Professional Documents
Culture Documents
B737-6/7/8/900
ATA 21
AIR CONDITIONING
For training purposes and internal use only.
AMEC PERU.
All rights reserved. No parts of this training
manual may be sold or reproduced in any form
without permission of:
AMEC PERU
AIR CONDITIONING B737−600/700
DISTRIBUTION
21−20
22.9.97 Page: 1
AIR CONDITIONING B737−600/700
GENERAL
21−00
21−00 GENERAL
AIR COND SYSTEM DESCRIPTION AIR CYCLE MASCHINE, (COMPRESSOR)
The air cycle maschine is a cooling unit consisting of a compressor and tur-
GENERAL bine on a common shaft. The air enters the compressor, where the pressure
The air conditioning system provides a conditioned air environment for the pas- and temperature of the air is increased.
sengers and crew, assuring comfort and safety. The air cycle machine (ACM) decreases air temperature, by expansion
The air conditioning packs receive hot air (212C) from the pneumatic system. through a turbine.
The packs control the temperature, rate of flow, and distribute it throughout the Foil air bearings support the shaft. The air bearings let the ACM rotate at
passenger and control compartments. high speed with little friction. An air-bearing boost-air line connects at the
center of the ACM. The upstream supply of air comes from a port on the
AIR CONDITIONING PACK upstream side of the flow control and shutoff valve.
The flow control valves (pack valves) provide pack ON / OFF control, and one When the airplane is in flight, demand from the air cycle machine decreases
of three different flow schedules in response to the pack switch and APU bleed and ram air pressure increases. The increase in ram air pressure opens the
switch selection on the P5 panel. check valve and lets more air go through the heat exchanger without the
MIXING VALVE HOT AIR increase of fan operation.
An air mix valve, downstream of the pack valve, regulates cabin tempera- WATER SEPARATOR
ture by allowing a controlled amount of hot air to by−pass the air cycle sys- As the air cools, its moisture content condenses. The water separator col-
tem. The valve is a dual housing assembly with two disk plates mounted on lects this atomized moisture and removes it from the air cycle system. This
a common shaft 90 opposed. As one disk moves from open toward closed, water is sprayed into the ram air inlet duct, upstream of the pack heat ex-
the other moves from closed toward open. One part of the air is routed to changer, through a water spray nozzle. The water separator 2C control
the hot air plate of the mixing valve, bypasses the cooling pack, directed system bypasses hot air around the air cycle machine, if needed, to prevent
through the mixing chamber. water freezing in the separator.
The remainder is directed through the PACK PROTECTION
PRIMARY HEAT EXCHANGER, Protection of the pack is provided by four thermal switches.
The primary heat exchanger is an air - to − air type. The ram air system em-
ploys outside air as a cooling medium across the heat exchanger. The − 90 C (Supply Duct).....................mixing valve drives to FULL COLD.
amount of outside air permitted to flow through the heat exchangers is de- − 100C (Turbine Inlet) ....................pack valve closes.
termined by ram air inlet panels. During periods of low ram air supply, such
For Training Purposes Only
20.09.00 Page: 2
Lufthansa Technical Training
AIR CONDITIONING B737−600/700
GENERAL
21−00
AFT
MIX HOT
CHAMBER ANTI ICE 2 C
TRIM
CONTROL BOX VALVE MIXING VALVE
AIR
PASSENGER CABIN 2 C M AIR CYCLE
MASCHINE COLD
DUCT ANTICIPATOR SENSOR
DUCT LIMIT SENSOR 60 C 2 C
DUCT OVHT SW 120 C SENSOR
DUCT OVHT SW 90C
CONTROL CABIN
TEMP SENSOR
WATER RAM
SEPARATOR AIR
200 C COMP FAN EXHAUST
OVERHEAT SW BYPASS
CHECK
VALVE
CONTROL CABIN RAM AIR
For Training Purposes Only
ACTUATOR
CONDITIONED AIR TO RAM AIR
INDIVIDUAL GASPER CONTROLLER
AIR OUTLET PRIMARY
SECONDARY HEAT EXCHANGER
HEAT EXCHANGER
HOT AIR
DEFLECTOR
WARM AIR
RAM AIR INLET 110 C RAM AIR
COOL AIR MODULATION PANELS TEMP SENSOR
COLD AIR 100 C TURBINE
WATER SPRAY INLET OVHT SW
CONDITIONED AIR NOZZLE
18.3.98 Page: 4
AIR CONDITIONING B737−600/700
GENERAL
21−00
MIXING VALVE
INDICATOR
TEST
TEMPERATURE
INDICATOR 60
L PACK R PACK 40 TEMP
ISOLATION
OFF VALVE OFF 80
PACK DUCT OVERHEAT DUCT DUCT
AUTO OPEN AUTO 20
SWITCH LIGHT OVERHEAT A OVERHEAT
100 A
HIGH AUTO HIGH
C
TRIP RESET
OFF OFF
SWITCH
RAM DOOR DUAL RAM DOOR RAM DOOR
ON ON FULL OPEN BLEED FULL OPEN FULL OPEN
1 APU 2 LIGHT A B B
BLEED
21−50 COOLING
PACK VALVE DESCRIPTION
The pack valve is a pneumatically actuated, electrically controlled disk valve. It The pack valve is controled by three solenoids A, B, C.
provides air conditioning pack ON or OFF capability in response to the pack Solenoid C is the OPEN/CLOSED solenoid. When it is electrically ener-
switch on the overhead panel, or to any of three overheat switches in the sys- gized to the open position (or manually operated by pulling out on the
tem. manual control rod), the ballvalve actuating rod is retracted and latched.
During normal operating, it modulates to meter pack airflow to one of three flow
Solenoid B regulates the LOW/HIGH flow mode. The solenoid is ener-
schedules:
gized to the low flow mode.
OFF
Solenoid A is energized:
The pack valve is closed.
− when the pack switch is at ”HIGH”,
AUTO − the APU bleed switch is at the ”ON” position and
With both packs operating in AUTO, each pack regulates to normal flow rate − the airplane is on the ”GROUND”.
approximately 55 Ibs/min. This is the normal in−flight schedule. It provides
optimum airplane performance, but requires a recirculation fan to meet de- Pack Valve Closed Limit Switch
sired cabin ventilation rate. As cabin altitude increases, the pack valve is The closed position of the pack valve controls the following subsystems:
biased to supply a lower airflow rate.
Mixing Valve ............................drives to full cold.
With one Pack operating, regulates to high Flow Rate when:
Recirculation Fan.....................may/may not activated.
− in Flight and Flaps Up (if Engine Bleed is used)
− in Flight, regardless of Flaps (if APU Bleed is used). Note:
HIGH An unsatisfactory operation of the pack valve will affect the pressurization sys-
Pack regulates − 80 Ibs/min. This rate can be selected manually when tem. The AUTO FAIL circuit will be trigger (high cabin rate).
additional cooling and or ventilation is desired. As cabin altitude increases,
the pack valve is biased to supply a lower airflow rate.
If APU bleed air is used on ground, the pack regulates to APU high flow
approximately − 100 Ibs/min.
The pack valve controls the mass flow so, that a nearly constant volumetric
For Training Purposes Only
18.3.98 Page: 6
AIR CONDITIONING B737−600/700
COOLING
21−50
VISUAL POSITION
INDICATOR
ACTUATOR
FWD
TO CABIN PRES-
SURE
SENSE PORT
SOLENOID B
BUTTERFLY
PLATE
For Training Purposes Only
665728
SOLENOID A SOLENOID C
The pack operates in the APU high flow rnode when all of these conditions are
true:
The pack switch is in the HIGH position
The APU bleed switch is in the ON position
The APU is operating above 95%
The airplane is on the ground.
When these conditions are true, then solenoid A will energize to permit a flow
rate greater than high flow mode.
