is off the ground.
• Throttle is above 80% N1 (Pre-pressurization)
• Controller Test Mode is selected
• ADC is providing an input of 15,000 feet or higher
The DUMP solenoid valve in the primary outflow valve is normally closed and only energized open when the DUMP mode is selected.
Ambient static air is ported to the dump solenoid valve and used to pull the outflow valve open in an emergency condition. The
solenoid valve is not a field serviceable item.
4. Components
A. Cabin Pressurization Controller
The cabin pressurization controller is located on the pressurization control panel in the center instrument panel below the
annunciator panel. The cabin pressurization controller maintains and controls the cabin pressure by providing an electrical
control signal to the outflow valves which modulates the position of the outflow valves. The pilot input to the cabin pressurization
controller for normal operation (AUTO mode), is landing field altitude. Isobaric or manual control modes are also available for
pilot selection. The cabin altitude, flight level, cabin rate, climb/descent arrow, and mode are displayed on the pressurization
controller. Refer to Figure 2 (Sheet 2 of 2).
B. Pressurization Mode Switch
The pressurization mode switch is located on the pressurization panel to the right of the pressurization controller. The
pressurization mode switch (21S1) is a five-position switch with four sets of contacts. The switch controls the mode of the
pressurization system. The switch positions are: TEST, OFF, AUTO, MAN, and DUMP.
C. Primary Outflow Valve
The primary outflow valve is installed in the right pressure can on the cabin side of the aft pressure bulkhead. The primary
outflow valve regulates the outflow of cabin air to provide a comfortable and safe environment for the crew and passengers. The
primary outflow valve operates in conjunction with the secondary outflow valve. The primary outflow valve receives electrical
signals from the pressurization controller allowing the pressurization system to monitor and adjust the cabin pressure. The
primary outflow valve contains a removable filter which is accessed by removing three screws and a cover located on the face
of the valve.
The primary outflow valve exhaust air flows through the can on the aft side of the aft pressure bulkhead and is routed by a duct to
an exhaust plenum on the bottom of the airplane. This ducts the moist air from the cabin out of the airplane.
The primary outflow valve has the following environmental interfaces:
• Air pressure connection to a regulated bleed air source for ejector operation. This bleed air input is filtered and applied
to the vacuum ejector (located within the primary outflow valve) for operation of the primary and secondary outflow valves.
• Ambient static air pressure port connection for maximum differential pressure reference located on the lower aft
fuselage shell at FS 382 and RBL 15.
• Static source air pressure connection for ejector exhaust and condensation drain.
• Air pressure connection to the secondary outflow valve.
D. Secondary Outflow Valve
The secondary outflow valve is installed in the left pressure can on the cabin side of the aft pressure bulkhead. The secondary
outflow valve regulates the outflow of cabin air to provide a comfortable and safe environment for the crew and passengers. The
secondary outflow valve operates in conjunction with the primary outflow valve. The secondary outflow valve receives pneumatic
input from the primary outflow valve.
The secondary outflow valve exhaust air flows through the can on the aft side of the aft pressure bulkhead and is routed by a
duct to an exhaust plenum on the bottom of the airplane. This ducts the moist air from the cabin out of the airplane.
The secondary outflow valve has the following interfaces:
• Ambient static line pressure port connection for maximum differential pressure reference. The static port is located on
the lower aft fuselage at FS 382 and RBL 12.
• Air pressure connection to the primary outflow valve.
E. Cabin Altitude High Switch
The cabin altitude high switch is located on the forward side of the pedestal on the right side of the cockpit. The cabin altitude
high switch (21S4) monitors the cabin pressure during flight. If the cabin altitude exceeds 10,000 +0/-500 feet, the cabin altitude
high switch will activate and supply a ground to the CABIN ALT HI indicator on the annunciator panel (31A4).
F. Cabin Pressure Annunciators
There are two cabin pressure annunciators associated with the pressurization system. The annunciators are located on the
annunciator panel which is located in the middle of the instrument panel just to the right of the centerline.
The CABIN ALT HIGH annunciator is illuminated when the cabin altitude high switch (21S4) provides a ground to the
annunciator panel (31A4). The ground is applied when the cabin altitude high switch senses a cabin altitude of 10,000 +0/-500
feet.
The PRESS CTL FAIL annunciator is illuminated when the pressurization controller loses the air data input from the data bus or
detects an internal failure via the Built-In-Test. The pressure controller receives input from the ARINC 429 data bus for the basis
of its computation and control of cabin pressure. The data received is barometric pressure and airplane pressure altitude. The
pressurization system will initiate a power-up BIT when first powered on. Then runs a time BIT continuously during the system
operation. Upon passing the power-up BIT, the system is released to enter the other modes. If the BIT fails or the air data input
is lost, the system automatically changes to the MAN mode and illuminates the PRESS CTL FAIL annunciator.
14. Rotate the pressurization mode switch to the MAN position. The airplane should remain de-pressurized.
15. Rotate the ALT SEL knob to -1000ft. The pressurization controller should display the selected
altitude and the airplane should remain de-pressurized.
16. Rotate and hold the pressurization mode switch in the TEST The door seal should inflate.
position.
17. Wait at least 15 seconds after switching to the TEST The airplane should pressurize at an initial rate of descent
position then rotate the ALT SEL knob to 0 ft. of no greater than 900 fpm (the cabin pressurization system
will not achieve an exact, unvarying dive rate every time it is
operated).
18. On the pressurization controller select an altitude of +3000 The airplane should de-pressurize at an initial rate of
ft. descent of no greater than 1200 fpm (the cabin
pressurization system will not achieve an exact, unvarying
dive rate every time it is operated).
19. Rotate the pressurization mode switch to the AUTO The pressurization controller should perform a LCD display
position. test after the release of the switch.
The cabin altitude indication on the pressurization panel
indicator should be approximately field (ground) altitude.
The door seal should deflate.
20. Advance the left and right thrust levers to 82 ± 2% N1. The airplane should pressurize at an initial rate of descent
of less than 500 fpm.
The airplane should remain pressurized for a minimum of
10 seconds
The door seal should inflate when the left thrust lever is
greater than 75% N1
21. Confirm the results in step 20 and return the left and right
thrust levers to the IDLE power position.
22. At the co-pilot circuit breaker panel open the #2 ADC circuit The PRESS CTL FAIL annunciator should come on and the
breaker. MASTER CAUTION lights should come on and flash.
23. At the co-pilot circuit breaker panel close the #2 ADC The PRESS CTL FAIL annunciator should go off and the
circuit breaker. MASTER CAUTION lights should go off.
24. Rotate the pressurization mode switch to the TEST position
then rotate it back to the AUTO position.
25. Rotate the pressurization mode switch to the MAN position.
26. Place the left weight on wheels (WOW) switch to the IN AIR The door seal should inflate.
position (vertical).
27. Wait at least 15 seconds after rotating the WOW switch to The airplane should pressurize at an initial rate of descent
the IN AIR position then rotate the ALT SEL knob to -1000 of less than 900 fpm.
ft.
28. Momentarily press the cabin door latch release button. The door seal should deflate while the cabin door latch
release is pushed.
29. Rotate the pressurization mode switch to the MAN position The airplane should de-pressurize at an initial rate of climb
and confirm the altitude selection of +3000 ft. of less than 1200 fpm.
30. Rotate the pressurization mode switch to the DUMP The airplane pressure should dump.
position.
31. Place the left weight on wheels (WOW) switch to the ON The door seal should deflate.
GROUND position.
32. Rotate the bleed air switch to the OFF position.
17. Wait at least 15 seconds after switching to the TEST The airplane should pressurize at an initial rate of descent
position then rotate the ALT SEL knob to 0 ft. of no greater than 900 fpm (the cabin pressurization system
will not achieve an exact, unvarying dive rate every time it is
operated).
18. During the 15 second test, spray 50% water and 50% mild Inspect for bubbles, note area and reseal as required.
soap mixture in the recently resealed area (cabin window,
escape hatch, windshields, main entry door seal).
19. On the pressurization controller select an altitude of +3000 The airplane should de-pressurize at an initial rate of
ft. descent, no greater than 1200 fpm (the cabin pressurization
system will not achieve an exact, unvarying dive rate every
time it is operated).
20 Rotate the pressurization mode switch to the AUTO The pressurization controller should perform a LCD display
position. test after release of the switch.
The cabin altitude indication on the pressurization panel
indicator should be approximately field (ground) altitude.
The door seal should deflate.
21. Rotate the pressurization mode switch to the DUMP The airplane pressure should dump.
position.
22. Rotate the bleed air switch to the OFF position.
23. Rotate the CKPT and CABIN temperature knobs to the
MAN-INC position for approximately 20 seconds.
24. Perform the ENGINE GROUND OPERATING procedure
(Ref. 71-00-00, 601) and shut down both engines.
4. Cabin Pressurization Leak Test
A. Safety Precautions
WARNING: Personnel who are detailed to work under pressurized conditions should be free from known medical
conditions such as obesity, heart conditions, respiratory conditions, or ear infections.
WARNING: The test equipment operator must be proficient in the setup and operation of the pressurization system
test equipment and operation of the airplane pressurization system.
WARNING: An inter-communication system shall be in operation to permit continuous voice contact with the
operator outside the cabin.
All personnel working inside the cabin while it is under pressure or operating the test equipment must be completely familiar
with and understand all of the following safety rules:
(1) The test equipment operator shall remain at the cabin tester (178, Table 501) whenever there is pressure inside the cabin.
(2) Before pressure is applied to the fuselage, the correct restraint must be put in position. Make sure that the cabin door net
(134, Table 501) is correctly installed.
(3) All electrical equipment used inside the cabin during pressurization must be of an approved design.
(4) The cabin tester (178, Table 501) must be turned on and stabilized for a minimum of 5 minutes before use.
(a) If the pressure gage is not reading exactly zero after 5 minute warm up, zero the gage by turning the zero adjustment
on the front cover of the pressure gage. Make sure that there is no pressure on the gage before it is zeroed.
(b) The vertical speed indicator must also be at zero ft/min.
(5) The cabin pressure hose must be free of leaks and the fittings must be tight to make sure that there are no leaks.
(6) Make sure there is a warning sign hanging from the door while there is pressure in the fuselage.
(7) Personnel inside the cabin shall not pull plugs, open outflow valves or do anything to speed up the rate of depressurization.
Too fast a rate could cause injury to occupants. Pushing open the outflow valve may damage the valve and cause
unnecessary rejection.
(8) When the fuselage is pressurized with personnel inside, the pressure shall not be changed at a rate in excess of 1,000 feet
per minute. There must be a least two people in the cabin while pressurized.
(9) When personnel are detailed to work inside the cabin while under pressure, the cabin pressure must not be more than 4.0
psi.
(10) Never put or use flammable substances inside the airplane while it is pressurized.
(11) All personnel involved with cabin pressurization shall understand and obey all safety rules as prescribed by any local or
company safety authority.
B. Cabin Tester Connection
(1) Make sure that the emergency exit hatch is secure. Perform the EMERGENCY EXIT HATCH INSTALLATION procedure
(Ref. 52-20-01, 401).
(2) Set the cabin tester (178, Table 501) into position.
(a) Connect the large grey hose to the cabin pressure service port in the aft maintenance bay with the adapter from the
adapter kit (179, Table 501).
CAUTION: The unused AN4 test port that is used to sense cabin pressure is never to be capped on the inside
of the airplane. If there is a cap installed on the inside, remove the cap before the sense line from
the cabin tester is connected. Never install a cap on the inside. When the test is complete cap the
open fitting on the outside with the correct cap.
NOTE: To check for an internal cap from outside the airplane, gently insert a length of safety wire into the
fitting.
(b) Connect the cabin sensing hose to the unused AN4 test port (Ref. Figure 504) on the aft pressure bulkhead.
(c) Tape the atmospheric vents for the left and right outflow valves closed.
(3) Connect the door seal hose to the pneumatic pressure service port in the aft maintenance bay. Cap the outflow valve
vacuum exhaust port on the right dump valve aft of the aft pressure bulkhead with the cap removed from the pneumatic
pressure service port.
(4) Connect the supply air hose from the cabin tester to the shop air supply. Connect the power cord, turn on the cabin tester
and let it warm up for 5 minutes before use.
(5) If necessary, load all equipment and personnel into the cabin. Make any necessary electrical and air connections and test
the intercom system.
C. Airplane Preparation
(1) Set the throttles to the NORM TAKEOFF position.
(2) Perform the CONNECTING AND APPLYING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(3) If a hydraulic power unit is connected to the airplane, perform the DISCONNECTING EXTERNAL HYDRAULIC POWER
procedure (Ref. 29-00-00, 301) and make sure that both hoses are disconnected from the airplane service ports before
any pressure is applied.
(4) Perform the CABIN ALTITUDE HIGH SWITCH REMOVAL procedure (Ref. 21-30-04, 401).
(5) Perform the OXYGEN BAROMETRIC PRESSURE SWITCH REMOVAL procedure (Ref. 35-20-05, 401).
D. Passenger Door Closing
CAUTION: If the door mechanism requires more force to latch the door from the outside than is required to latch it
from the inside, open the door and correct the problem. Never use too much force to close the cabin
door.
CAUTION: To make sure that the cabin door is correctly closed and latched for cabin pressure checks, the
following precautions must be taken.
(1) The passenger door rigging must be correctly adjusted. If necessary, perform the PASSENGER DOOR ADJUSTMENT
procedures (Ref. 52-10-01, 501).
(2) When personnel are present inside the cabin during pressurization, they must visually inspect all latching mechanisms to
make sure that the door is securely closed.
(3) If no personnel are present inside the cabin during pressurization, a door latch inspection is to be done through the right
flight deck window or cabin window to make sure that the door is latched correctly after the door has been closed from the
outside.
(4) After the door is closed, install the cabin door net (134, Table 501) into position over the door and tightly fasten the
buckles.
(5) Put the warning sign in position on the cabin door and turn on the red light on the pressure test cart.
CAUTION: Do not inflate the door seal while the door is open or unlatched.
(6) Close the DOOR SEAL circuit breaker (21CB3) on the aft relay panel. Apply 20 ± 2 psi to the pneumatic service port
plumbing by use of the DOOR SEAL switch and regulator.
NOTE: Make sure that the door seal is depressurized before the cabin door is opened after pressurization.
Open the DOOR SEAL circuit breaker (21CB3) on the aft relay panel to do this. Always unlatch the
cabin door before the safety net is unbuckled.
E. Cabin Leak Sealing
WARNING: Do not exceed 4.0 PSI with personnel inside cabin.
NOTE: Any necessary repairs to cabin sealing may be done during this test procedure.
(1) After the 5 minute warm up, make sure that the cabin pressure indicated on the main display and the cabin pressure
indicated on the electronic controller labeled CABIN PRESSURE are within 0.05 psi of each other. If within 0.05 psi, open
the air supply valve on the cabin tester. If not, the cabin tester will require servicing or repair.
(2) Locate the button labeled SCREENS below the main display.
(a) Press the SCREENS button. A list of pressure options should display.
(b) Rotate the thumb wheel (round button) located to the right of the screens display to move the highlight box up and
down.
(c) Put the highlight box on the pressure from 1.0 to 1.5 PSI option.
(d) Press the thumb wheel to select the pressure.
NOTE: After a selection is made, the tester will pressurize the cabin to that pressure if possible. It will
also control the rate of change. As the leaks are located and sealed, the cabin pressure will
begin to rise and flow will decrease. If the airplane leakage is too great to allow the tester to
reach the selected pressure, reselect a pressure lower than the existing pressure and allow
time for the tester to stabilize.
(e) Maintain flow and blower pressure as low as possible when sealing to reduce the wet sealer blow-out.
(3) Locate leakage and apply sealant in accordance with the appropriate SEALING procedures (Ref. 20-22-00, 201).
(4) Make sure that any work required in the airplane cabin has been completed.
(5) Set the tester SCREENS menu to 0 psi. to allow the cabin to depressurize.
NOTE:If at any time, the operator of the cabin tester decides that the tester is not operating correctly, the
operator is to first select 0 psi from the SCREENS menu. If the pressure does not begin to reduce in
a few seconds, the E-Stop button should be pressed in. This will disconnect the electrical power
from the air control system in the tester. The rate back to 0 psi will not be controlled. If in a rare
instance, the E-Stop has no effect, close the air supply valve on the side of the tester. Never leave
the tester unattended for more than a few seconds until it has reached a test pressure setting and
stabilized at that setting.
CAUTION: Never assume that the pressure in the cabin has returned to zero without looking at the cabin pressure
gauge on the tester. Always unlatch the door before removing the safety net.
(6) Make sure that the cabin pressure has returned to zero.
(7) Open the DOOR SEAL circuit breaker (21CB3) on the aft relay panel to depressurize the door seal.
(8) Remove the warning notice and unlatch the cabin door before the safety net is removed.
(9) Remove the safety net and open the cabin door to allow the personnel and equipment to be off loaded.
NOTE: Make sure that any applied sealer has cured before further pressure is applied to the cabin.
(10) Perform the rest of the FOLLOW ON MAINTENANCE procedures (this section, paragraph 4.I.) or perform the other tests
as required.
F. Leak Rate Tests
(1) Make sure that paragraphs 4.A. thru 4.D. have been completed.
(2) After the 5 minute warm up, make sure that the cabin pressure indicated on the main display and the cabin pressure
indicated on the electronic controller labeled CABIN PRESSURE are within 0.05 psi of each other. If within 0.05 PSI, open
the air supply valve on the cabin tester. If not, the cabin tester will require servicing or repair.
(3) LEAK RATE TEST AT 3.0 ± 0.1 PSIG
(a) Locate the button labeled SCREENS below the main display.
(b) Press the SCREENS button. A list of pressure options should display.
(c) Rotate the thumb wheel (round button) located to the right of the screens display to move the highlight box up and
down.
(d) Put the highlight box on the pressure 3.0 ± 0.1 PSI option.
(e) Press the thumb wheel to select the pressure.
NOTE: After a selection is made the tester will pressurize the cabin to that pressure if possible. It will
also control the rate of change. If the airplane leakage is too great to allow the tester to reach
the selected pressure, reselect a pressure lower than the existing pressure and allow time for
the tester to stabilize.
(f) When 3.0 ± 0.1 PSIG pressure can be achieved, let the cabin pressure stabilize for three minutes. View the
flowmeter. Read the flow from the level on the float. Make sure that the leakage at this pressure is 56 SCFM.
(g) Make sure that the acceptable leak rate of 56 CFM is not exceeded.
NOTE: If the leak rate cannot be obtained, perform the CABIN LEAK SEALING procedure in this
section to repair the leaks.
(h) Proceed to the next LEAK RATE TEST AT 8.0 ± 0.1 PSIG or Step (5).
(4) LEAK RATE TEST AT 8.0 ± 0.1 PSIG
(a) Locate the button labeled SCREENS below the main display.
(b) Press the SCREENS button. A list of pressure options should display.
(c) Rotate the thumb wheel (round button) located to the right of the screens display to move the highlight box up and
down.
(d) Put the highlight box on the pressure 8.0 ± 0.1 PSI option.
(e) Press the thumb wheel to select the pressure.
NOTE: After a selection is made the tester will pressurize the cabin to that pressure if possible. It will
also control the rate of change. If the airplane leakage is too great to allow the tester to reach
the selected pressure, reselect a pressure lower than the existing pressure and allow time for
the tester to stabilize.
(f) When 8.0 ± 0.1 PSIG pressure can be achieved, let the cabin pressure stabilize for three minutes. View the
flowmeter. Read the flow from the level on the float. Make sure that the leakage at this pressure is 56 SCFM.
(g) Make sure that the acceptable leak rate of 56 CFM is not exceeded.
NOTE: If the leak rate cannot be obtained, perform the CABIN LEAK SEALING procedure in this
section to repair the leaks.
(5) When the leak test is complete select 0 PSI on the from the SCREENS menu and the tester will reduce the pressure to 0
PSI.
NOTE: The tester will record the results and they can be printed for QA or record purposes.
G. Leak Rate Correction
Air density effects the accuracy of the flowmeter in the cabin tester, therefore a correction must be made to the indicated leak
rate to determine if the cabin leakage is below the allowable rate. To correct the flowmeter reading, record the indicated flow
(CFM), air temperature and the inlet pressure while the cabin is at 8.0 ± 0.1 PSI. After recording, refer to the correction chart
(Ref. Figure 503) and plot the corrected flow. The acceptable leakage should be on, or less than 56 SCFM at 8.0 ± 0.1 PSI and
56 SCFM at 3.0 ± 0.1 PSI. If leakage is unacceptable, continue to search for and repair excessive leakage.
H. Dump Valve Test
(1) After reaching and recording an acceptable leak rate, set the pressure to 7.8 ± 0.1 PSI.
(2) Remove the tape from the left outflow valve atmospheric vent. Increase the flow by 30 CFM. observe the rate of climb
gage. The outflow valve should open between 8.2 and 8.4 PSI indicated by a return to zero on the rate of climb gage.
(3) Re-tape the left outflow valve atmospheric vent.
(4) Repeat steps (1) thru (3) for the right outflow valve.
I. Follow On Maintenance
CAUTION: Never assume that the pressure in the cabin has returned to zero without looking at the cabin pressure
gauge on the tester. Always unlatch the door before removing the safety net.
(1) Make sure that the cabin pressure has returned to zero.
(2) Open the DOOR SEAL circuit breaker (21CB3) on the aft relay panel to depressurize the door seal.
(3) Remove the warning notice and unlatch the cabin door before the cabin door net (134, Table 501) is removed.
(4) Remove the cabin door net and open the cabin door.
(5) Return the throttles to CUT OFF.
(6) Perform the CABIN ALTITUDE HIGH SWITCH INSTALLATION procedure (Ref. 21-30-04, 401).
(7) Perform the OXYGEN BAROMETRIC PRESSURE SWITCH INSTALLATION procedure (Ref. 35-20-05, 401).
(8) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(9) Disconnect the cabin tester power cord and the shop air supply.
(10) Disconnect the door seal hose from the pneumatic pressure service port in the maintenance bay. Remove the cap from the
outflow valve vacuum exhaust port on the right dump valve and install the cap to the pneumatic pressure service port.
(11) Remove the tape from the atmospheric vents for the left and right outflow valves.
(12) Disconnect the cabin sensing hose from the unused AN4 test port on the aft pressure bulkhead (Ref. Figure 504). Install a
cap to the open fitting on the outside of the aft pressure bulkhead.
(13) Disconnect the cabin tester large grey hose from the adapter kit and disconnect the adapter from the service port. Install
the correct blank to the cabin pressure service port.
5. Cabin Altitude High Switch Functional Test
NOTE: The Cabin Altitude High Switch Functional Test may performed using either the GROUND TEST or FLIGHT
TEST METHOD to meet the test requirements. Both procedures are presented as alternate methods for
functionally testing the switch, it is not necessary to perform both tests to prove the switch.
A. Functional Test (Ground Test Method)
The cabin altitude high switch can be tested using a fabricated vacuum chamber.
(1) Fabricate a vacuum chamber from 3-inch schedule 40 PVC plumbing pipe or suitable equivalent, 4 to 8 inches long with
two end caps. One end cap is permanently attached to the plumbing pipe with PVC cement then drilled and tapped for an
AN816-4D fitting. The other end cap is a removable closure. Material required for the vacuum chamber may be obtained
locally. Refer to Figure 502 for an example of a fabricated vacuum chamber.
(2) Remove the left pedestal side panel upholstery to gain access to the cabin altitude high switch.
(3) Remove screws (4) and washers (3) securing the cabin altitude high switch (1) to the bracket (2). Do not disconnect the
electrical connector from the cabin altitude high switch (1). Cut the tie wraps from the wire harness to allow adequate length
to place the cabin altitude high switch (1) in the vacuum chamber (Ref. Figure 501).
(4) Suspend the vacuum chamber from the airplane structure to eliminate strain on the cabin altitude high switch (1) wires.
Place the switch inside the vacuum chamber with the wires exiting the chamber from the locations referenced in Figure
502. Install the end cap then apply plumbers putty or equivalent around the wires to seal the chamber.
(5) Perform the CONNECTING AND APPLYING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301)
(6) Connect an altimeter test unit (099, Table 501) or similar device with a certified altimeter to the fitting on vacuum chamber.
Set the altimeter to 29.92 inches of Hg.
(7) Slowly increase the vacuum in the chamber and check for leaks. Make adjustments to the end cap and apply plumbers
putty as required to reduce leak rate to a manageable amount. Total sealing may not be possible.
(8) Slowly increase the vacuum in the chamber and note the altitude at which the CABIN ALT HI annunciator illuminates. The
annunciator shall illuminate at 9,500 to 10,000 feet (20.96 to 20.58 inches of Hg).
(9) Slowly decrease the vacuum in the chamber and note the altitude on the test unit at which the CABIN ALT HI annunciator
light extinguishes. The annunciator light shall extinguish at a decreasing minimum altitude of 8,500 feet (21.80 inches of
Hg). Allow the vacuum chamber to return to atmospheric pressure.
(10) The switch must be replaced if it does not meet these specifications.
(11) Disconnect the test unit from the fitting on the vacuum chamber
(12) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(13) Remove the cabin altitude high switch (1) from the vacuum chamber (Ref. Figure 501). Do not disconnect the electrical
connector from the cabin altitude high switch
(14) Secure the cabin altitude high switch (1) with screws (4) and washers (3) and secure wire harness with tie wraps.
(15) Install the left pedestal side panel upholstery.
B. Functional Test (Flight Test Method)
The cabin altitude high switch can be tested during flight.
WARNING: During the following functional test, the pilot shall wear his oxygen mask in the normal mode. During
the flight, the pilot will utilize a calibrated hand-held altimeter set to 29.92 inches Hg.
(1) Fly the airplane at an altitude between 13,000 to 15,000 feet.
(2) The pilot should select MAN on the cabin pressurization switch and select 11,000 feet altitude.
(3) As cabin altitude rises, the pilot will note the cabin altitude at which the CABIN ALT HI annunciator illuminates from the
hand-held altimeter (099, Table 501). The annunciator shall illuminate at 9,500 to 10,000 feet cabin altitude.
(4) The pilot shall then select AUTO and landing altitude on the cabin pressurization switch.
(5) As the cabin pressurizes, the pilot will note the cabin altitude at which the CABIN ALT HI annunciator extinguishes. The
annunciator shall extinguish by 8,500 feet altitude upon descent.
Figure 502 : Sheet 1 : Vacuum Chamber Fabrication and Cabin Altitude High Switch Test Setup
A. Replacement
The primary outflow valve filter (3) is located inside the faceplate of the primary outflow valve (Ref. Figure 402).
(1) Perform the MAIN BATTERY DISCONNECTING procedure (Ref. 24-30-00, 301) and disconnect the main battery and tag
the connector with a caution tag indicating "DO NOT RECONNECT".