21.09.00 Page: 8
AIR CONDITIONING B737−600/700/800
COOLING
21−50
28V DC
BAT BUS
A/C OVERHEAT 1
CLOSED
OVHT CLOSE
28V DC
BAT BUS
C
A/C PACK CONT
VALVE LEFT NORM
OPEN
P6 CB PANEL K8 PACK
OVHT RLY
OFF LOW FLOW
AUTO MODE
HIGH B
APU HIGH
K18 FLOW FLOW MODE
MODE RLY
AIR A
28V DC
L FCSOV
95%
GND CLOSED
L PACK SW
APU CONTROL R595 GND
UNIT SENSE RLY OFF OFF CLOSED
(J20) 1
OPEN
R FCSOV
ON K23 RAM MOD
ON CONTROL RLY
ENG BLEED SW(S)
ACAU (E4−1)
For Training Purposes Only
OFF
ON
NOTE: RIGHT PACK FCSOV
CIRCUIT SIMILAR APU BLEED
SWITCH
1 PROVIDES A DISCRETE TO
THE FMCS, RECIRC, AIR COND/BLEED AIR
PRESSURIZATION AND CONTROLS PANEL (P5)
TEMP CONTROL SYSTEMS
PACK PROTECTION
The pack protection circuit stops operation of the pack to prevent damage to
the air cycle machine and discomfort to the airplane passengers.
Normal Operation
The pack flow control and shutoff valve receives 28v dc, from the battery bus.
The valve open solenoid receives 28v dc through the pack switch in the AUTO
or HIGH position, and a de−energized pack overheat relay. This will electrically
enable the flow control and shutoff valve (pack valve) to move to the open posi-
tion.
Pack Trip
Pack protection is a function of these three switches:
Compressor discharge overheat switch
Turbine inlet overheat switch
Pack discharge duct overheat switch.
The switches are normally open. When an overheat condition occurs, the over-
heat switch closes. This energizes the pack overheat relay. When the pack
overheat relay energizes, power goes to the close solenoid of the flow control
and shutoff valve.
Indication
These are the indications when pack trip occurs:
PACK TRIP OFF amber light comes on
MASTER CAUTION and AIR COND annunciator lights come on.
Pack Reset
The overheat relay latches in the overheat position. When the condition that
For Training Purposes Only
caused the pack trip off is corrected, push the TRIP RESET switch on the
P5−10 panel to deenergize the overheat relay.
AIR CONDITIONING
VALVE PACK − L
AUTO CLOSE
HIGH
28/16V DC PACK
199C
TRIP OFF
MASTER DIM A
SEC 1 LEFT COMPRESSOR
DISCHARGE OVHT SW
OVERHEAT
OVHT 99C
P6 CB PANEL
K8 LEFT PACK LEFT TURBINE INLET
OVHT RELAY OVERHEAT SWITCH
AIR CONDITIONING
NOTE: LEFT PACK PROTECTION SHOWN. ACCESSORY UNIT
RIGHT PACK SIMILAR.
PACK VALVE
Operation
Valve shutoff operation is accomplished by energizing solenoid “C” to seat the
solenoid ball on the inlet pressure port, closing off the actuator air supply and
venting the actuator. The actuator spring will move the disk to the closed posi-
tion.
When solenoid “C” is energized to seat the ball on the vent port and open the
actuator supply pressure port, the valve actuator is supplied with air pressure
for airflow control operation. The pressure is supplied from an upstream pres-
sure port and is regulated to a desired value by the pilot regulator. Air then
passes through the control orifice and increases pressure in the actuator cham-
ber, moving the disk toward the open position. When the airflow increases to
the desired valve, the selected flow servo bleeds off air through its ball valve at
a rate that maintains the actuator pressure for the desired flow. The high flow
servo is selected when solenoid “B” is de−energized, low flow is selected when
solenoid “B” is energized. As cabin altitude increases, a bellows expands and
biases the servo spring balance to produce a lower airflow rate.
For APU operating on the ground, solenoid “A” is energized to allow inlet pres-
sure to act on high flow servo. As the piston moves, control balance is biased
to control at a higher airflow rate for maximum cooling.
Electrical power, through the pack valve closed limit switch and valve close
relay, will drive the mix valve full cold when the pack valve closes.
Solenoid “C” is provided with a manual control to allow manual operation during
ground maintenance.
For Training Purposes Only
18.3.98 Page: 12
AIR CONDITIONING B737−600/700
COOLING
21−50
CHAMBER E
APU/HIGH
FLOW SERVO AUTO
80 LBS FLOW
SERVO
CHAMBER D 55 LBS
SERVO VALVE
CHAMBER B
APU
HIGH FLOW
SOLENOID A CHAMBER C
BELLOW
CABIN PRESSURE
AUTO FLOW SENSE PORT
PILOT PRESSURE SOLENOID B
REGULATOR
OPEN−CLOSE SOLENOID C
MANUAL
CONTROL
CONTROL
For Training Purposes Only
ORIFICE CHAMBER A
ACTUATOR CL.
OPEN
VENTURI
FLOW UPSTREAM VALVE SENSE PORT DOWNSTREAM
SENSE PORT BUTTERFLY SENSE PORT
CLOSED LIMIT
SWITCH
Secondary plenum/diffuser
Compressor discharge duct assembly
Air cycle machine.
Functional Description
Air from the FCSOV flows through the primary heat exchanger. A cross flow of
ram air removes heat before the air enters the ACM compressor inlet.
When the airplane is on the ground, the ACM impeller fan makes a low pres-
sure zone. This pulls air through the heat exchangers and up through the ple-
num to the impeller fan. Then the impeller fan sends the air through the diffuser
03.12.01 Page: 14
AIR CONDITIONING B737/600/700
COOLING
21−50
PLENUM
FWD
DIFFUSER
FWD
PRIMARY PLENUM/DIFUSER
OUTLET
For Training Purposes Only
(TO ACM
COMPRESSOR)
PRIMARY
INLET PLENUM/DIFFUSER
(FROM FLOW
CONTROL SHUTOFF
VALVE) FWD
RAM AIR
(TO EXHAUST)
Location
The ram air inlet ducts are outboard of the air conditioning compartment. They
extend forward to the ram air inlet in the wing−to−body fairing.
The ram air exhaust ducts are aft of the air conditioning compartments. You get
access to the exhaust ducts from the air conditioning compartment.
An inspection door is in the aft inlet duct at the aft end.
Training Information Point
There is a heat exchanger inlet inspection/clean−out panel in the inlet ducts.
This permits access to the primary and secondary heat exchanger inlets. The
access panel is in the lower area of the duct, adjacent and outboard of the heat
exchangers. You get access to the ram air inlet duct through the fairing panels.
They are outboard of the air conditioning doors.
A special tool lets you clean the heat exchangers when they are dirty.
You can repair the ducts if they have cracks or leaks.
For Training Purposes Only
03.12.01 Page: 16
AIR CONDITIONING B737/600/700
COOLING
21−50
RAM AIR
ACCESS INLET DUCT
AFT RAM (AFT SECTION)
AIR DUCTS PANEL
SECONDARY HX
PRIMARY HX
SECONDARY HX
HEAT EXCHANGER
RAM AIR INLET INSPECTION/ ASSEMBLY
EXHAUST DUCT CLEAN−OUT PANEL
FWD
RAM AIR
For Training Purposes Only
INLET
RAM AIR
INLET DUCT
FWD
Physical Description
The ram air inlet modulation panel is made up of two panel sections. The two
panels are hinged. The forward panel has a hinge at the forward end that con-
nects to the airplane structure. The aft panel has rollers in tracks at the aft end.
On the aft panel, clevis fittings on the mid section, and the upper surface, con-
nect link arms to the shaft assembly.
There is a ram air inlet modulation panel for the left and right ram air system.
Functional Description
The ram air inlet modulation panel and shaft assembly adjusts the quantity of
air that goes into the ram air system. The ram air inlet controller and actuator
supply the command and movement functions.
The ram air inlet actuator moves the modulation panel. Linear movement of the
actuator arm transmits movement through a link arm to the modulation panel
shaft. The shaft turns link arms that lift or lower the two panels. The aft panel
has rollers that let it move forward or aft as the two panels move up or down.
The modulation panel and the ram air inlet deflector door are mechanically con-
nected.
For Training Purposes Only
21.09.00 Page: 18
AIR CONDITIONING B737/600/700/800
COOLING
21−50
DEFLECTOR DOOR
SPRING LOADED
DEFLECTOR DOOR SHAFT
LINKAGE
ROLLER
For Training Purposes Only
DEFLECTOR
DOOR (REF)
FORWARD
MODULATION FORWARD PANEL
PANEL HINGE
Physical Description
The ram air sensor has a stainless steel probe housing. The probe housing
attaches to the electrical connector and is hermetically sealed. The housing
has external threads and hexagonal flats for a boss mount.
Functional Description
The ram air sensor is a thermistor bead element. The resistance of the temper-
ature sensing element changes as the air temperature changes. The ram air
temperature controller uses the resistance of the temperature sensor in a con-
trol bridge. When the temperature is above or below 230F (110C), the control-
ler continues to change the position of the ram air inlet modulation panel. The
controller does not send control signals when the temperature is approximately
230F (110C)
For Training Purposes Only
ELECTRICAL
CONNECTOR
PROBE
HOUSING FWD
opens the modulation panel and extends the deflector door. When the actuator
is in the fully retracted position, S1 opens to remove power to the motor.
The deflector door is in the extended position when the actuator shaft is be-
tween limit switch positions S1 and S2.
The limit switch, S3 (top contact), in the ram air actuator supplies a ground dis-
crete to the air conditioning/bleed air controls panel. This causes the left RAM
DOOR FULL OPEN light to come on.
When K24 relay is de−energized, 115v ac power is supplied to the left ram air
actuator. Power to the motor extend coils is through the S2 switch at takeoff.
29.11.01 Page: 22
AIR CONDITIONING B737/600/700
COOLING
21−50
GROUND
GND
K24 LEFT AIR
GROUND RELAY
PROXIMITY SWITCH
ELECTRONICS UNIT ACAU
S2 S3
EXTEND
(CLOSE)
28/16V DC
RAM DOOR
MASTER DIM FULL OPEN B OPEN CLOSE
For Training Purposes Only
SECT 1
(OPEN)
AIR CONDITIONING/ RETRACT
P6 CB PANEL BLEED AIR CONTROLS
PANEL
S1 S4
NOTE: LEFT SYSTEM SHOWN, RIGHT SYSTEM SIMILAR LEFT RAM AIR ACTUATOR
1 RIGHT SYSTEM USES FLAP/SLAT ELECT UNIT
29.11.01 Page: 24
AIR CONDITIONING B737/600/700
COOLING
21−50
ON UP GRD
OR 1 EXTENDED
GROUND OPEN
DOWN
ON
ACTUATOR
MOVES MOVES TO
CLIMB TO 3 MOD. RANGE
UP RETRACTED
1
MODULATES MODULATES
BETWEEN BETWEEN
CRUISE UP RETRACTED
3 AND 4 NORMAL OPEN
1 AND CLOSED
MOVES
LANDING MOVES TO
For Training Purposes Only
DOWN TO 3 RETRACTED
APPROACH MOD. OPEN
Location
The air cycle machine is in the air conditioning compartment. There is an ACM
for each of the left and right pack systems.
Physical Description
The air cycle machine is a high-speed rotating assembly. It has three sections
connected by a common shaft:
Turbine
Compressor
Fan.
Foil air bearings support the shaft. The air bearings permit the ACM to rotate at
high speed with little friction.
Functional Description
The ACM makes air cool by rapid expansion. Rapid expansion of the air drives
the turbine and compressor. Work is removed by the compressor and fan.
Air from the pneumatic systern goes into the compressor. The compressor in-
creases the pressure and the temperature of the air. This increases the tem-
perature differential in the secondary heat exchanger to improve heat transfer.
The air then goes into the turbine section of the ACM.
The fan impeller moves air through the ram air system when the airplane is on
the ground. It pulls air in from the ram air inlet through the heat exchangers. It
pushes air out through the ram air exhaust. This permits cooling airflow through
For Training Purposes Only
03.12.01 Page: 26
AIR CONDITIONING B737/600/700
COOLING
21−50
FWD
AIR CONDITIONING COMPARTMENTS
COMPRESSOR
INLET
TURBINE
SECTION
For Training Purposes Only
FAN
SECTION
COMPRESSOR
SECTION
TURBINE
OUTLET
TURBINE
INLET
COMPRESSOR/TURBINE OVERHEAT SW
The compressor discharge overheat switch and the turbine inlet overheat
switch monitor the pack for an overheat condition.
Location
There is a compressor discharge overheat switch and a turbine inlet overheat
switch in each of the air conditioning compartments. The compressor discharge
overheat switch is in the duct between the air cycle machine compressor sec-
tion and the secondary heat exchanger. The turbine inlet overheat switch is in
the duct from the secondary heat exchanger to the turbine section of the air
cycle machine.
Physical Description
The overheat switches have these parts:
− Electrical connector
− Switch housing
− Probe.
The overheat switches look similar. The compressor discharge overheat switch
closes at 390F/199C and the turbine inlet overheat switch closes at
210F/99C.
The electrical connection is through a hermetically sealed connector. The hous-
ing has external threads and hexagonal wrench flats for a boss mount.
For Training Purposes Only
03.12.01 Page: 28
AIR CONDITIONING B737/600/700
COOLING
21−50
TURBINE INLET
OVERHEAT SWITCH
99C
FWD
AIR CONDITIONING COMPARTMENT
PROBE
PROBE
SWITCH
HOUSING
TURBINE
For Training Purposes Only
INLET
ACM
COMPRESSOR
FWD
WATER SEPARATOR
Cold air leaving the air cycle machine passes through a muff to the water sepa- The water separator also has a bag condition indicator. As the bag becomes
rator. Moisture in the air at this reduced temperature begins to condense. The clogged, the pressure applied to the bag condition indicator piston is increased,
condensate is so finely atomized, however, that it follows along in the air forcing the disk on the piston shaft toward the red colored window section of
stream. The water separator is used to separate, collect and remove the ex- the indicator cap. When the disk is positioned within the red colored portion of
cess moisture from the air before it enters the distribution system. the cap, its indicates a dirty bag and the bag should be replaced.
stream end. The water and air whirling in a greater diameter than the baffle find
it necessary to make a double reverse turn in order to leave the separator. The
turning does not appreciably affect airflow but the water being much heavier
cannot make the turn and remains in the collection chamber. An overboard
drain mates to an outlet in the equipment bay door.
The bypass valve allows air to pass through the water separator to the distribu-
tion system without first passing through the coalescer bag. The valve opens
as a result of increased pressure differential should the coalescer bag become
clogged or frozen.
03.12.01 Page: 30
AIR CONDITIONING B737/600/700
COOLING
21−50
AIR LINE
WATER LINE
SECONDARY HEAT
EXCH
%
FWD
WATER SPRAY INJECTOR
"
"
#"" "
!
!
"
" !
!
For Training Purposes Only
" %"
! ' %
'!! "
$$
!
!# " %" " "
%
03.12.01 Page: 32
AIR CONDITIONING B737/600/700
COOLING
21−50
POSITION
INDICATOR
ACTUATOR HOUSING
ELECTRICAL
CONNECTOR
VALVE
VALVE BODY
DISK
For Training Purposes Only
FW
D
WATER SEPARATOR
PROBE
BODY
ELECTRICAL
CONNECTION
Figure 16 2 C Anti Ice Valve and Sensor
03.12.01 Page: 33
AIR CONDITIONING B737/600/700
COOLING
21−50
2° CONTROLLER BITE
The control unit has Built In Test Equipment (BITE). Instructions for testing are
on the side of the control box. The unit has a green light for “GO”, a red light for
“NO GO”, and a rotating−type test switch. A placard on the cover gives test
instructions. You must put the switch in the FLIGHT position after you do the
test. The switch is spring-loaded to the FLIGHT position. You enable the BITE
test when you move the selector switch to any of the other positions. The posi-
tions of the switch are for the followings tests:
Position Test
1 Amplifier Controller
Position 1 is a test of the dc power supplies. This test makes sure the basic
fault detection circuit of the BITE function operates.