(2) Perform the AFT COMPARTMENT UPHOLSTERY PANEL REMOVAL procedure (Ref. 25-40-02, 401) and remove the
aft lavatory upholstery to gain access to the primary outflow valve (2) (Ref. Figure 402).
(3) Remove the screws (5), washers (4) and faceplate (1) from the primary outflow valve (2).
CAUTION: Do not use a sawing motion when cutting through the sealant as this will introduce sealant particles
into the valve.
When prying the cover from the valve body, do not use metal tools or implements that will scratch the
anodized aluminum surface.
(4) Insert a razor blade or exacto knife between the faceplate (1) and the valve (2) body to cut through the sealant. Slide the
blade through the sealant to separate the faceplate (1) from the primary outflow valve (2). Use a plastic putty knife to gently
pry the faceplate (1) loose.
(5) Cover the exposed opening of the valve using masking tape (09-035, Table 401). Do not cover the residual sealant
adhering to the bottom cover if sealant is present.
(6) Gently rub the sealant from the bottom cover, if sealant is present.
(7) Remove the masking tape and clean the flat portion of the bottom cover and any residual sealant from the faceplate with
isopropyl alcohol (06-001, Table 401).
(8) Allow the cover and valve to dry completely.
(9) Remove filter (3) from the sheet metal rails (6).
(10) Install a new filter (3) in the sheet metal rails (6) with the smooth side facing outwards.
(11) Apply a bead of sealant (05-016, Table 401) around the perimeter of the filter (3). Make sure all gaps are sealed.
(12) Apply a bead of adhesive sealant (05-016, Table 401) around the perimeter of the faceplate (1) and at the recess of the
screw holes.
(13) Align the faceplate (1) with the primary outflow valve (2) and install the screws (5) and washers (4). Wipe off any excess
adhesive from the faceplate.
(14) Remove the caution tag and perform the BATTERY CONNECTING procedure (Ref. 24-30-00, 301).
CAUTION: Allow a minimum of four hours for the sealant to cure before operating the pressurization system.
(15) Perform the PRIMARY OUTFLOW VALVE FUNCTIONAL TEST procedure (Ref. 21-30-02, 501).
(16) Perform the AFT COMPARTMENT UPHOLSTERY PANEL INSTALLATION procedure (Ref. 25-40-02, 401) and install the
aft lavatory upholstery.
4. Primary Outflow Valve Filter (Effectivity: Airplanes prior to RB-302 With 390-384024-0009 Valve Installed; RB-302 and
After)
A. Replacement
The primary outflow valve filter (3) is located inside the faceplate cover (2) of the primary outflow valve (Ref. Figure 403).
(1) Perform the MAIN BATTERY DISCONNECTING procedure (Ref. 24-30-00, 301) and disconnect the main battery and tag
the connector with a caution tag indicating "DO NOT RECONNECT".
(2) Perform the AFT COMPARTMENT UPHOLSTERY PANEL REMOVAL procedure (Ref. 25-40-02, 401) and remove the
aft lavatory upholstery to gain access to the primary outflow valve (2) (Ref. Figure 403).
(3) Remove the screws (1) from the faceplate cover (2) of the primary outflow valve (4).
CAUTION: When prying the cover from the valve body, do not use metal tools or implements that will scratch the
anodized aluminum surface.
(4) Use a plastic putty knife to gently separate the faceplate cover (2) loose.
(5) Carefully remove the filter (3) and discard.
(6) Align the new filter (3) flange flush against the faceplate cover (2).
(7) Align the "C" on the faceplate cover (2) over the connector (5) on the valve (4).
(8) Apply a thin bead of adhesive sealant (05-016, Table 401) under the screw heads and secure the faceplate cover (2) and
filter (3) to the valve (4) with the three screws. Tighten the screws and make sure the perimeter of the cover is sealed.
(9) Remove the caution tag and perform the BATTERY CONNECTING procedure (Ref. 24-30-00, 301).
CAUTION: Allow a minimum of four hours for the sealant to cure before operating the pressurization system.
(10) Perform the PRIMARY OUTFLOW VALVE FUNCTIONAL TEST procedure (Ref. 21-30-02, 501).
(11) Perform the AFT COMPARTMENT UPHOLSTERY PANEL INSTALLATION procedure (Ref. 25-40-02, 401) and install the
aft lavatory upholstery.
Figure 402 : Sheet 1 : Primary Outflow Valve Filter Replacement (Effectivity: Airplanes prior to RB-302 without 390-384024-0009 Valve
Installed)
Figure 403 : Sheet 1 : Primary Outflow Valve Filter Replacement (Effectivity: Airplanes prior to RB-302 with 390-384024-0009 Valve
Installed; RB-302 and After)
8. Select an altitude of -1000ft. Make sure both outflow valves remain open.
9. Advance thrust levers to full power. Make sure both outflow valves partially close and the pressure
tester connected to the 3-way solenoid valve (1) should read
20 ± 5 PSIG (Ref. Figure 501).
10. Return thrust levers to IDLE. Make sure both outflow valves open and the door seal tester
depressurizes to 0 PSIG.
11. On airplanes prior to RB-100 without Kit 390- Make sure both outflow valves close.
8103 Installed, rotate the left squat switch to the "in The pressure tester connected to the 3-way solenoid valve (1)
air" position (Ref. 32-00-00, 201). On airplanes should read 20 ± 5 PSIG.
prior to RB-100 with Kit 390-8103 Installed, and
RB-100 and After, depress and hold the squat
switch plunger to the "in air" position (Ref. 32-00-
00, 201).
12. Momentarily press the cabin door latch release Make sure pressure tester connected to the 3-way solenoid
button. valve (1) reads 0 PSIG while the button is pressed.
13. Set the pressurization mode switch to DUMP Make sure there is an audible sound (clunk) from the primary
(PULL). outflow valve.
4. Rotate the BLEED AIR switch to NORM. At the copilot sub-panel, the cabin altitude indication on the
CABIN ALT/DIFF PRESS indicator should be approximately
field (ground) altitude.
The cabin altitude indicated on the PRESSURIZATION panel
indicator should be approximately field (ground) altitude.
5. Rotate the PRESSURIZATION MODE switch to the Airplane should remain de-pressurized.
MANUAL position.
6. Rotate the ALT SEL knob to -1000 feet. Selected altitude should be displayed on the pressurization
controller and the airplane should remain de-pressurized.
7. Rotate the PRESSURIZATION MODE switch to the The door seal should inflate.
The airplane should pressurize at an initial rate of descent of
TEST position and hold. Wait at least 15 seconds
900 fpm.
after switching to TEST, then rotate the ALT SEL
knob to 0 feet. The cabin altitude indication on the hand held altimeter (099,
Table 501) should stabilize at 0 ± 300 feet.
8. Rotate the ALT SEL knob to +3000 feet. The airplane should de-pressurize at an initial rate of climb of
1200 fpm.
9. Return the PRESSURIZATION MODE switch to the Door seal should deflate.
AUTO position. The pressurization controller display should perform a LCD
display test.
The cabin altitude indicated on the PRESSURIZATION panel
indicator should be approximately field (ground) altitude.
10. Advance the LEFT and RIGHT thrust levers to 82 ± The door seal should inflate when the left throttle lever is
2% N1 greater than 75% N1 (approximately).
The airplane should pressurize at an initial rate of descent of
less than 500 fpm and should remain pressurized for at least
ten seconds.
11. Confirm the results obtained in step (10) and return
the LEFT and RIGHT thrust levers to the IDLE
position.
12. At the copilots circuit breaker panel, OPEN the #2 The PRESS CTL FAIL annunciator illuminates and the
ADC circuit breaker. MASTER CAUTION lights illuminate and flash continuously.
13. At the copilots circuit breaker panel, CLOSE the #2 The PRESS CTL FAIL annunciator should turn OFF and the
ADC circuit breaker. MASTER CAUTION lights should turn OFF.
Rotate the PRESSURIZATION MODE switch to the
TEST position and then return it to the AUTO
position.
14. Rotate the PRESSURIZATION MODE switch to the
MANUAL position.
15. On airplanes prior to RB-100 without Kit 390- The door seal should inflate.
8103 Installed, rotate the left squat switch to the "in
air" position (vertical) (Ref. 32-00-00, 201). On
airplanes prior to RB-100 with Kit 390-8103
Installed, and RB-100 and After, depress and
hold the squat switch plunger to the "in air" position
(Ref. 32-00-00, 201).
16. Wait at least 15 seconds after switching the squat The airplane should pressurize at an initial rate of descent of
switch to the "in air" position, then rotate the ALT less than 900 fpm.
SEL knob to -1000 feet.
17. Momentarily push the CABIN DOOR LATCH The door seal should deflate while the CABIN DOOR LATCH
RELEASE button. RELEASE button is pushed.
18. With the PRESSURIZATION MODE switch set to The airplane should depressurize at an initial rate of climb of
the MAN position, rotate the ALT SEL knob to less than 1200 fpm.
+3000 feet.
19. Rotate the PRESSURIZATION MODE switch to the Airplane pressure should dump.
DUMP position.
20. On airplanes prior to RB-100 without Kit 390- Door seal should deflate.
8103 Installed, rotate the left squat switch to the
"on ground" position (Ref. 32-00-00, 201). On
airplanes prior to RB-100 with Kit 390-8103
Installed, and RB-100 and After, release the
squat switch plunger and allow to go to the "on
ground" mode (Ref. 32-00-00, 201)
21. Rotate the BLEED AIR switch to the OFF position.
22. Rotate the PRESSURIZATION MODE switch to the
AUTO position.
23. Rotate the COCKPIT TEMPERATURE knob and
the CABIN TEMPERATURE knob to the MANUAL-
INC position for approximately 20 seconds.
C. Follow On Procedures
(1) Perform the ENGINE SHUTDOWN procedure (Ref. 71-00-00, 601).
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
Figure 401 : Sheet 1 : Cabin Altitude and Differential Pressure Indicator Installation
HEATING - ADJUSTMENT/TEST
1. Baggage Heat System Functional Test
A. Test Setup Procedures
(1) Perform the CONNECTING AND APPLYING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301)
B. Functional Test
ACTION RESULT
(1) Position the BAT switch to ON.
(2) Ensure the R BL AIR VALVE circuit breaker located on
the pilot's circuit breaker panel is closed.
(3) Ensure the BLEED AIR source select switch is in the
OFF position.
(4) Locate the aft baggage thermostat switch connector, and The aft baggage blower remains off.
jumper pins 1 and 2.
(5) Set the BLEED AIR source select switch to any position The aft baggage blower turns on and airflow is noted in
except OFF. the baggage duct. (The baggage heat distribution duct is
located along the roof of the baggage compartment.)
(6) Open the AFT BAGGAGE HEAT circuit breaker on the The aft baggage blower turns off.
aft relay panel.
(7) Close the AFT BAGGAGE HEAT circuit breaker on the The aft baggage blower turns on.
aft relay panel.
(8) Open the R BL AIR VALVE circuit breaker on the pilot's The aft baggage blower turns off.
circuit breaker panel.
(9) Close the R BL AIR VALVE circuit breaker on the pilot's The aft baggage blower turns on.
circuit breaker panel.
(10) Remove the jumper wire from the aft baggage thermostat The aft baggage blower turns off.
switch connector.
C. Follow On Procedures
(1) Set the BLEED AIR source select switch (21S21) to OFF.
(2) Set the BAT switch to OFF.
(3) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
inrush current to a maximum of 400 amps. One second after full voltage has been applied to the motor, the bypass contacts.
Refer to Figure 4 (Sheet 3 of 3) and Figure 5 (Sheet 1 of 2).
C. Load Shed Controller
The load shed controller (21A20) is located on the aft fuselage avionics rack inboard of the anti-skid controller. The load shed
controller is part of the qualifying circuitry for the compressor. The controller receives 28 VDC from the NON-ESSENTIAL BUS
by the LOAD SHED CNTRL circuit breaker (21CB19). The controller is enabled by the cockpit or cabin modulating valves and
monitors inputs from the windshield heat (HI mode only), horizontal stabilizer de-ice, and engine start systems prior to
energizing the air conditioning system. The load shed controller will disable/interrupt the operation of the air conditioning system
and condenser blower when any of the following systems are operating: L WINDSHIELD HEAT (HI mode), R WINDSHIELD
HEAT (HI mode), HORIZONTAL STAB DE-ICE, L or R ENGINE START. When the controller is enabled by the cockpit or cabin
modulating valve, the load shed controller furnishes an output control signal to the condenser blower relay (21K9) and the soft
start module via the low outside air temperature switch (21S12), the low pressure cutout relay (21K15), and the high pressure
cutout relay(21K14). Refer to Figure 4 (Sheet 3 of 3) and Figure 5 (Sheet 1 of 2).
D. Condenser
The condenser is located along the center baggage wall in the right aft empennage compartment between FS 429 and FS 448.
The condenser transfers heat from the refrigerant to the atmosphere. The gaseous refrigerant is passed through a series of
finned coils transferring heat to the fins and condensing the refrigerant into a liquid. The air is blown overboard by the condenser
blower. Refer to Figure 4 (Sheet 3 of 3).
E. Condenser Blower
The condenser blower (21B5) is located in the right aft empennage at FS 439 and WL 95. The condenser blower draws air
from the left aft fuselage, through the condenser, and discharges the air through an overboard grill. The aft fuselage receives
ventilation air from an inlet on the left aft fuselage. The blower pulls ambient air through the condenser to cool the gaseous
refrigerant entering the condenser. As the refrigerant cools, the gaseous refrigerant condenses to a liquid which is circulated
through the receiver/dryer to the evaporators. The blower is powered from the NON-ESSENTIAL BUS by the CONDENSER
BLOWER circuit breaker (21CB16). The blower is controlled by the condenser blower relay (21K9) which is energized by the
load shed controller and its qualifying circuitry. Refer to Figure 4 (Sheet 1 of 3) and Figure 5 (Sheet 1 of 2).