2 Valve Opens
Position 2 test the open drive (heat) command for the low limit valve. You
can monitor the low limit valve as it moves to the open position.
3 Dead Band in Controller (1.1° −2.2° C)
Position 3 test the deadband. The controller makes sure that the valve will
not move when the deadband is simulated.
4 2° Valve Closes
Position 4 test the close drive (cold) command for the low limit valve. You
can monitor the low limit valve as it moves to the close position.
5 Temperature Sensor for Open and Short Circuits
Position 5 is a test of the sensor. This test makes sure the sensor does not
have an open or short.
For Training Purposes Only
03.12.01 Page: 34
AIR CONDITIONING B737/600/700
COOLING
21−50
TEST INSTRUCTIONS
POS GO NO GO
N
1
VERIFY 35 VALVE
2 OPENS. IF NOT REPLACE REPLACE 35
VALVE. CONTROL
AND RESTART
TEST AT
3 POSN 1
VERIFY 35 VALVE
4 CLOSES. IF NOT REPLACE
VALVE.
BITE
INSTRUCTION REPLACE 35
ROTARY PLACARD 5 SENSOR
SELECTOR
VERIFY TEST SWITCH IS IN
AIR CONDITIONING PACK FLIGHT POSITION
INSTRUCTION PLACARD
For Training Purposes Only
GO INDICATOR
LIGHT (GREEN)
NO GO
INDICATOR
LIGHT (RED)
ELECTRICAL
CONNECTOR
03.12.01 Page: 36
AIR CONDITIONING B737/600/700
COOLING
21−50
115 V AC
OPEN
XFR BUS 2
For Training Purposes Only
AIR CONDITIONING
TEMP CONTROL
35F − RIGHT −
+
P6 CB PANEL CLOSE
04.12.01 Page: 38
Lufthansa Technical Training
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
DUCT OVHT
60
40TEMP. WARM
80
DUCT 20 DUCT COOL
OVERHEAT OVERHEAT
100
AUTO AUTO
AUTO
MIX VALVE ACAU
COOL WARM COOL WARM POSITION
CTC
COOL WARM COOL WARM WARM AIR MIX
MANUAL MANUAL MANUAL COOL
OFF OFF VALVE
(60° C) DUCT
DUCT TEMP
LIMIT BULB
SENSOR
TEMPERATURE SENSORS
Duct Limit Sensor Functional Description
The duct temperature limit sensor supplies a signal to the cabin temperature The duct temperature anticipator sensor is a variable−resistance type. As tem-
controller (CTC) when the DUCT temperature is 140F (60C). perature increases, the resistance of the sensor decreases.
The duct temperature anticipator sensor is part of a bridge circuit in the CTC. It
Location
reads the rate of change in the duct air temperature. The CTC uses this data to
The flight compartment duct temperature limit sensor is in the flight compart- adjust the air mix valve position.
ment distribution supply duct. The supply duct is in the EE compartment.
The passenger compartment duct temperature limit sensor is in the passenger Duct Overheat Switch
overhead distribution duct. The duct overheat switch 190F (88C) turns on the DUCT OVERHEAT light and
causes the air mix valve to close the hot side of the valve.
Physical Description
The duct sensor has a probe body and an electrical connector end. The sensor Location
is hermetically sealed in a metal housing. The flight compartment duct overheat switch is in the flight compartment dis-
tribution supply duct. The supply duct is in the EE compartment.
Functional Description
The passenger compartment duct overheat switch is in the passenger over-
The duct temperature limit sensor is a variable−resistance type. As tempera-
head distribution duct.
ture increases, the resistance of the sensor decreases.
The duct limit sensor is part of a bridge circuit in the CTC. The CTC sends a Physical Description
close signal to the air mix valve when the air temperature in the duct is 140F The duct overheat switch has a probe body, electrical connector, and flange. A
(60C) or more. bimetal element that is normally open is in the duct overheat switch.
Duct Anticipator Sensor
The duct temperature anticipator sensor supplies the cabin temperature con-
troller (CTC) with rate of temperature change (increase or decrease).
Location
The flight compartment duct temperature anticipator sensor is in the flight
For Training Purposes Only
04.12.01 Page: 40
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
FWD
PASSENGER COMPARTMENT
OVERHEAD DISTRIBUTION DUCT
For Training Purposes Only
FWD
FLIGHT COMPARTMENT SUPPLY DUCT
(EE COMPARTMENT − LEFT SIDE WALL)
DUCT ANTICIPATOR SENSOR 60° DUCT LIMIT SENSOR 88° DUCT OVERHEAT SW
WARM closes a different switch moving the valve in the opposite direction.
Only one of the switches in the selector can be closed at a particular time.
A 90C duct overheat thermal switch gives system protection to prevent adjust-
ment of the mix valve such that air entering the cabin becomes too hot. At ap-
proximately 90C the thermal switch closes, energizing the cabin duct overheat
relay. The energized relay completes a circuit to move the mix valve to the full
cold position. The thermal switch, when closed, also completes a circuit to illu-
minate the DUCT OVERHEAT light. After correcting the overheat condition the
system may be returned to normal. Another thermal switch protects against
04.12.01 Page: 42
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
115V AC
XFR BUS 1 OFF
SECT 2 WARM
OFF
A/C TEMP
CTRL − MAN COOL
AUTO
P6 CB PANEL CONTROL CABIN
L PACK TEMP SELECTOR
SWITCH
TEMP CONTROL PANEL (P5)
AIR COND/BLEED
AIR CONTROLS PANEL (P5)
NORMAL
OPEN
OPEN
CLOSE CLOSED
OVHT
ACAU
switch contacts close to complete a circuit. The duct overheat switch causes
the air mix valve to close when the air temperature is above 190F (90C). The
closed switch causes the DUCT OVHT light, on the P5-17 panel, to come on.
04.12.01 Page: 44
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
LIMIT
SENSOR > (60° C) DET
BRIDGE
DUCT TEMPERATURE
LIMIT SENSOR COOL(−)
DUCT
TEMP
ANTIC > (0.5° C)
BRIDGE COO
DUCT TEMPERATURE MOD
L
ANTICIPATOR SENSOR PASS −
CABIN
TEMP
HEAT
BRIDGE MOD
CABIN TEMP
SENSOR +
PASS
WARM
CABIN
115V AC OFF TEMP
XFR BUS 2 COOL
BRIDGE
A/C TEMP POWER
CTRL AUTO−R
AUTO/ AUTO
HIGH CABIN TEMPERATURE CONTROLLER
P6 CB PANEL PASS TEMP SELECTOR
R PACK
SWITCH TEMP CONTROL PANEL (P5)
AIR COND/BLEED
AIR CONTROLS OPEN
PANEL (P5) OPEN
For Training Purposes Only
CLOSE CLOSED
OVHT
K2 R PACK VALVE
PASS CABIN K1 PASS CAB
DUCT OVHT CLOSED RELAY
AIR MIX VALVE
RELAY
BITE
A built−in test circuit in the temperature controller provides a quick electrical
check of temperature control system components. A rotary test switch, two
sets of ”GO”, ”NO GO” lights and a test instruction decal are provided on the
face of the controller. When the temperature control system is not being tested
the switch must be returned to START position.
The following components can be tested:
Control box
Cabin sensor
Anticipator sensor
60C duct limit sensor
Temperature selector
For Training Purposes Only
21.09.00 Page: 46
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
TEST INSTRUCTIONS
TEST INSTRUCTIONS
GO GO
Position all ENGINE and APU
BLEED switches to OFF (Closed).
737 ONLY − ON P6 Panel open
air conditioning OVERHEAT circuit LEFT PACK RIGHT PACK
breaker.
TEMP
Position LEFT A/C PACK and RIGHT CONTROL
A/C PACK switches to AUTO or HIGH BOX
Operate TEMP SELECTORS in
For Training Purposes Only
NO GO NO GO
MANUAL and verify AIR MIX
Valves are functional. CABIN
START SENSOR
Seth both TEMP SELECTORS to
mid range of AUTO mode
Press and rotate TEST switch ANTICIPATOR
SENSOR
clockweise. At each position
wait for steady light indication. TEMP DUCT LIMIT
SELECTOR SENSOR
If NO−GO replace faulty unit.
RETURN TEST SWITCH TO
START POSITION
21.4.98 Page: 48
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
For Training Purposes Only
21.4.98 Page: 50
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
TEMPERATURE
SENSOR
AIR FILTER
STOWAGE BIN
STRUCTURE
PSU STRUCTURE
BULLNOSE COVER
SCREW
INBD
SENSOR
GRILL DUCT
PASSENGER BULLNOSE ATTACHMENT
SERVICE UNIT
For Training Purposes Only
21.4.98 Page: 52
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
115V AC TEMPERATURE
OFF
XFR BUS 1 SENSOR FAN
A/C TEMP
CTRL AUTO−L
AUTO
P6 CB PANEL
L PACK
SWITCH
AIR COND/BLEED
AIR CONTROLS PANEL (P5)
TEMPERATURE
SENSOR
FLIGHT COMPARTMENT
TEMPERATURE SENSOR ASSEMBLY
TEMPERATURE
SENSOR FAN
115V AC OFF
XFR BUS 2
A/C TEMP
CTRL AUTO−R
For Training Purposes Only
AUTO
P6 CB PANEL
R PACK CABIN TEMP
SWITCH BULB
CABIN TEMP
AIR COND/BLEED SENSOR
AIR CONTROLS PANEL (P5)
PASSENGER COMPARTMENT
TEMPERATURE SENSOR ASSEMBLY
21.09.00 Page: 54
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
VALVE POSITION
COLD
HOT
TRANSMITTER VISUAL POSITION
INDICATOR VALVE
POSITION
INDICATOR
COLD VALVE
HOT VALVE
TO
AIR CYCLE
MACHINE
TO VISUAL POSITION
MIXING INDICATOR
CHAMBER
For Training Purposes Only
VALVE ACTUATOR
04.12.01 Page: 56
AIR CONDITIONING B737−600/700
ZONE TEMP. CONTROL
21−60
60
40TEMP.
80
DUCT 20 DUCT
OVERHEAT OVERHEAT
100
AUTO AUTO
NEEDLE
INDICATOR
COOL WARM COOL WARM
HOT
28V DC COLD
BUS 2
AIR CONDITIONING
For Training Purposes Only
P6 CB PANEL
AIR MIX VALVE
PASS CABIN R2
AIR MIX VLV POS
INDICATOR
NOTE: PASSENGER COMPARTMENT
SHOWN. FLIGHT COMPARTMENT TEMPERATURE CONTROL PANEL (P5)
SIMILAR.
Physical Description
The printed circuit assembly is a circuit card. There are electrical contacts on
the printed circuit assembly that attaches to the temperature control module
connector.
Functional Description
The printed circuit assembly receives 28v dc. The circuit makes sure the volt-
age and current for the airmix valve position indicator and transmitter are
stable.
For Training Purposes Only
04.12.01 Page: 58
AIR CONDITIONING B737−600/700
ZONE TEMP. CONTROL
21−60
!! !
"
"
"
""!
For Training Purposes Only
TEMPERATURE INDICATING
The temperature indicating system permits monitoring passenger cabin tem-
peratures and passenger supply air temperature from the control cabin.
Features
The temperature indicating system includes a temperature indicator, an AIR
TEMP selector, and two temperature bulbs. When power is supplied to the 28
volt dc bus 1 and the TEMPERATURE INDICATION circuit breaker is closed,
the selected temperature will be indicated.
Temperature Bulbs
Each temperature bulb contains an element whose resistance varies with
changing temperature. A bulb is installed in the supply duct and with the pas-
senger cabin temperature sensor below the stowage compartment in the for-
ward cabin. An in−line fan downstream of the bulb, draws air from the cabin
across the bulb.
Operation
Passenger cabin air supply and passenger cabin temperatures may be moni-
tored by the temperature indicator on the forward overhead panel. The temper-
ature is indicated according to the position of the AIR TEMP selector.
The AIR TEMP selector switch permits switching between supply duct and pas-
senger cabin temperature indication.
For Training Purposes Only
04.12.01 Page: 60
AIR CONDITIONING B737−600/700
TEMPERATURE CONTROL
21−60
SUPPLY PASS
AIR MIX DUCT CABIN AIR MIX
VALVE VALVE
60
40 TEMP.
80
DUC A DUC A
20
T
OVERHEAT 100 T
OVERHEAT
C
AUT AUT
O O
AIR TEMP
SUPPLY PASS
DUCT CABIN
60
28V DC 40TEM
80 PASSENGER
BUS 2 20 P.
For Training Purposes Only
P6 CB PANEL
21-20 DISTRIBUTION
The A/C distribution system supplies conditioned air to the passenger and flight
compartments.
The main air distribution system gets air from these sources:
Air conditioning packs
Ground conditioned air
Recirculation system.
The main distribution manifold collects and mixes air from any combination of
the sources.
Flight Compartment Distribution
The flight compartment gets conditioned air from the left pack and the main
distribution manifold. A duct on the left side of the airplane transmits the air.
The flight compartment has supply ducts and outlets to control the airflow at
each station.
Recirculation System
The recirculation system uses a fan to move air from the passenger compart-
ment to the main distribution manifold. This system reduces the amount of air
that the packs need to supply.
Ventilation
For Training Purposes Only
The ventilation system uses differential pressure to pull air out of the airplane.
The air moves through overboard vents from the cabin galley and the lavatory
areas.
04.12.01 Page: 62
AIR CONDITIONING B737−600/700
DISTRIBUTION
21−20
VENTILATION
SYSTEM
PASSENGER CABIN
CONDITIONED AIR
DISTRIBUTION
FLIGHT COMPARTMENT
CONDITIONED AIR
DISTRIBUTION
For Training Purposes Only
Location
The overhead distribution duct is in the center ceiling area of the passenger
compartment.
Physical Description
The overhead distribution duct is a cylindrical composite tube. There are outlets
along its length that attach to riser ducts and flexible sidewall ducts. The fit-
tings, in the area where the sidewall riser ducts attach, permit the attachment
of temperature sensors.
04.12.01 Page: 64
AIR CONDITIONING B737−600/700
DISTRIBUTION
21−20
FLEXIBLE DUCT
CONNECTIONS
(TYP)
SIDEWALL
RISER DUCTS
TEMPERATURE
SENSOR FITTINGS
SIDEWALL (REF)
RISER DUCT
CONNECTIONS PASSENGER OVERHEAD
DUCT DISTRIBUTION DUCTS
BRACKETS
For Training Purposes Only
(TYP)
DUCT
BRACKETS
SIDEWALL CEILING
OVERHEAD DISTRIBUTION DUCT OUTLETS
PANEL DIFFUSER
(TOP VIEW) (TYP) (REF) OUTLET ASSEMBLY
OVERHEAD DISTRIBUTION DUCT INSTALLATION
GALLEY VENTILATION
The galley ventilation muffler decreases noise levels as air flows out of the gal-
leys.
General
The ventilation system uses differential pressure, cabin—to—ambient, to re-
move air by suction. The system uses these components to take air out of the
galley:
Galley vent inlet
Flexible ducts
Galley ventilation muffler
Exhaust nozzle.
The flexible ducts connect the vent inlet opening in the galley ceiling to an ex-
haust nozzle in the airplane skin. The galley ventilation muffler reduces the
noise of air being released from the pressurized cabin.