F. Receiver Dryer
The receiver dryer is located in the right aft avionics compartment below the avionics rack, behind the battery. The receiver
dryer removes moisture and contaminants from the liquid refrigerant. The receiver/dryer has a sight glass located on the top to
monitor the refrigerant charge in the air conditioning system. The sight glass is used to view the flow of high pressure liquid
refrigerant. The presence of bubbles in the sight glass indicates low refrigerant charge or air in the system. Refer to Figure 4
(Sheet 3 of 3).
G. High Pressure Cutout Switch
The high pressure cutout switch (21S13) is located aft of the air conditioning service panel in the right aft avionics compartment.
The high pressure cutout switch tees off the high pressure refrigerant line between the receiver/dryer and evaporator. The cutout
switch protects the compressor from damage due to high system pressure. The cutout switch monitors the high pressure
refrigerant line and closes above 350 ± 10 PSIG. When the cutout switch closes, the high pressure cutout relay (21K14) is
grounded. The high pressure relay opens to cut off power to the soft start module and interrupts the operation of the compressor
motor. The high pressure cutout relay also energizes and illuminates the yellow OVER AIR CONDITIONING LOCK OUT (reset)
switch on the air conditioning service panel. Refer to Figure 4 (Sheet 2 of 3) and Figure 5 (Sheet 1 of 2).
H. Low Pressure Cutout Switch
The low pressure cutout switch (21S14) is located in the right aft avionics compartment inboard of the air conditioning service
panel. The low pressure cutout switch tees off the low pressure refrigerant return line between the evaporators and compressor.
The cutout switch protects the compressor from damage due to insufficient pressure. The cutout switch monitors the low
pressure refrigerant line and closes when the pressure falls below 6 ± 0.5 PSIG. When the cutout switch closes, the low
pressure cutout relay (21K15) is grounded. The low pressure cutout relay opens to cut off power to the soft start module and
interrupts the operation of the compressor motor. The low pressure cutout relay also energizes and illuminates the yellow
UNDER AIR CONDITIONING LOCK OUT (reset) switch on the air conditioning service panel. Refer to Figure 4 (Sheet 2 of 3)
and Figure 5 (Sheet 1 of 2).
I. Low OAT Temperature Switch
The low OAT temperature switch (21S12) is located on the center of the upper aft baggage wall at FS439 and LBL10. The low
OAT temperature switch prevents the compressor from operating when the air temperature is below 30 ± 5° F. The switch
opens to cutoff power from the load shed controller to the soft start module. The switch will reset at 50 ± 5° F. Refer to Figure 4
(Sheet 3 of 3) and Figure 5 (Sheet 1 of 2).
contaminants from the cockpit and cabin air prior to entering the evaporators and distribution ducts. Refer to Figure 4 (Sheet 2
of 3).
R. Evaporator Blower
There is an evaporator blower installed in each zone of the airplane to circulate air from the cabin into the distribution ducting.
Each blower is a centrifugal blower with a D.C. motor and integral three speed controller. The blowers are mounted to isolated
support brackets with saddle clamps to minimize vibration.
The cockpit evaporator blower (21A6) is located below the center floorboard (130AC) at FS 175 and BL 0. The cockpit blower
draws air from the cockpit intake vent on the floorboard through the evaporator filter and evaporator, then discharges the air into
the cockpit distribution ducting (Ref. 21-20-00). The cockpit blower receives power from the LEFT MAIN BUS by the COCKPIT
BLOWER circuit breaker on the AFT RELAY PANEL. Whenever there is power on the bus, the cockpit blower will operate. The
blower speed (LO, MED, HI) is controlled by the CKPT BLOWER switch located on the environmental control panel. The CKPT
BLOWER switch receives power through the COCKPIT BLOWER CONTROL circuit breaker on the pilot's circuit breaker panel.
The cabin evaporator blower (21A7) is located inside the fan box housing assembly on the right side of the lavatory at FS 335
and RBL 15. The evaporator blower draws air from the cabin through the evaporator filter, and evaporator, and discharges the
air into the cabin distribution ducting (Ref. 21-20-00). The cabin blower receives power from the NON-ESSENTIAL BUS by the
CABIN BLOWER circuit breaker on the AFT RELAY PANEL. Whenever there is power on the bus, the cabin blower will
operate. The blower speed (LO, MED, HI) is controlled by the CABIN BLOWER switch located on the environmental control
panel. The CABIN BLOWER switch receives power through the CABIN BLOWER CONTROL circuit breaker on the pilot's
circuit breaker panel. Refer to Figure 4 (Sheet 1 of 3) and Figure 6.
leakage.
CAUTION: Ensure there is nothing obstructing the airflow through the condenser and condenser blower. All
shrouds that control airflow through the condenser and must be installed before operating the system.
C. Air Conditioning System Refrigerant Leak Check (Partial Charge)
A reduction of cooling ability or the continual presence of bubbles in the refrigerant may indicate a partial loss of refrigerant. The
sight glass should be checked during system operation at maximum ambient and cabin temperatures. The sight glass is
located on the receiver dryer in the right aft fuselage. Streams of bubbles or foam in the glass indicate the refrigerant quantity is
low.
If a loss of refrigerant is suspected, the system plumbing or components should be inspected to determine the source of the
leak. Large leaks can be located by the appearance of oily spots where oil has been carried out by escaping refrigerant.
Smaller leaks can be detected by applying leak detector fluid (09-002, Table 201) or by using a refrigerant leak detector (135,
Table 201). The system must contain a partial charge in order to detect leaks. A solution test is accomplished by applying leak
detector fluid (09-002, Table 201) to an area suspected of leaking. Bubbles form if leaks are present. The electronic refrigerant
leak detector, (135, Table 201) includes a probe that is moved along plumbing to detect escaping refrigerant. The probe should
be held below the plumbing line because refrigerant is heavier than air. The probe should be capable of detecting leaks equal
to 1/2 ounce per year and will emit a flashing light or high-pitched sound when refrigerant is detected.
NOTE: Perform this procedure when a leak is suspected or a test of the system`s integrity is desired due to a
reduction in the cooling ability of the system.
(1) Use a refrigerant leak detector (135, Table 201) around the air conditioning system tubing connections to check for
refrigerant leakage.
(2) Tighten or replace any fittings which are determined to be leaking. Replace any components that are determined to be
leaking.
(3) Perform the AIR CONDITIONING SYSTEM REFRIGERANT CHARGING procedure (Ref. 12-10-01, 301).
(4) Use the refrigerant leak detector (135, Table 201) to verify the system is not losing refrigerant.
D. Air Conditioning System Refrigerant Leak Check (No Charge)
NOTE: Perform this procedure when there is no refrigerant charge due to leakage or component replacement.
(1) Connect a high pressure nitrogen cart (064, Table 201) to the high pressure service port (discharge) of the air conditioning
system.
(2) Connect a pressure gage (102, Table 201) to the low pressure service port (suction) on the air conditioning service panel.
(3) Apply a leak detector fluid (09-002, Table 201) to areas where leaks are suspected.
(4) Pressurize the system with a partial nitrogen charge to 150 PSIG and check the system for leaks.
(5) Tighten or replace any fittings which are determined to be leaking. Replace any components which are determined to be
leaking.
(6) Repeat this procedure until no leakage is detected and the system can maintain the nitrogen charge.
(7) Disconnect the pressure gage (102, Table 201) from the low pressure service port and disconnect the high pressure
nitrogen cart (064, Table 201) from the high pressure service port.
(8) Perform the AIR CONDITIONING SYSTEM REFRIGERANT CHARGING procedure (Ref. 12-10-01, 301).
COOLING - ADJUSTMENT/TEST
1. Information
Refer to Chapter 20-52-00, 201 for information on tools and equipment referenced in the table below. Refer to Chapter 20-53-00,
201 for information on recommended materials referenced in the table below.
Table 501. Tools/Equipment and Recommended Materials
ITEM TOOLS AND EQUIPMENT ITEM RECOMMENDED
MATERIALS
023 Air Conditioning Recovery Unit
024 Multimeter
027 Air Conditioning Service Gages
2. Air Conditioning System Functional Test
A. Test Setup Procedures
(1) Perform the CONNECTING AND APPLYING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301)
(2) Connect the air conditioning recovery unit (023, Table 501) to the airplane in accordance with the manufacturer's operating
manual.
(3) Connect the air conditioning service gages (027, Table 501) to the air conditioner service ports in accordance with the
manufacturer's operating manual.
(4) Perform the AIR CONDITIONING SERVICING procedure (Ref. 12-10-01, 301), and confirm the system is fully charged and
operating properly.
B. Functional Test
ACTION RESULT
WARNING:
Do not smoke while performing maintenance on R134a refrigeration systems.
WARNING:
Keep hands clear of moving components (blowers, motors, belts, etc.) while operating the system. Ensure that
other personnel working in the area are kept clear of moving equipment, intakes, and exhaust ducts.
CAUTION:
All personnel performing this procedure MUST be familiar with the operation and maintenance of R134a
refrigeration systems.
CAUTION:
Ensure there is nothing obstructing the airflow through the condenser and condenser blower. All shrouds that
control airflow through the condenser must be installed before operating the system.
1. Position the CKPT and CABIN auto temp control
switches to MANUAL.
2. Turn and hold the CKPT and CABIN auto temp switches The compressor shall begin to operate.
to DEC for 20 seconds.
3. Set the CKPT and CABIN BLOWER switches to HI. Ensure cooled air discharges from the cabin and cockpit
air outlets, after a few minutes.
4. Observe the service gages. 1. The discharge (high) side pressure increases.
2. The suction (low) side pressure decreases.
3. The system should be producing conditioned air within
five minutes run time.
CAUTION:
When observing R134a refrigerant in the sight glass, the milky appearance of R134a must not be mistaken for
bubbles or low refrigerant charge. Personnel MUST be familiar with R134a systems to distinguish correct
refrigerant charge.
5. Observe the airplane sight glass. There shall be no vapor bubbles (foam) visible.
6. Turn the air conditioning system off. Turn and hold CKPT The compressor shall shut off.
and CABIN AUTO TEMP switches to INC until the
compressor shuts off.
7. Set the BAT switch to OFF.
C. Follow On Procedures
(1) Disconnect the air conditioner service gages from the air conditioning service ports in accordance with the Manufacturer's
Operating Instructions for service equipment.
(2) Disconnect the air conditioning recovery unit from the airplane in accordance with the Manufacturer's Operating
Instructions for service equipment.
(3) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
3. Air Conditioning Load Shed System Functional Test
A. Test Setup Procedures
(1) Perform the AIR CONDITIONING SERVICING procedure (Ref. 12-10-01, 301), and confirm the system is fully charged and
operating properly. Confirm the condenser blower and heat exchanger blower are operational.
B. Compressor Drive Electrical Wiring Connection Functional Test
ACTION RESULT
WARNING:
Keep hands clear of moving components (blowers, motors, belts, etc.) while operating the system. Ensure that
other personnel working in the area are kept clear of moving equipment, intakes, and exhaust ducts.
CAUTION:
All personnel performing this procedure MUST be familiar with the operation and maintenance of R134a refrigerant
systems.
CAUTION:
Ensure there is nothing obstructing the airflow through the condenser and condenser blower. All shrouds that
control airflow through the condenser must be installed before operating the system.
1. Verify the BLEED AIR switch on the ENVIRONMENTAL
panel is OFF.
2. Verify the positions of the following switches on the ICE
PROTECTION PANEL:
L WSHLD...........OFF
R WSHLD...........OFF
WSHLD...............NORM
STAB..................OFF
3. Perform the CONNECTING AND APPLYING
EXTERNAL ELECTRICAL POWER procedure (Ref. 24-
40-00, 301).
NOTE:
If the air conditioner compressor begins operating when external power is applied, rotate and hold the CKPT and
CABIN auto temp control knobs to the MAN INC position for a minimum of ten seconds until the air conditioner
compressor stops operating.
4. On the ENVIRONMENTAL panel, rotate and hold the The air conditioning system and condenser blower start
CKPT auto temp control knob to the MAN DEC position operating.
for a minimum of ten seconds.
5. On the ice protection section of the subpanel, set the L The air conditioning system and condenser blower
WSHLD switch to the LO position. remain operating.
6. On the ice protection section of the subpanel, set the L The air conditioning system and condenser blower stop
WSHLD switch to the HI position. operating.
7. On the ice protection section of the subpanel, set the L The air conditioning system and condenser blower start
WSHLD switch to the LO position. operating.
8. On the ice protection section of the subpanel, set the L The air conditioning system and condenser blower
WSHLD switch to the OFF position. remain operating.
9. On the ice protection section of the subpanel, set the R The air conditioning system and condenser blower
WSHLD switch to the LO position. remain operating.
10. On the ice protection section of the subpanel, set the R The air conditioning system and condenser blower stop
WSHLD switch to the HI position. operating.
11. On the ice protection section of the subpanel, set the R The air conditioning system and condenser blower start
WSHLD switch to the LO position. operating.
12. On the ice protection section of the subpanel, set the R The air conditioning system and condenser blower
WSHLD switch to the OFF position. remain operating.
13. On the ice protection section of the subpanel, set the L The air conditioning system and condenser blower
WSHLD switch to the LO position. remain operating.