Location
The galley ventilation muffler is in the ceiling area above the galley.
Training Information Point
Air velocity through the galley ventilation muffler will increase if the muffler shell
has contamination or cracks. This may cause noise levels to increase.
For Training Purposes Only
22.9.97 Page: 66
AIR CONDITIONING B737−600/700
DISTRIBUTION
21−20
GALLEY CEILING
PANEL
GALLEY
VENTILATION
MUFFLER
FLEXIBLE
GALLEY
DUCT
INLET
OPENING
EXHAUST NOZZLE
(VENT TO AMBIENT)
For Training Purposes Only
Recirculation Fan
A recirculation system is installed to provide ventilation while minimizing bleed
air requirements. An electrically blower draws cabin air through filters and dis-
charges into the mixing and distribution manifold. The system recirculates
approximately 23,5 m3/min (830 cubic feed /min).
The recirculation fan is energized if:
Recirculation fan switch in AUTO and
For Training Purposes Only
21.4.98 Page: 68
AIR CONDITIONING B737−600/700
DISTRIBUTION
21−20
TO PASSENGER
CABIN OVERHEAD
DISTRIBUTION DUCT
CONDENSATE
DRAIN FROM
PLENUM
PRESSURE
SKIN
FROM FORWARD
CARGO COMPARTMENT SWING
CHECK VALVE
AIR COLLECTOR
DRAIN
RECIRCULATION FAN
HOLE
AIR FILTERS
TO PASSENGER CABIN
RECIRCULATION
FAN CHECK VALVE HOT AIR
(LEFT PACK TYP)
COLD AIR
MIXING CHAMBER (LEFT PACK TYP)
CHECK VALVE
GROUND SERVICE (LEFT PACK TYP)
CONNECTION
HOT AIR BLEED TO MIX MUFF
CONTROL CABIN (LEFT SIDE ONLY)
04.12.01 Page: 70
AIR CONDITIONING B737−600/700/800
DISTRIBUTION
21−20
115V AC
MAIN
BUS 2
AIR CONDITIONING
RECIRC FAN CABIN
AIR
28V DC
BUS 2
AIR CONDITIONING
RECIRC FAN CONT
CABIN AIR
28V DC R331 CABIN RECIRC FAN
BAT BUS 2 AIR RECIRC
FAN RELAY (P6)
AIR CONDITIONING NORMAL
OVERBOARD EXHAUST BYPASS
VALVE CONT
OPEN OFF/HIGH
SMOKE
AIR CONDITIONING
OVERBOARD EXHAUST NORMAL R648 SMOKE
VALVE RECONFIG CONT CONTROL
RELAY (J24) CLOSED AUTO
R644 RECIRC
P6 CB PANEL FAN SWITCH K7 L PACK
BYPASS RELAY K13 L PACK
(J24) VALVE CLOSED VALVE NORMAL
RELAY RELAY
OFF
OPEN OFF/HIGH
For Training Purposes Only
AUTO
CLOSED AUTO
RECIRC FAN
SWITCH K2 R PACK K14 R PACK
VALVE CLOSED VALVE NORMAL
RELAY RELAY
AIR CONDITIONING
PANEL (P5)
AIR CONDITIONING ACCESSORY UNIT
The windshield and foot air outlet valves control airflow to the captain’s and first
officer’s windshield outlets and foot outlets.
Location
The windshield outlets are forward of the captain’ s and first officer’s glare-
shield. They supply airflow up and along the windshield plane. The windshield
and foot air outlet valves are forward of the rudder pedals. The foot air outlets
are inside the captain’s and first officer‘s rudder pedal housings.
21.4.98 Page: 72
AIR CONDITIONING B737−600/700/800
DISTRIBUTION
21−20
LEFT AIR
CONDITIONING
PACK
OVERHEAD
OBSERVER
OUTLETS
INDIVIDUAL
AIR OUTLETS
FLIGHT COMPARTMENT
CONDITIONED AIR
SUPPLY DUCT
WINDSHIELD
OUTLETS SIDEWALL
OUTLET
"
%! "
"
FIRST OFFICER
WINDSHIELD AIR/
FOOT OUTLET VALVE
" %!
#!
For Training Purposes Only
" #
#!
METERING
ORIFICES
CAPTAIN
WINDSHIELD AIR/ UNDERSEAT
CAPTAIN DIFFUSER
FOOT OUTLET VALVE
INDIVIDUAL
GASPER
"
Cargo Compartments
For Training Purposes Only
The cargo compartments receive heat from equipment cooling exhaust and
passenger compartment air. Warm equipment cooling exhaust air flows under
the forward cargo compartment floor and along the sidewalls. The air mixes
with passenger compartment air in the main distribution manifold.
The aft cargo compartment air comes from the passenger compartment
through the foot level grilles. The air goes into the sidewall area around and
under the aft cargo compartment through the outflow valve.
The warm air on all sides of the cargo compartments is an insulator. It prevents
the transfer of heat through the skin by conduction.
21.4.98 Page: 74
AIR CONDITIONING B737−600/700
DISTRIBUTION
21−20
DIFFUSER
OUTLETS (TYP)
OUTFLOW
VALVE
AFT CARGO
FWD CARGO COMPARTMENT
COMPARTMENT
OVERHEAD DISTRIBUTION
MANIFOLD
DIFFUSER DIFFUSER
OUTLET OUTLET
CARPET
RISER
PANEL
For Training Purposes Only
DIFFUSER, OVERHEAD OUTLETS AND FWD DIFFUSER, OVERHEAD OUTLETS AND AFT
CARGO COMPARTMENT AIRFLOW CARGO COMPARTMENT AIRFLOW 101020
Location
The forward door area heater is on the left outboard side of the nose wheel
well. Remove the aft left access panel from inside the nose wheel well to get
access to the heater.
The aft door area heater is in the center ceiling area in the aft passenger
compartment.
The overwing escape door heaters are behind the lining, close out panel, and
the door trim.
The overwing emergency escape hatch door heaters are surface electric
heater.
Physical Description
The door area heaters are electrical heat elements in a cylindrical housing.
There is an electrical connector on the housing. Flexible hoses connect condi-
tioned air distribution supply ducts to the door area heaters. A flexible hose
connects the outlet side of the heater to a fitting at the base of the door.
The forward door heater uses conditioned air from the flight compartment dis-
tribution supply.
The aft door heater uses conditioned air from the aft passenger compartment
distribution supply ducts.
For Training Purposes Only
21.09.00 Page: 76
AIR CONDITIONING B737−600/700/800
SUPPLEMENTAL HEATING
21−45
AFT PASSENGER
DISTRIBUTION SUPPLY DUCT
AFT DOOR
AREA HEATER
FLIGHT COMPARTMENT
DISTRIBUTION SUPPLY DUCT
FORWARD DOOR
For Training Purposes Only
AREA HEATER
FWD
Functional Description
The door area heater power relay (R560) controls power to the heaters. When
the airplane is in the air and one of the pack flow control and shutoff valves is
open, the relay energizes. When the relay energizes, 115v ac power from main
bus 1 goes to the heaters.
The door area heaters use phase-to-phase power . Power goes through two
heat elements per unit. Each heat element uses 325 watts. There are internal
temperature control components that keep the temperature to a limit. The over-
heat switch opens at a temperature of 230F (110C) and closes at 200F
(93C). The thermal fuse opens at a temperature of 300F (148C).
The overwing exit doors are heated with heaters behind the lining, door trim,
and close out panels
For Training Purposes Only
10.11.98 Page: 78
AIR CONDITIONING B737−600/700/800
SUPPLEMENTAL HEATING
21−45
OTHER
HEAT OFF ESCAPE DOOR NC
115V AC A HEATERS
MAIN
BUS 1 B
FWD DOOR
OVERTEMP THERMAL FUSE
AREA HEATER
OTHER CLOSE OUT 230F(110° C) 300F(148° C)
PANEL HEATERS 200F(93° C)
M1708 FWD DOOR AREA
HEATER
115V AC A
MAIN
BUS 1 B
AFT DOOR
AREA HEATER
HEAT ON
GND
CLOSED
28V DC
BUS 1
AIR CONDITIONING LEFT FLOW CONTROL
AND SHUTOFF VALVE
DOOR AREA HEAT
For Training Purposes Only
Supply
The supply fans push air to these components:
P1, P2, P3 (display units)
P9 panel (FMC control display units)
Equipment racks in the EE compartment.