14. On the ice protection panel, set the WSHLD switch to The air conditioning system and condenser blower stop
STBY. operating.
15. On the ice protection panel, set the L WSHLD switch to The air conditioning system and condenser blower start
the OFF position. operating.
16. On the ice protection panel, set the WSHLD switch to The air conditioning system and condenser blower
NORM. remain operating.
17. On the ice protection panel, set the STAB switch to the The air conditioning system and condenser blower stop
MAN position. operating.
18. On the ice protection panel, set the STAB switch to the The air conditioning system and condenser blower start
OFF position. operating.
19. On the ENVIRONMENTAL panel, rotate and hold the The air conditioning system and condenser blower stop
CKPT auto temp control knob to the MAN INC position operating.
for a minimum of ten seconds.
20. On the ENVIRONMENTAL panel, rotate and hold the The air conditioning system and condenser blower start
CABIN auto temp control knob to the MAN DEC position operating.
for a minimum of ten seconds.
21. On the aft relay panel, open the CPRSR LSR circuit The air conditioning system and condenser blower stop
breaker (21CB19). operating.
22. On the aft relay panel, close the CPRSR LSR circuit The air conditioning system and condenser blower start
breaker (21CB19). operating.
23. On the ENVIRONMENTAL panel, rotate and hold the The air conditioning system and condenser blower stop
CABIN auto temp control knob to the MAN INC position operating.
for a minimum of ten seconds.
C. Follow On Procedures
(1) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(8) Remove screws (23), washers (24), and cover (22) from compressor motor module (34).
(9) Loosen nut (41) and washer (40) on belt tensioner (38). Loosen nut (39) on belt tensioner (38) and remove belt (21) from
compressor motor module (34).
(10) Remove nut (41) and washer (40) from belt tensioner (38).
(11) Remove bolts (37) and washers (36) securing the compressor mount (35) to the compressor motor module (34).
(12) Remove bolts (5), washers (6), compressor motor module (34), and isolator (15) from the mount (14).
B. Installation
The compressor motor module is located in the right aft avionics compartment (Ref. Figure 402, Sheets 1 and 2).
NOTE: Align reference notch in isolator pad to the forward side of the mount.
(1) Align compressor motor module (34) and isolator (15) with mount (14), and install bolts (5) and washers (6) securing motor
module (34) to mount (14).
(2) Align compressor mount (35) and belt tensioner (38) with motor module (34) and install bolts (37) and washers (36).
(3) Loosely install the nut (41) and washer (40) on the belt tensioner (38).
(4) Position clamp (9) on flexible air duct (10), align flexible air duct (10) with motor intake (7) and tighten clamp (9).
NOTE: When securing electrical cables (29) to positive and negative terminals (33, 32) on the motor (4), install
lockwasher (27) under nut (26) and torque nuts (26) to 140 to 160 inch-lbs.
(5) Connect electrical cables (29) to the terminals (32, 33) and install washers (28), lockwashers (27), and nuts (26). Torque
nuts (26) to 140 to 160 inch-lbs.
(6) Install cover (31) and secure with screws (30).
(7) Perform the COMPRESSOR MOTOR BELT INSTALLATION procedure (Ref. Step 2.B).
NOTE: Install washers (1) on the studs (19) on both sides of the cover (3).
(8) Position cover (3) on the top of the motor (4) and install screws (2) and washers (1).
(9) Remove caution tag and reconnect main battery (Ref. DC GENERATION SYSTEMS, 24-30-00, 301).
(10) Perform the CONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(11) Set the CABIN and CKPT AUTO TEMP switches to MAN.
(12) Turn and hold the CABIN and CKPT AUTO TEMP switches to DEC until the compressor begins to operate.
(13) Allow the system to operate and make sure that cooled air discharges from the air outlets in the cockpit and overhead
outlets in the cabin.
(14) Turn and hold the CABIN and CKPT AUTO TEMP switches to INC until the compressor shuts off.
(15) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(16) Close right aft avionics door (860AR, Figure 201, 06-50-07).
4. Compressor Motor Module (Effectivity: RB-130 and After)
A. Removal
The compressor motor module is located in the right aft avionics compartment (Ref. Figure 403, Sheets 1 and 2).
(1) Open right aft avionics door (860AR, Figure 201, 06-50-07).
(2) Make sure BAT switch is set to the OFF position and tag switch with a caution tag indicating "DO NOT APPLY POWER".
(3) Disconnect the main battery (Ref. DC GENERATION SYSTEMS, 24-30-00, 301) and tag connector with a caution tag
indicating "DO NOT RECONNECT".
(4) Remove screws (2) and washers (1) securing the cover (3) to the top of the motor (4) (Ref. Figure 403).
(5) Remove screws (40) and cover (41) from the electrical box on the motor (4).
(6) Remove nuts (36), lockwashers (37), washers (38), and electrical cables (39) from the positive terminal (43) and negative
terminal (42).
(7) Loosen clamp (7) and disconnect flexible air duct (8) from motor intake (5).
(8) Remove screws (26), washers (27), and cover (31) from compressor motor module (44).
(9) Loosen nut (51) and washer (50) on belt tensioner (48). Loosen nut (49) on belt tensioner (48) and remove belt (30) from
compressor motor module (24).
(10) Remove nut (51) and washer (50) from belt tensioner (48).
(11) Remove bolts (47) and washers (46) securing the compressor mount (45) to the compressor motor module (44).
NOTE: The screw (32) used to secure the jumper (14) is longer than the other three screws (32) used to secure
the compressor motor module (44).
(12) Remove screw (32), lock washer (33), washer (34), washer (35) and separate jumper (14) from compressor motor module
(44).
(13) Remove screws (32), lock washers (33), washers (34), compressor motor module (44) from the shock mounts (17).
B. Installation
The compressor motor module is located in the right aft avionics compartment (Ref. Figure 403, Sheets 1 and 2).
NOTE: Bolts (20) and washers (19) securing shock mounts (17) can be loosened to properly align the shock
mounts (17) and compressor motor module (44).
(1) Align compressor motor module (44) with the shock mounts (17). Align jumper (14) with compressor motor module (44)
and secure with the longest screw (32), lock washer (33), washer (34) and washer (35). Install screws (32), lock washers
(33) and washers (34) securing motor module (44).
(2) Align compressor mount (45) and belt tensioner (48) with motor module (44) and install bolts (47) and washers (46).
(3) Loosely install the nut (51) and washer (50) on the belt tensioner (48).
(4) Position clamp (7) on flexible air duct (8), align flexible air duct (8) with motor intake (5) and tighten clamp (7).
NOTE: When securing electrical cables (39) to positive (43) and negative terminals (42) on the motor (4), install
lockwasher (37) under nut (36) and torque nuts (36) to 140 to 160 inch-lbs.
(5) Connect electrical cables (39) to the terminals (42, 43) and install washers (38), lockwashers (37), and nuts (36). Torque
nuts (36) to 140 to 160 inch-lbs.
(6) Install cover (41) and secure with screws (40).
(7) Perform the COMPRESSOR MOTOR BELT INSTALLATION procedure (Ref. Step 2.B).
NOTE: Install washers (1) on the studs (25) on both sides of the cover (3).
(8) Position cover (3) on the top of the motor (4) and install screws (2) and washers (1).
(9) Remove caution tag and reconnect main battery (Ref. DC GENERATION SYSTEMS, 24-30-00, 301).
(10) Perform the CONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(11) Set the CABIN and CKPT AUTO TEMP switches to MAN.
(12) Turn and hold the CABIN and CKPT AUTO TEMP switches to DEC until the compressor begins to operate.
(13) Allow the system to operate and make sure that cooled air discharges from the air outlets in the cockpit and overhead
outlets in the cabin.
(14) Turn and hold the CABIN and CKPT AUTO TEMP switches to INC until the compressor shuts off.
(15) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(16) Close right aft avionics door (860AR, Figure 201, 06-50-07).
Figure 402 : Sheet 1 : Air Conditioning Compressor/Motor Installation (Effectivity: RB-2 thru RB-129)
Figure 402 : Sheet 2 : Air Conditioning Compressor/Motor Installation (Effectivity: RB-2 thru RB-129)
Figure 403 : Sheet 1 : Air Conditioning Compressor/Motor Installation (Effectivity: RB-130 and After)
Figure 403 : Sheet 2 : Air Conditioning Compressor/Motor Installation (Effectivity: RB-130 and After)
COMPRESSOR - REMOVAL/INSTALLATION
1. Information
Refer to Chapter 20-52-00, 201 for information on tools and equipment referenced in Table 401. Refer to Chapter 20-53-00, 201 for
information on recommended materials referenced in Table 401.
Table 401. Tools/Equipment and Recommended Materials
ITEM TOOLS AND EQUIPMENT ITEM RECOMMENDED
MATERIALS
02-011 Poly Alkaline Glycol (PAG) Oil
2. Compressor
A. Removal
The compressor (5) is located in the right aft avionics compartment (Ref. Figure 401).
(1) Open right aft avionics door (860AR, Figure 201, 06-50-07).
(2) Make sure BAT switch is set to the OFF position and tag switch with a caution tag indicating "DO NOT APPLY POWER".
(3) Perform the MAIN BATTERY DISCONNECTING procedure (Ref. 24-30-00, 301) and disconnect the main battery and tag
connector with a caution tag indicating "DO NOT RECONNECT".
CAUTION: When performing the AIR CONDITIONING SYSTEM REFRIGERANT RECOVERY procedure, note the
amount of Poly Alkaline Glycol (PAG) oil recovered from the system. During installation, the same
amount of oil must be added to the system.
(4) Perform the AIR CONDITIONING SYSTEM REFRIGERANT RECOVERY procedure (Ref. 12-10-01, 301).
(5) Remove screws (1), washers (2), and cover (4) from compressor (5) (Ref. Figure 401).
(6) Loosen nut (17) and washer (16) on belt tensioner (14). Loosen nut (15) on belt tensioner and remove belt (3) from
compressor (5).
(7) Remove nut (17) and washer (16) from belt tensioner (14).
CAUTION: R134A refrigerant and PAG oil are hydrascopic. To prevent contamination of the vapor-cycle cooling
system, it is essential that plugs and caps be installed on all components and refrigerant lines as soon
as the lines are disconnected to prevent moisture from entering the system.
(8) Loosen fitting (6) and disconnect tube from the suction port (9) of the compressor (5). Install caps and plugs on the open
fitting and suction port to prevent contamination of the system.
(9) Loosen fitting (7) and disconnect tube from the discharge port (8) of the compressor (5). Install caps and plugs on the open
fitting and discharge port to prevent contamination of the system.
(10) Remove bolts (12) and washers (13) securing the compressor mount (11) to the motor module (10).
CAUTION: If the compressor is being replaced, note the amount of PAG oil recovered from the compressor. During
installation, the same amount of new oil must be added to the system.
NOTE: When draining PAG oil from the compressor, allow approximately 30 minutes to drain the oil from the
compressor.
(11) If the compressor is being replaced, remove compressor (5) from the airplane and drain any PAG oil from the compressor.
Add the amount of oil recovered from the compressor to the amount recovered from the system during refrigerant recovery.
If the compressor will be reinstalled, DO NOT drain the PAG oil from the compressor.
B. Installation
The compressor (5) is located in the right aft avionics compartment (Ref. Figure 401).
CAUTION: If the compressor has experienced a catastrophic failure or the system has particulate contamination,
system flushing will be required prior to installation of a new compressor.
(1) If required, perform AIR CONDITIONING SYSTEM FLUSHING procedure (Ref. 12-10-01, 301).
(2) Align compressor mount (11) and belt tensioner (14) with motor module (10) and install bolts (12) and washers (13).
(3) Loosely install the nut (17) and washer (16) on the belt tensioner (14).
(4) Remove the cap and plug from the fitting (7) and discharge port (8).
(5) For airplanes RB-2 thru RB-274; align tube with discharge port (8) of the compressor (5) and tighten fitting (7).
For airplanes RB-275 and After; lubricate the threads of the discharge port (8) and the contact surfaces of the fitting (7)
with PAG oil (02-011, Table 401). Align tube with discharge port (8) of the compressor (5) and torque tighten the fitting (7)
to between 180 to 240 in-lbs.
(6) Remove the cap and plug from the fitting (6) and suction port (9).
(7) For airplanes RB-2 thru RB-274; align tube with suction port (9) of the compressor (5) and tighten fitting (6).
For airplanes RB-275 and After; lubricate the threads of the suction port (9) and the contact surfaces of the fitting (6) with
PAG oil (02-011, Table 401). Align tube with suction port (9) of the compressor (5) and torque tighten the fitting (6) to
between 336 to 396 in-lbs.
(8) Perform the COMPRESSOR MOTOR BELT INSTALLATION procedure (Ref. 21-50-02, 401).
(9) Remove caution tag and perform the MAIN BATTERY CONNECTING procedure (Ref. 24-30-00, 301).
CAUTION: During the AIR CONDITIONING SYSTEM REFRIGERANT RECHARGING procedure, charge the
refrigerant system with the same amount of PAG oil (02-011, Table 401) that was recovered from the
system during removal.
PAG oil is hydrascopic. Do not use PAG oil that has been drained from the system.
(10) Perform AIR CONDITIONING SYSTEM REFRIGERANT CHARGING procedure (Ref. 12-10-01, 301).
(11) Perform the CONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(12) Set the CABIN and CKPT AUTO TEMP switches to MAN.
(13) Turn and hold the CABIN and CKPT AUTO TEMP switches to DEC until the compressor begins to operate.
(14) Allow the system to operate and make sure that cooled air discharges from the air outlets in the cockpit and overhead
outlets in the cabin.
(15) Turn and hold the CABIN and CKPT AUTO TEMP switches to INC until the compressor shuts off.
(16) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(17) Close right aft avionics door (860AR, Figure 201, 06-50-07).
CONDENSER - REMOVAL/INSTALLATION
1. Information
Refer to Chapter 20-52-00, 201 for information on tools and equipment referenced in the table below. Refer to Chapter 20-53-00,
201 for information on recommended materials referenced in the table below.
Table 401. Tools/Equipment and Recommended Materials
ITEM TOOLS AND EQUIPMENT ITEM RECOMMENDED
MATERIALS
02-011 Poly Alkaline Glycol (PAG) Oil
04-034 Sealant
2. Condenser
A. Removal
The condenser (1) is located in the right aft avionics compartment (Ref. Figure 401).
(1) Open right aft avionics door (860AR, Figure 201, 06-50-07).
(2) Open left aft baggage door (850AL, Figure 201, 06-50-07).
(3) Perform the AIR CONDITIONING SYSTEM REFRIGERANT RECOVERY procedure (Ref. 12-10-01, 301).
(4) Ensure BAT switch is set to the OFF position and tag switch with a caution tag indicating "DO NOT APPLY POWER".
(5) Disconnect the main battery (Ref. DC GENERATION SYSTEMS, 24-30-00, 301) and tag connector with a caution tag
indicating "DO NOT RECONNECT".
(6) Perform the CONDENSER BLOWER REMOVAL procedure (Ref. 21-50-07, 401).
(7) Remove screws (15), washers (13, 16), and nuts (12) securing jumpers (18, 19) across air conditioning line adapters (10,
20).
CAUTION: R134a refrigerant and PAG oil are hydrascopic. To prevent contamination of the vapor-cycle
cooling system, it is essential that plugs and caps be installed on all components and refrigerant
lines as soon as the lines are disconnected to prevent moisture from entering the system.
(8) Loosen fittings and disconnect the condenser outlet fitting (9) from adapter (10). Install caps and plugs on the line (9) and
adapter (10).
(9) Loosen fittings and disconnect the condenser inlet fitting (21) from adapter (20). Install caps and plugs on the line (21) and
adapter (20).
(10) Remove screws (23) and washers (22) securing condenser plenum (24) to condenser (1).
(11) Break the seal and remove condenser plenum (24) from airplane.
(12) Remove screws (7), washers (6), and condenser plenum shear panel (8) from the upper baggage wall (5).
(13) Support the condenser (1), and remove screws (4), washers (3) securing the condenser (1) to the center baggage wall
frame (2). Remove the condenser (1) from the airplane.
B. Installation
The condenser (1) is located in the right aft avionics compartment (Ref. Figure 401).
(1) Remove sealant from condenser plenum (24) and prepare the surface according to SURFACE PREPARATION
procedure (Ref. 20-22-00, 201).
(2) Align condenser (1) with center baggage wall frame (2) and secure with screws (4) and washers (3) (Ref. Figure 401).
(3) Install screws (7), washers (6) and condenser plenum shear panel (8) to the upper baggage wall (5).
(4) Apply sealant (04-034, Table 401) to caulk and seal gap between the condenser (1) and condenser plenum (24) (Ref. 20-
22-00, 201).
(5) Align condenser plenum (24) with condenser (1) and secure with screws (23) and washers (22).
(6) Remove the cap and plug from the condenser outlet fitting (9) and adapter (10). Lubricate the threads of the fitting and the
contact surfaces of the adapter with PAG oil (02-011, Table 401).
(7) Connect the condenser outlet fitting (9) to adapter (10) and torque tighten the fitting to between 230 to 260 in.-lbs.
(8) If the torque between the compressor pressure line (11) and adapter (10) was loosened during removal of condenser (1),
lubricate the threads of the fitting and the contact surfaces of the adapter with PAG oil (02-011, Table 401) and torque
Figure 401 : Sheet 1 : Low Outside Air Temperature Cutout Switch Installation
(14) Rotate the CABIN auto temp control switch to MAN (manual mode).
(15) Turn and hold the CABIN auto temp control switch to DEC until the compressor/motor starts operating.
(16) Verify the upper cabin air outlets begin to emit cool air.
(17) Turn and hold the CABIN auto temp control switch to INC until the compressor/motor shuts off.
(18) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(12) Perform AIR CONDITIONING SYSTEM REFRIGERANT CHARGING procedure (Ref. 12-10-01, 301).
(13) Set the CKPT AUTO TEMP switches to MAN.
(14) Turn and hold the CKPT AUTO TEMP switches to DEC until the compressor begins to operate.
(15) Allow the system to operate and make sure that cooled air discharges from the air outlets in the cockpit.
(16) Turn and hold the CKPT AUTO TEMP switches to INC until the compressor shuts off.
(17) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
3. Cabin Thermal Expansion Valve
A. Removal
The cabin thermal expansion valve (3) is located inside the ECS box cover located in the lower right sidewall of the lavatory
(Ref. Figure 402).
(1) Perform the ECS BOX COVER REMOVAL procedure (Ref. 25-40-01, 401).
(2) Perform AIR CONDITIONING SYSTEM REFRIGERANT RECOVERY procedure (Ref. 12-10-01, 301).
(3) Remove insulation covering the thermal bulb (6) and tube assembly (Ref. Figure 402).
(4) Loosen clamp (7) and remove thermal bulb (6) from the evaporator suction tube assembly.
CAUTION: R134a refrigerant, and PAG oil are hydrascopic. To prevent contamination of the vapor-cycle cooling
system, plugs and caps must be installed on all components and refrigerant lines as soon as the lines
are disconnected to prevent moisture from entering the system.
(5) Loosen fitting (2) and disconnect tube assembly (1) from cabin thermal expansion valve (3). Install cap and plug on the
cabin thermal expansion valve and tube assembly.
(6) Loosen fitting (4) and disconnect cabin thermal expansion valve (3) from cabin evaporator inlet tube (5). Install cap and
plug on the cabin thermal expansion valve and fitting.
(7) Remove cabin thermal expansion valve (3) from airplane.
B. Installation
The cabin thermal expansion valve (3) is located inside the ECS box cover located in the lower right sidewall of the lavatory
(Ref. Figure 402).
(1) Remove the cap and plug from the cabin thermal expansion valve (3) and cabin evaporator inlet tube (5).
(2) Lubricate the threads of the fitting (4) and the contact surfaces of the cabin thermal expansion valve (3) with Poly Alkaline
Glycol (PAG) oil (02-011, Table 401).
(3) Align cabin evaporator inlet tube (5) with cabin thermal expansion valve (3) and torque tighten the fitting (4) to between 230
to 260 in-lbs.
(4) Remove the cap and plug from the cabin thermal expansion valve (3) and tube assembly (1).
(5) Lubricate the threads of the fitting (2) and the contact surfaces of the cabin thermal expansion valve (3) with PAG oil (02-
011, Table 401).
(6) Align cabin thermal expansion valve (3) with tube assembly (1) and torque tighten the fitting (2) to between 110 to 130 in-
lbs.
CAUTION: Thermal bulb must be firmly attached to the upper half (between 9 and 3 o'clock) of the evaporator
suction tube assembly in order to properly sense the temperature of the suction tube.
(7) Align thermal bulb (6) on the upper half of the evaporator suction tube assembly and tighten clamp (7).
CAUTION: The thermal bulb must be properly insulated for the expansion valve to sense the temperature of the
tube assembly.
(8) Install insulation (09-044, Table 401) over the thermal bulb (5) and suction tube assembly and secure and cover insulation
with two wraps of tape (09-045, Table 401).
(9) Perform the ECS BOX COVER INSTALLATION procedure (Ref. 25-40-01, 401).
(10) Perform the CONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(11) Perform AIR CONDITIONING SYSTEM REFRIGERANT CHARGING procedure (Ref. 12-10-01, 301).
(12) Set the CABIN AUTO TEMP switches to MAN.
(13) Turn and hold the CABIN AUTO TEMP switches to DEC until the compressor begins to operate.
(14) Allow the system to operate and make sure that cooled air discharges from the overhead air outlets in the cabin.
(15) Turn and hold the CABIN AUTO TEMP switches to INC until the compressor shuts off.
(16) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
(6) Install right forward overwing fairing (230BR, Figure 201, 06-50-02).
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
(11) Perform the AIR CONDITIONING SYSTEM REFRIGERANT CHARGING procedure (Ref. 12-10-01, 301).
(12) Remove the caution tag and reconnect the main battery (Ref. 24-30-00, 301).
(13) Perform the CONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(14) Rotate the CKPT auto temp control switch to MAN (manual mode).
(15) Turn and hold the CKPT auto temp control switch to DEC until the compressor/motor starts operating.
(16) Verify the upper cockpit air outlets begin to emit cool air.
(17) Turn and hold the CKPT auto temp control switch to INC until the compressor/motor shuts off.
(18) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
3. Cabin Refrigerant Solenoid Valve
A. Removal
The cabin refrigerant solenoid valve (12) is located in the aft lavatory adjacent to the cabin evaporator (Ref. Figure 402).
(1) Perform the ECS BOX COVER REMOVAL procedure (Ref. 25-40-01, 401).
(2) Perform the AIR CONDITIONING SYSTEM REFRIGERANT RECOVERY procedure (Ref. 12-10-01, 301).
(3) Ensure BAT switch is set to the OFF position and tag switch with a caution tag indicating "DO NOT APPLY POWER".
(4) Disconnect main battery (Ref. DC GENERATION SYSTEMS, 24-30-00, 301) and tag connector with a caution tag
indicating "DO NOT RECONNECT".
(5) Disconnect electrical connector (5) from cabin refrigerant solenoid valve (12) (Ref. Figure 402).
(6) Remove screw (1), washers (2), nut (4), and bonding jumper (6) from clamp (3).
CAUTION: R134a refrigerant, and pag oil are hydrascopic. To prevent contamination of the vapor-cycle
cooling system, plugs and caps must be installed on all components and refrigerant lines as soon
as the lines are disconnected to prevent moisture from entering the system.
(7) Loosen fitting (13) and disconnect tube assembly (14) from cabin refrigerant solenoid valve (12). Install cap and plug on
the fitting (13) and solenoid valve (12).
(8) Loosen fitting (8) and disconnect tube assembly (7) from cabin refrigerant solenoid valve (12). Install cap and plug on the
fitting (8) and solenoid valve (12).
(9) Remove screw, washer (9), and clamp (11) securing cabin refrigerant solenoid valve (12) to the aft environmental box (10).
(10) Remove cabin refrigerant solenoid valve (12) from airplane.
B. Installation
The cabin refrigerant solenoid valve (12) is located in the right aft lavatory adjacent to the cabin evaporator (Ref. Figure 402).
(1) Install clamp (11) on cabin refrigerant solenoid valve (12).
(2) Align clamp (11) with aft environmental box (10) and install washer (9) and screw.
(3) Remove the cap and plug from the cabin refrigerant solenoid valve (12) and fitting (8). Lubricate the threads of the fitting
and the contact surfaces of the adapter with PAG oil (02-011, Table 401).
(4) Connect fitting (8) to the cabin refrigerant solenoid valve (12) adapter port and torque tighten the fitting to between 266 to
294 in.-lbs.
(5) Remove the cap and plug from the cabin refrigerant solenoid valve (12) and fitting (13). Lubricate the threads of the fitting
and the contact surfaces of the adapter with PAG oil (02-011, Table 401).
(6) Connect fitting (13) to the cabin refrigerant solenoid valve (12) adapter port and torque tighten the fitting to between 162 to
179 in.-lbs.
(7) If the torque between the expansion valve pressure tube fitting (14) and the expansion valve adapter was loosened during
removal of the refrigerant solenoid valve (12), lubricate the threads of the fitting and the contact surfaces of the adapter with
PAG oil (02-011, Table 401) and torque tighten the fitting to between 110 to 130 in.-lbs.
(8) Install screw (1), washers (2) and nut (4) securing bonding jumper (6) to clamp (3).
(9) Connect electrical connector (5) to cabin refrigerant solenoid valve (12) (Ref. Figure 402).
(10) Perform the ECS BOX COVER INSTALLATION procedure (Ref. 25-40-01, 401).
(11) Perform the AIR CONDITIONING SYSTEM REFRIGERANT CHARGING procedure (Ref. 12-10-01, 301).
(12) Remove the caution tag and reconnect the main battery (Ref. 24-30-00, 301).
(13) Perform the CONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(14) Rotate the CABIN auto temp control switch to MAN (manual mode).
(15) Turn and hold the CABIN auto temp control switch to DEC until the compressor/motor starts operating.
(16) Verify the upper cabin air outlets begin to emit cool air.
(17) Turn and hold the CABIN auto temp control switch to INC until the compressor/motor shuts off.
(18) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
vapor cycle compressor/motor module if the outside air temperature is above 50° F. The electrical signal is interrupted when the heat
exchanger inlet butterfly moves 30 degrees toward the closed position.
Bleed air heat is provided to the cockpit zone from the left engine. The right engine provides bleed air heat to the cabin zone. Bleed
air inflow from each engine is controlled by the bi-level flow control valve. One inlet of the inflow system modulating valve receives
high temperature air directly from the bi-level flow control valve and the other inlet receives air cooled to approximately 20° F above
ambient after being passed through the bleed air heat exchanger. The inflow system modulating valves control the mix of bleed air
from the engine and cooled bleed air from the heat exchanger. The modulating valves receive inputs from the cockpit and cabin
temperature controllers which change the position of the two butterfly valves to provide the appropriate outlet air temperature.