Exhaust
The exhaust fans pull air from these components:
P1, P2, P3 (display units)
P9 (FMC control display units)
P6 (circuit breaker panel)
P5 (control and indication)
P8 (center aisle stand)
For Training Purposes Only
22.4.98 Page: 80
AIR CONDITIONING B737−600/700/800
EQUIPMENT COOLING
21-27
EQUIP COOLING
SUPPLY EXHAUST MASTER FIRE
CAUTION WARN
NORMAL
GND
ANTI−ICE ENG
AIR
OVERHEAD
ALTERNATE
DOORS AIR COND CREW CALL
OFF OFF HORN (NWW)
RIGHT MASTER CAUTION
AND ANNUNCATOR LIGHTS
SUPPLY FANS
CHECK VALVES
P5 PANEL
ADIRU (E5)
For Training Purposes Only
OVERBOARD
EXHAUST
VALVE
P8
CENTER AISLE
STAND
P9 EQUIPMENT RACKS
FMC CONTROL
DISPLAY UNITS
P1, P2, P3
DISPLAY UNITS FLIGHT COMPARTMENT EE COMPARTMENT
COMPONENT LOCATIONS
The equipment cooling system is divided into two parts:
Supply
Exhaust.
Supply
The right sidewall section of the EE compartment contains these components:
Normal and alternate supply fans
Check valves
Air filter.
The supply duct extends forward along the right sidewall. It divides to supply
the equipment racks in the EE compartment and the panels in the flight
compartment. The supply low flow sensor is in the duct forward of the nose
wheel well. You get access through the forward equipment compartment ac-
cess door.
Exhaust
The aft lower section of the EE compartment contains these components:
Normal and alternate exhaust fans
Check valves
Overboard exhaust valve.
The overboard exhaust valve is under the floor structure at the center aft area
of the EE compartment.
The exhaust low flow sensor is forward of the nose wheel well. You get access
through the forward equipment compartment access door.
For Training Purposes Only
22.4.98 Page: 82
AIR CONDITIONING B737−600/700/800
EQUIPMENT COOLING
21-27
SUPPLY FANS/
CHECK VALVES
FORWARD
AIR FILTER
EQUIPMENT
COMPARTMENT
FORWARD EQUIPMENT
ACCESS DOOR (REF)
NOSE WHEEL
WELL (REF)
EE COMPARTMENT
EE RACK COOLING
SUPPLY AND EXHAUST
For Training Purposes Only
Physical Description
The normal and alternate cooling fans are single stage vaneaxial fans intergra-
ting the motor into the fan. The rotating impeller pushes air over the motor hou-
sing and through de−swirl vanes before exiting the fan. Three miniature ther-
mostats (204C) serve as thermal protective devices for the fan.
Training Information Point
The supply and exhaust fans install with v-band clamps. Arrows show the
proper flow direction. The supply and exhaust fans are interchangeable.
Check Valves
A two section swing check valve, spring loaded closed, is located down stream
of each fan to prevent back flow of air through the fan that is not operating.
For Training Purposes Only
22.09.00 Page: 84
AIR CONDITIONING B737−600/700/800
EQUIPMENT COOLING
21-27
SUPPLY FAN/
CHECK VALVE
EXHAUST FAN/
CHECK VALVE
OXYGEN BOTTLE
For Training Purposes Only
RAISED PLATFORM
SUPPORT
AIR FILTER
The equipment cooling air filter removes small particles of dirt from the air be-
fore it enters the EE cooling system. This prevents contamination of the electri-
cal and the electronic equipment.
The air filter is upstream of the supply fans.
The air filter is a cartridge type filter inside the air filter housing.
Training Information Point
A clogged air filter will cause low flow through the equipment cooling supply
system. The air filter will require replacement on a regular maintenance sched-
ule. Release the quick release tabs on the air filter housing cover to get access
to the filters.
test, the alarm circuit causes the MASTER CAUTION light and the related
EQUIP COOLING OFF light to come on.
Interfaces
The low flow sensors supply an alarm signal to these components for indica-
tion:
Flight recorder/mach airspeed module
The equipment cooling panel
The ADIRS (crew call).
22.09.00 Page: 86
AIR CONDITIONING B737−600/700/800
EQUIPMENT COOLING
21-27
AIR FILTER
HOUSING
QUICK RELEASE
LATCHES (2)
For Training Purposes Only
!#' &#!"
% % !! % % !! FWD AIR FILTER INSTALLATION
Functional Description
The low flow sensors are a hot wire anemometer type. The low flow sensor
monitors the airflow and temperature of the equipment cooling air. The sensor
sends an alarm signal when the equipment cooling airflow is not within limits.
The low flow sensors have an internal BIT. At power-up, the low flow sensors
and alarm circuits do a test for correct operation. If the sensor(s) fail the BIT
test, the alarm circuit causes the MASTER CAUTION light and the related
EQUIP COOLING OFF light to come on.
Interfaces
The low flow sensors supply an alarm signal to these components for indica-
tion:
Flight recorder/mach airspeed module
The equipment cooling panel
The ADIRS (crew call).
The alarm signal causes these indications to occur:
MASTER CAUTION Light comes on
For Training Purposes Only
28/16V DC
OFF R29 NORM EXH
MASTER DIM A FAN CTRL RLY
SECT 3 TO MASTER (P91) R30 ALT EXH
EXHAUST FAN CTRL RLY (P92)
CAUTION
P6 CB PANEL
OFF
A
SUPPLY R347 NORM SUP
FAN CTRL RLY (P92) R373 ALT SUP
FAN CTRL RLY (P91)
EQ CLNG PANEL (P5)
LOW ALARM
28V DC
BUS 2
INHIBIT
EQUIP CLNG R645 SUP CTRL
LOW FLOW
HIGH ALARM INTERRUPT RLY
DET SUPPLY
(J20)
SUPPLY LOW
FLOW DETECTOR
CREW CALL
LOW ALARM 28V DC HOT
28V DC BAT BUS
BUS 1 GND CREW
HOR
EQUIP CLNG
(NOSE
N WW)
LOW FLOW
For Training Purposes Only
Smoke/ Interrupt
When the smoke control relay energizes, it supplies 28v dc power to energize
For Training Purposes Only
the supply system control interrupt relay (R645). This relay energizes immedi-
ately and prevents power to the normal and alternate fans. The supply low flow
detector receives an inhibit signal. This prevents the low flow signal to cause
the OFF light and MASTER CAUTION light to come on.
The supply system control interrupt relay de-energizes after a 5-minute time
delay.
22.9.97 Page: 90
AIR CONDITIONING B737−600/700/800
EQUIPMENT COOLING
21-27
$
& #!
#"
!#'
%
!#'
!#'
" '
" !"
$
#"
#
!#'
$
$ #!
#!
#
!#'
$ "
" "
#!
#" #
# !% !#' "
!#' !%" ! #"
" " !
!#'
!'!" "
" #" '
For Training Purposes Only
"
$
& #! $
% #!
$
#" " #!
!#' " " " " !#' % !
% " !#' !#' % ""
" ' !