Vapor cycle cooling is provided by a compressor/motor module and separate cockpit and cabin evaporators. The temperature
control system signals the load shed controller to enable operation of the compressor/motor module when the auto/manual
temperature switches call for decreased zone temperatures if the outside air temperature is above 50° F. Refer to AIR
CONDITIONING, COOLING in Chapter 21-50-00 for information regarding the vapor cycle cooling system. Refer to Figure 1 and
Figure 4.
4. Components
A. Temperature Controller (Cockpit/Cabin)
The cockpit and cabin temperature controllers are located below the cockpit floorboard (130AL) under the pilot's seat between
FS 175 and FS 182, and between LBL 10 and LBL 20. The temperature controllers receive power from the CKPT and CABIN
TEMP CTRL circuit breakers. The controllers receive input signals from the temperature sensors in the bleed air inflow system
and distribution ducts which sense zone temperature. The AUTO/MANUAL TEMP switches provide a requested temperature
input to the temperature controllers. Refer to Figure 1, Figure 2, Figure 3 and Figure 7.
The temperature controllers compare the requested temperature to the actual zone temperature sensor inputs. The temperature
controller output signals drive the inflow system modulating valves. The modulating valves vary the mixing of bleed air from the
engine with cooled bleed air from the heat exchanger to maintain the requested input temperature. If the modulating valves
cannot provide air that is cool enough, the controllers will signal the load shed controller to enable the air conditioning system to
operate to further reduce the temperature if the outside air temperature is above 50° F.
B. Heat Exchanger Blower
The heat exchanger blower (21B4) is located in the upper center aft fuselage aft of the baggage/avionics compartment. The
blower intake is attached to the aft side of the cockpit and cabin heat exchangers and the exhaust is connected to the exhaust
ducting. The heat exchanger blower receives 28 VDC from the HX BLOWER (21CB40) circuit breaker through the LEFT MAIN
BUS. The heat exchanger blower is energized by the HX BLOWER RELAY (21K1). The HX BLOWER RELAY is activated
when the BLEED AIR source select switch (21S21) is in any position (L ENG, NORM, R ENG, HIGH, CKPT ALTN) except OFF
and the airplane is on the ground (L LDG GND SAFETY RELAY No. 3 (21K3) is closed). The heat exchanger blower is an axial
blower which pulls air through the dorsal intake ducts on each side of the vertical stabilizer and through the aft fuselage
compartment via check valves located in the lower dorsal intake ducts. This intake air is drawn through the heat exchangers and
blower, then exhausted through the exhaust on the left side of the aft fuselage. The heat exchanger blower has spring-loaded
check valves on each side of the blower which open to protect the blower from overspeed windmilling in flight. Refer to Figure 6
and Figure 7.
C. Cabin Bleed Air Heat Exchanger
The cabin bleed air heat exchanger is a stainless steel unit mounted by flanges in the upper empennage below the dorsal inlet
on the right side. The inlet port receives regulated bleed air from the bi-level control valve. The outlet port is connected to the
inflow system modulating valve. The heat exchanger receives bleed air from the right engine at a temperature of approximately
850° F and cools it to approximately 20° F above ambient. The bleed air is circulated through the heat exchanger while ambient
air is introduced across the heat exchanger.
The cooling air ducting from the dorsal ram air inlets is connected to the forward side of the heat exchanger. The aft side is
connected to the blower/plenum assembly. Check valves located on the inlet ducts open during heat exchanger blower
operation to provide additional inlet air for the heat exchanger. During flight, ram air is inducted through dorsal fairing across the
heat exchanger. On the ground, the heat exchanger blower pulls air through the heat exchanger by way of the dorsal fairing
opening and inlet duct check valve. Refer to Figure 7.
D. Cockpit Bleed Air Heat Exchanger
The cockpit bleed air heat exchanger is a stainless steel unit mounted by flanges in the empennage on the left side. The inlet
port receives regulated bleed air from the bi-level control valve. The outlet port is connected to the inflow system modulating
valve. The heat exchanger receives bleed air from the left engine at a temperature of approximately 850° F and cools it to
approximately 20° F above ambient. The bleed air is circulated through the heat exchanger while ambient air is introduced
across the heat exchanger. Refer to Figure 7.
The cooling air ducting from the dorsal ram air inlets is connected to the forward side of the heat exchanger. The aft side is
connected to the blower/plenum assembly. Check valves located on the inlet ducts open during heat exchanger blower
operation to provide additional inlet air for the heat exchanger. During flight, ram air is ducted through the dorsal fairing and
across the heat exchanger. On the ground, the heat exchanger blower pulls air through the dorsal fairing and heat exchanger by
way of the dorsal fairing opening and inlet duct check valve.
E. Cabin Temperature Control (Armrest)
The CABIN TEMP CONTROL potentiometer (21A23) is located in the right sidewall armrest to allow passengers to adjust the
cabin temperature. The potentiometer is activated by setting the TEMP CONTROL COCKPIT/CABIN switch to the CABIN
position. The CABIN TEMP CONTROL bezel illuminates green when the switch is operational. The potentiometer and bezel
light are powered by the CABIN TEMP CONTROL circuit breaker. Refer to Figure 3 and Figure 7.
F. Auto/Manual Temperature Switches
The CKPT (21S9) and CABIN (21S8) AUTO/MAN TEMP switches are located on the environmental control panel. The switches
are multifunctional rotary switch/potentiometers with an automatic and manual operating range. The AUTO/MAN TEMP
switches provide input to the temperature controllers to set and adjust the cockpit or cabin temperature either manually or
automatically. When the switches are in the MAN (manual) detent and rotated slightly to the left or right, the temperature
controller drives the modulating valve to increase or decrease the inflow temperature. Vapor cycle cooling is actuated by the
modulating valves in the manual mode. A sensing switch on the modulating valve provides an electrical signal indicating when
the heat exchanger inlet butterfly valve is full open to signal the load shed controller and initiate vapor cycle operation for added
cooling, if the outside air temperature is above 50° F. The signal ends when the heat exchanger inlet butterfly moves 30
degrees toward the closed position.
Rotating the controls out of the MAN detent and past the INC or DEC legends places the system in the AUTO (automatic) mode.
In the AUTO mode, the temperature controllers will automatically maintain the temperature between 60× F and 80× F. The DEC
position represents 60× F and the INC position 80× F. In the AUTO mode, rotating the control in a clockwise direction increases
the temperature input to the temperature controllers. The output of the CKPT AUTO/MAN TEMP control is input to the cockpit
temperature controller. The output of the CABIN AUTO/MAN TEMP control is provided as an input to the TEMP CONTROL
COCKPIT/CABIN switch. When the TEMP CONTROL COCKPIT/CABIN switch is in the COCKPIT position, the output of the
CABIN AUTO/MAN TEMP control is input to the cockpit temperature controller. Refer to Figure 2, Figure 3 and Figure 7.
G. Temperature Control Cockpit/Cabin Switch
The TEMP CONTROL COCKPIT/CABIN switch (21S10) is located on the environmental control panel. The switch allows
selection of either the CABIN AUTO/MAN TEMP switch in the cockpit or the CABIN TEMP CONTROL potentiometer in the
cabin armrest as the input to the cabin temperature controller. When the TEMP CONTROL COCKPIT/CABIN switch is in the
CABIN position, the bezel of the CABIN TEMP CONTROL potentiometer illuminates in the cabin to indicate switch is
operational. Refer to Figure 3 and Figure 7.
H. Inflow System Modulating Valves (Cockpit/Cabin)
There are two inflow system modulating valves located in the aft fuselage compartment above the left aft baggage compartment
at FS 343. The cockpit modulating valve (21VL7) is located on the left side of the upper aft fuselage compartment and the cabin
modulating valve (21VL6) is located on the right side of the upper aft fuselage compartment. The inflow system modulating valve
receives bleed air from the bi-level flow control valve. One inlet receives high temperature air directly from the bi-level flow
control valve and the other inlet receives air cooled to within 20° F of ambient after being passed through the bleed air heat
exchanger. The inflow system modulating valves control the mix of bleed air from the engine and cooled bleed air from the heat
exchanger. The modulating valves receive inputs from the cockpit and cabin temperature controllers which change the position
of the two butterfly valves to provide the appropriate outlet air temperature. When the temperature controllers are in the manual
mode and the modulating valves reach the full open position, (the valves cannot provide enough cool air for the temperature
controller) the modulating valves will signal the load shed controller to enable the vapor cycle system to operate to satisfy the
demand for cooler air, if the outside air temperature is above 50° F. The inflow system modulating valves receive input power
for the air conditioning system enable circuit from the CKPT or CABIN TEMP CNTL circuit breaker. Refer to Figure 2, Figure 3
and Figure 7.
I. Bleed Air Duct Temperature Sensors (Cockpit/Cabin)
The cabin (21A16) and cockpit (21A21) bleed air duct temperature sensors are located forward of the modulating valves in the
bleed air outflow tube assemblies. The temperature sensors are installed in a square mounting flange in the bleed air tube. The
bleed air duct temperature sensors provide input temperature to the cockpit or cabin temperature controllers. Refer to Figure 2,
Figure 3 and Figure 7.
J. Cockpit Zone Temperature Sensor (Effectivity: RB-2 thru RB-101, RB-103 thru RB-134)
The cockpit zone temperature sensor (21A18) is located in the bottom compartment of the pilot's JEPP manual cabinet. The
cockpit zone temperature sensor has an internal fan which pulls ambient air across a sensor. The zone temperature sensor
receives 28 VDC from the CKPT TEMP CTRL circuit breaker to operate the sensor fan. The cockpit zone temperature sensor
provides input to the cockpit temperature controller. Refer to Figure 1 and Figure 2.
K. Cockpit Zone Temperature Sensor (Effectivity: RB-102, RB-135 and After)
The cockpit zone temperature sensor (21A18) is located in the outboard center of the refreshment cabinet forward bulkhead.
The cockpit zone temperature sensor has an internal fan which pulls ambient air across a sensor. The zone temperature sensor
receives 28 VDC from the CKPT TEMP CTRL circuit breaker to operate the sensor fan. The cockpit zone temperature sensor
provides input to the cockpit temperature controller. Refer to Figure 1 and Figure 2.
L. Cabin Zone Temperature Sensor
The cabin zone temperature sensor (21A14) is located below the right cabin floorboard (140BR, Figure 201, 06-50-01) at FS
258. The cabin zone temperature sensor is installed on the right mid-fuselage wire tray outboard of the inlet vent on the right
side of the center aisle. The cabin zone temperature sensor provides input to the cabin temperature controller. Refer to Figure
3.
M. Vent Duct Temperature Sensor (Cockpit/Cabin)
The cockpit vent duct temperature sensor (21A19) is located in the center cockpit distribution duct forward of the instrument
panel at FS 129. The vent duct temperature sensor is installed next to the vent duct overtemperature switch in a round mounting
plate. The vent duct temperature sensor is a thermistor which provides input to the cockpit temperature controller.
The cabin vent duct temperature sensor (21A15) is located in the right lower cabin sidewall duct at FS 322. The sensor is
installed next to the cabin vent duct overtemperature switch in a plate assembly on the underside of the vent duct. The vent duct
temperature sensor provides input to the cabin temperature controller. Refer to Figure 2, Figure 3 and Figure 7.
N. Bleed Air Duct Over temperature Thermal Switches (Cockpit/Cabin)
The cockpit (21S20) and cabin (21S18) bleed air duct overtemperature thermal switches are located forward of the inflow
system modulating valves in the bleed air outflow tube assemblies. The bleed air overtemperature thermal switches are
installed in a round port in the bleed air tube. The overtemperature thermal switches are thermocouples that close at 420± 10°F
and illuminate the R or L BLEED OVHT annunciator. Refer to Figure 5 and Figure 7.
O. Vent Duct Over temperature Thermal Switches (Cockpit/Cabin)
The vent duct overtemperature thermal switches activate at 210 ± 6 ×F and illuminate the R or L BLEED OVHT annunciator.
The switches reset at 170± 5×F. The cockpit vent duct overtemperature thermal switch (21S17) is located in the center cockpit
distribution duct forward of instrument panel at FS 129. The cockpit vent duct overtemperature thermal switch is installed next to
the cockpit vent duct temperature sensor in a round mounting plate. The cabin vent duct overtemperature thermal switch
(21S19) is installed next to the vent duct overtemperature sensor in the underside of the right lower cabin sidewall duct at FS
322. Refer to Figure 5 and Figure 7.
(1) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(2) Close the right aft avionics door (860AR, Figure 201, 06-50-07).
3. Heat Exchanger functional Test
A. Preparation
Table 502. Bleed Air Sensor/Heat Exchanger Temperature Data Table
Test Temperature Test Point Deg F
Ambient Temperature
Vent Duct
Bleed Air Sensor Cockpit Temperature Sensor
Cabin Bleed Duct
Cabin Temperature Sensor
Ambient Temperature
Heat Exchanger Cockpit Bleed Duct
Cabin Bleed Duct
(1) Gain access to the bleed air heat exchangers and for exchangers (P/N 390-385033-0001) check the heat exchanger data
plates (located on the right side of each exchanger). If the serial number suffix on both exchangers ends in either "T" or
"R2T" then no further action is required otherwise proceed to Step 2.
(2) Connect the Enviro-Systems Breakout Box (205, Table 501) to the airplane as follows:
(a) Perform the CONNECTING AND APPLYING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301)
but do not set the BAT switch to the ON position.
(b) Make sure the BAT switch is set to the OFF position.
(c) Perform the CREW SEAT REMOVAL procedure (Ref. 25-10-01, 401).
(d) Remove the left, aft cockpit floorboard (130BL, Figure 201, 06-50-01, 201).
(e) Disconnect cabin temperature controller connector (21J13) and cockpit temperature controller (21J14) and connect
the Enviro-Systems Breakout Box (205, Table 501) between the airplane harness and either temperature controller.
(3) Connect a Laptop (148, Table 501) with Diagnostic Software (206, Table 501) loaded to the Enviro-Systems test box
(205, Table 501).
(4) Make sure no residual heat from previous engine running is present (approximately 2 hours from the last run).
B. Bleed Air Temperature Sensor Test
ACTION RESULT
NOTE:
The following test should be done in the hangar prior to engine running outside.
1. Suspend a Digital Thermometer (022, Table 501) through
the airplane door and at least four feet from the floor.
2. Read the ambient air temperature of the hangar. Record the Ambient Temperature of the outside air on
the Bleed Air Sensor Temperature Data Table (Ref.
Table 502).
3. Make sure that the CABIN TEMP CTRL circuit breaker
and the CKPT TEMP CTRL circuit breaker on the Pilots
Circuit Breaker Panel are closed.
4. Set BAT switch to the ON position.
Allow a five minute warm up period to elapse. Cockpit and cabin temperature sensors should read the
same temperature (± 5° F) compared to each other and
within 10° F of the vent duct sensor. Record the
temperature results on the Temperature Data Table (Ref.
Table 502).
6. Place the BAT switch to the OFF position.
7. Perform the DISCONNECTING EXTERNAL
ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
C. Heat Exchanger Test
ACTION RESULT
1. Tow the airplane (Ref. 09-10-01, 201) to a position
suitable for running the airplane engines at high power
settings.
2. Position the temperature probe outside the main entry Record the Heat Exchanger Ambient Temperature of the
door, but out of the sunlight and as high as possible outside air on the Heat Exchanger Temperature Data
above the parking surface. Table (Ref. Table 502).
3. Wait five minutes and perform the CONNECTING AND
APPLYING EXTERNAL ELECTRICAL POWER (Ref. 24-
40-00, 301).
NOTE:
The ambient air temperature reading must not be more than 15 minutes old when the bleed air temperature
readings are taken.
4. Start the engines using ENGINE GROUND OPERATING
PROCEDURE (Ref. 71-00-00, 601).
5. Place the COCKPIT AUTOTEMP switch and the CABIN
AUTOTEMP switch to the MANUAL (MAN) position.
6. Place and hold both switches to the fully cold position for
15 seconds.
7. With the engines at idle, place the BLEED AIR switch to
the NORM position.
8. Increase both engines to 80% N 1 (± 3%).
9. After five minutes at 80% N1, record the Cabin Bleed
Duct sensor temperature on the Temperature Data Table
(Ref. Table 502)
10. Decrease both engine power levels to idle.
11. OPEN the CABIN TEMP CTRL circuit breaker and the
CKPT TEMP CTRL circuit breaker.
12. Swap connectors (21J13) and (21J14) over and CLOSE
the CABIN TEMP CTRL circuit breaker and the CKPT
TEMP CTRL circuit breaker.
13. Record the temperature reading for the Cockpit Bleed The recorded bleed air temperatures should be no more
Duct temperature sensor on the Temperature Data Table than 32° F above the ambient temperature recorded in
(Ref. Table 502). Step 2. If the temperatures recorded are within
acceptable limits, go to Step 17. If the bleed air
temperatures are too high, make sure engine power is
stable at 80% N1 (± 3%).
14. If the engine power settings are stable and within limits Repeat Steps 8 thru 12. Verify the recorded
(80% N1 ± 3%), reduce engine power to idle. Place the temperatures are within the acceptable limits. If they are
COCKPIT AUTOTEMP switch and the CABIN not, then shut down the engines and repeat Steps 2 and
AUTOTEMP switch to the MANUAL (MAN) position and 3. Check to see if the temperatures are now within
then place and hold both switches to the fully cold position acceptable limits, if so, go to Step 18.
for 15 seconds.
15. If bleed air temperatures are still too high, shut down the
engines using ENGINE GROUND OPERATING
PROCEDURE (Ref. 71-00-00, 601) and allow the bleed
air system to cool.
16. Make sure that the temperature modulating valve on the If this brings the temperatures to within acceptable limits,
side with the highest bleed air temperature is in the fully then replace the unserviceable modulating valve. If not
cold position. Perform the INFLOW SYSTEM install the valves back to their original positions and go to
MODULATING VALVE REMOVAL/INSTALLATION Step 17.
procedure (Ref. 21-60-03, 401), swap over the cockpit
and cabin inflow temperature modulating valves, and
repeat Steps 2 thru 13.
17. Perform the BI-LEVEL FLOW CONTROL If the bleed air temperatures are still too high, perform the
REMOVAL/INSTALLATION procedure (Ref. 21-20-06, CABIN HEAT EXCHANGER REMOVAL/INSTALLATION
401) and replace the valve. Repeat Steps 2 thru 13. procedure (Ref. 21-60-12, 401) and the COCKPIT HEAT
EXCHANGER REMOVAL/INSTALLATION procedure
(Ref. 21-60-13, 401) to replace the bleed air heat
exchangers.
18. Shut down the engines using ENGINE GROUND
OPERATING PROCEDURE (Ref. 71-00-00, 601).
D. Follow On Maintenance
(1) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-40-00, 301).
(2) Make sure the BAT switch is in the OFF position and OPEN the CABIN TEMP CTRL circuit breaker and the CKPT TEMP
CTRL circuit breaker.
(3) Disconnect the Laptop and Enviro-System Breakout box.
(4) Connect the cabin temperature controller connector (21J13) and cockpit temperature controller (21J14) electrical
harnesses.
(5) CLOSE the CABIN TEMP CTRL circuit breaker and the CKPT TEMP CTRL circuit breaker.
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
(9) Install the insulation (09-039, Table 401) on the tube assemblies (8, 17, 25, 34) and secure with tape (09-038, Table 401).
(10) Install the insulation (09-115, Table 401) on the tube assemblies (1, 18) and secure with tape (09-038, Table 401).
(11) Remove caution tags and reconnect main battery (Ref. DC GENERATION SYSTEMS, 24-30-00, 301).
(12) Perform the ENGINE GROUND OPERATING PROCEDURE (Ref. 71-00-00, 601).
(13) Rotate the CABIN or CKPT auto temp control switch to MAN (manual mode).
(14) Turn and hold the CABIN or CKPT auto temp control switch to DEC until the compressor/motor starts operating.
(15) Make sure the upper cabin or cockpit air outlets begin to emit cool air.
(16) Turn and hold the CABIN or CKPT auto temp control switch to INC until the compressor/motor shuts off and warm air
discharges from the lower air outlets in the cockpit or cabin.
(17) Perform the ENGINE SHUTDOWN procedure (Ref. 71-00-00, 601).
(18) Close the upper center baggage compartment access door (310BZ, Figure 201, 06-50-03).
(19) Close left aft baggage door (850AL, Figure 201, 06-50-07).
Figure 401 : Sheet 1 : Bleed Air Over Temperature Thermal Switch Installation
Figure 201 : Sheet 1 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 2 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 3 : Radome and Area Below Floorboards Access Plates and Panels
Figure 201 : Sheet 4 : Radome and Area Below Floorboards Access Plates and Panels
(4) Align heat exchanger blower (22) with the heat exchanger housing (15) and install bolts (27) and washers (28).
(5) Install bolts (12) and washers (13) securing heat exchanger blower (22) to heat exchanger housing (15).
(6) Align heat exchanger housing (15) with heat exchanger plenum (24) and brackets (3), and secure with bolts (5), washers
(2, 4) and nuts (1).
WARNING: Silicone adhesive sealant gives off acetic vapors when curing, adequate ventilation must be provided to
keep vapors from accumulating in the aft fuselage.
WARNING: Keep silicone adhesive sealant away from heat, sparks, and flame.
CAUTION: Make sure all bonding surfaces are clean.
(7) Apply sealant (04-057, Table 401) to the mating surfaces of heat exchanger housing (15) and the heat exchanger plenum
(24).
(8) Assemble heat exchanger plenum (24) and heat exchanger housing (15) and install washers (17) and bolts (16).
WARNING: Silicone adhesive sealant gives off acetic vapors when curing, adequate ventilation must be provided to
keep vapors from accumulating in the aft fuselage.
WARNING: Keep silicone adhesive sealant away from heat, sparks, and flame.
CAUTION: Make sure all bonding surfaces are clean.
(9) Apply sealant (04-057, Table 401) to the mating surfaces of heat exchanger housing (15) and the ram air duct (6).
(10) Align ram air duct (6) with heat exchanger housing (15) and install bolts (9), and washers (10).
(11) Connect electrical terminals (20) to studs (21) and install washers (19) and nuts (18).
(12) Align ram air flex duct assembly (8), and install clamp (7) securing ram air duct (6) to ram air flex duct assembly (8).
WARNING: Silicone adhesive sealant gives off acetic vapors when curing, adequate ventilation must be provided to
keep vapors from accumulating in the aft fuselage.
WARNING: Keep silicone adhesive sealant away from heat, sparks, and flame.
CAUTION: Make sure all bonding surfaces are clean.
(13) Apply sealant (04-057, Table 401) between ram air duct (6) and ram air flex duct assembly (8) and seal around electrical
harness (14) opening in the heat exchanger housing (15).
CAUTION: Do not pinch drain line tubes when installing clamps.
CAUTION: Route and secure drain line tubes to ensure that they do not contact bleed air lines.
CAUTION: Maintain a downhill orientation to the drain line tubes to ensure water does not get trapped in the tubes.
(14) Connect drain line tube (32) to heat exchanger housing (15) and secure with clamp (31).
(15) Connect drain line tube (34) to ram air flex duct assembly (8) and secure with clamp (33).
(16) On Airplanes RB-27 and After, apply sealer (04-003, Table 401) to both the inner surface of the louver (29) and contacting
surface of the fuselage according to the CONTOUR SMOOTHNESS SERVICE JOINT description (Ref. SRM, 51-10-03).
(17) Install left empennage louver (29) panel (310AL, Figure 201, 06-50-03) and secure with screws (30).
(18) On Airplanes Prior to RB-27, fill gap and/or step between louver (29) and fuselage with sealant (04-039, Table 401)
according to the CONTOUR SMOOTHNESS SERVICE JOINT description (Ref. SRM, 51-10-03).
(19) Remove caution tag and reconnect main battery (Ref. DC GENERATION SYSTEMS, 24-30-00, 301).
(20) Perform the CONNECTING AND APPLYING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-30-00, 301).
(21) Make sure the airplane has weight on wheels and BAT switch is ON.
(22) Set the BLEED AIR SOURCE SELECT switch to any position except OFF.
(23) Verify the heat exchanger blower operates and air discharges from the left empennage panel (310AL, Figure 201, 06-50-
03).
(24) Set the BLEED AIR SOURCE SELECT switch to OFF.
(25) Perform the DISCONNECTING EXTERNAL ELECTRICAL POWER procedure (Ref. 24-30-00, 301).
(26) Close upper center baggage compartment door (310BZ, Figure 201, 06-50-03).
(27) Close left aft baggage door (860AL, Figure 201, 06-50-07).
(9) Align tube (5) with heat exchanger outlet (10) and install sleeve (8) and clamps (7). Torque tighten the clamps to between
18 to 22 in-lbs.
(10) Perform the MAIN BATTERY CONNECTING procedure (Ref. 24-30-00, 301), remove caution tags, and reconnect main
battery.
(11) Perform the ENGINE GROUND OPERATING PROCEDURE (Ref. 71-00-00, 601) and check the bleed air tubes for
leakage.
(12) Close baggage compartment upper center access door (310BZ, Figure 201, 06-50-03).
(13) Close left aft baggage door (850AL, Figure 201, 06-50-07).
(9) Align tube (18) with heat exchanger outlet (14) and install sleeve (4) and clamps (3). Torque tighten the clamps to between
18 to 22 in-lbs.
(10) Perform the MAIN BATTERY CONNECTING procedure (Ref. 24-30-00, 301), remove caution tags, and reconnect main
battery.
(11) Perform the ENGINE GROUND OPERATING PROCEDURE (Ref. 71-00-00, 601) and check the bleed air tubes for
leakage.
(12) Close baggage compartment upper center access door (310BZ, Figure 201, 06-50-03).
(13) Close left aft baggage door (850AL, Figure 201, 06-50-07).
(4) Install the upper tray (6) in the refreshment cabinet (8).
(5) Insert the hot tank (5) in the refreshment cabinet (8). Gently shift the hot tank (5) in the cabinet compartment until the plugs
(4) are aligned and gently push in on the hot tank (5) until the plugs are fully engaged and seated.
(6) Insert the hot tank closeout panel (1) over the spigot (2) and align the panel in the lower track. Gently push in on the top of
the panel (1) and engage the upper clips.
(7) Lower the forward door of the refreshment cabinet (8).
(8) Remove caution tags and reconnect main battery (Ref. DC GENERATION SYSTEMS, 24-30-00, 301).
Figure 401 : Sheet 1 : Cockpit Temperature Sensor (Effectivity: RB-2 thru RB-101, RB-103 thru RB-134)
Figure 402 : Sheet 1 : Cockpit Temperature Sensor (Effectivity: RB-102, RB-135 and After)