" '
12.12.01 Page: 92
AIR CONDITIONING B737−600/700/800
EQUIPMENT COOLING
21-27
115V AC
GND SVCE
BUS 1
EQUIPMENT
COOLING EXHAUST
FAN PWR − NORM NORMAL EXHAUST
R29 NORMAL
EXHAUST FAN FAN
CONTROL RELAY
P91
LOW 28V DC
28V DC OFF BUS 1
A ALARM
TO MASTER
EQUIP COOLING CAUTION EXHAUST LOW
EXHAUST (P5) FLOW DETECTOR
NORMAL
28V DC
GND SERV
BUS EQUIP COOLING
EXHAUST FAN
CONTROL NORMAL
28V DC
ALTERNATE
BUS 2 EQUIP COOLING R678 RLY EQUIP
EXHAUST FAN EQUIPMENT COOLING EXHAUST
CONTROL ALTN COOLING SW SWITCH DISRUPT
(P5) (J24)
P6 CB PANEL
For Training Purposes Only
115V AC
XFR BUS 2
EQUIPMENT
COOLING EXHAUST R30 ALTERNATE ALTERNATE
FAN PWR − ALTN EXHAUST FAN EXHAUST FAN
CONTROL RELAY
P92
Location
The overboard exhaust valve is in the aft center section of the EE compart-
ment, below the floor.
Physical Description
The 4 inch diameter overboard exhaust valve has these physical features:
Valve body
Electromechanical rotary actuator (electric motor, gear reduction train)
Position indicator (NORMAL/SMOKE).
Valve disk
Damper housing (silicone oil filled).
It attaches to the overboard exhaust duct by v-band clamps.
Functional Description
The overboard exhaust valve is a pneumatically controlled pressure regulated
air shutoff valve. A 28v dc actuator overrides the valve pneumatic control for
smoke clearance in the EE cooling system.
A spring force on the valve disk fully opens the valve. When the airplane pres-
surizes, airflow through the valve increases. The valve stays fully open until the
airflow rate through it is more than 30 lbs/min (14 kg/min). It is fully closed
when differential pressure is more than 1 psid.
In the smoke clearance position the valve disc is able to move freely from fully
For Training Purposes Only
CREW
OXYGEN CYLINDER
For Training Purposes Only
VALVE DISK
ELECTROMECHANICAL
ACTUATOR EE COMPARTMENT
FWD
POSITION
INDICATOR
Right recirculation fan switch − AUTO. SMOKE (open) position. The close enable signal keeps the actuator in the
When the switches are in the normal position, relay R650 is deenergized. NORMAL position.
Power then goes through R648 and R650 to energize the valve actuator to the The open enable signal is set when the outflow valve is more than 8.5 degrees
NORMAL position. open. The open enable signal stays true until the outflow valve is less than 2
degrees open.
The closed enable signal is set when the outflow valve is less than 2.0 degrees
open. The closed enable signal energizes relay K1. Relay R649 then ener-
gizes. R649 remains energized until five minutes after relay K1 relaxes. The
five−minute time delay lets the cabin pressure become stable.
29.11.01 Page: 96
AIR CONDITIONING B737−600/700/800
EQUIPMENT COOLING
21-27
28V DC NORMAL
BAT BUS
EQUIPMENT COOLING
AIR CONDITIONING SUPPLY SYSTEM
OVERBOARD EXHAUST
VALVE CONT
P6 CB PANEL
SMOKE
R648 SMOKE
AIR CONTROL RLY
AUTO/OFF (J24)
AUTO/OFF
HIGH
L PACK HIGH NORMAL
SWITCH R PACK (CLOSED)
GND
SWITCH
21−50 COOLING
COOLING — FUNCTIONAL DESCRIPTION switch. The air then enters the secondary heat exchanger. Again, thermal
energy is extracted by ram air passing around the heat exchanger. However,
The temperature control system is configured in such a way that under normal the heat transfer is augmented by water evaporating on the surface of the se-
operation, the airplane is divided into three zones. These zones are the, condary heat exchanger. The water is sprayed on to the secondary heat ex-
control cabin zone, changer by a water spray nozzle located in the ram air duct. Upon leaving the
forward passenger cabin zone, and aft passenger cabin zone. secondary heat exchanger, the air enters a high pressure water separator sy-
Controlling the temperature in the cabins is accomplished by controlling the stem. The first item the air enters is the water extractor duct. The water extrac-
temperature of the air entering the cabins. Air conditioning operation begins tor duct removes any condensate on the inner walls of the duct leaving the se-
when the pack switches are positioned to AUTO or HIGH. This commands the condary heat exchanger. The extracted water is ducted the collection manifold
respective pack valve to open allowing bleed air into the pack. installed on the bottom of the condenser. After leaving the water extractor duct,
the air enters the hot side of the reheater on its way to the condenser. This air
Pack Valve transfers some of its heat to the dehumidified air returning from the water ex-
During normal operating, it modulates to meter pack airflow to one of three flow tractors. Next, the air enters the condenser where it is cooled by the discharge
schedules: air leaving the air cycle machine turbine. The cooling of the air causes the moi-
sture in the air to condense. The moisture is removed by passing through the
OFF water extractors. The static swirl vanes located in the core of the water extrac-
The pack valve is closed. tors removes the water by centrifugal motion. The water is collected in sumps
AUTO on the water extractors. The water from the sumps is ducted to a collection ma-
With both packs operating in AUTO, each pack regulates to normal flow rate nifold located on the bottom of the high pressure water separator system.
approximately 75 Ibs/min. This water is ducted from the manifold to the water spray nozzle located in
With one Pack operating, regulates to high Flow Rate when: the ram air duct. A port on the manifold is provided for overflow provisions cau-
− in Flight and Flaps Up (if Engine Bleed is used) sed by a clogged nozzle. The dehumidified air then enters the reheater for the
second time. This will heat the air before entering the air cycle machine tur-
− in Flight, regardless of Flaps (if APU Bleed is used). bine. Across either path of the condenser, icing may occur restricting the air-
HIGH flow. This will cause a change in differential pressure sensed by the standby
Pack regulates − 105 Ibs/min. pack temperature control valve. In this situation, the standby pack temperature
If APU bleed air is used on ground, the pack regulates to APU high flow control valve will allow hot bleed air to enter the condenser to deice either path.
approximately − 131 Ibs/min. When the differential pressure returns to normal, the standby pack tempera-
For Training Purposes Only
ture control valve will close. The air expands in the turbine decreasing its tem-
Pack Flow perature and pressure. This expansion through the turbine powers the com-
Downstream of the pack valve, the bleed air is diverted to a trim air system, pressor. The compressor and turbine are connected by a common shaft. For
pack temperature control valve, standby pack temperature control valve, and system protection, the air entering the turbine is limited to 100C by the turbine
the primary heat exchanger. The bleed air enters the primary heat exchanger inlet overheat switch. The air leaving the turbine is extremely cold and is war-
where thermal energy is extracted from the bleed air by the cooler ram air pas- med by bleed air from the pack temperature control valve. The air then passes
sing around the primary heat exchanger. The air leaves the primary heat ex- through the condenser for the second time cooling the air from the reheater.
changer and enters the compressor side of the air cycle machine. In the com- Next the air enters the mix manifold by way of the conditioned air check valve.
pressor, the pressure and temperture of the air is increased. For system For system protection, the discharge temperature is limited to120C by the
protection, the compressor is limited to 200C by the compressor overheat pack discharge overheat switch.
20.09.00 Page: 98
AIR CONDITIONING B737−800
COOLING
21−50
PNEUMATIC
AIR RH
120 C
PACK
DISCHARGE
CABIN TEMP
BULB FILTER
CABIN TEMP R PACK
VALVE S
SENSOR
DUCT
OVHT RIGHT PACK
SW 90C (SIMILAR)
M TRIM AIR MOD
VALVE
ISOLATION
VALVE M
R MIX MAN CONDITIONED
TEMP GROUND AIR
SENSOR CONNECTION TRIM AIR PRESS
MIX REGUL VALVE L PACK
AFT PASS ZONE VALVE S
MANIFOLD S
CABIN TEMP DUCT DUCT
TEMP TEMP
BULB M
CABIN TEMP SENSOR BULB
SENSOR SV STBY TCV
L MIX MAN
TEMP SENSOR
M
PRIMARY
WATER
EXTRACTORS PNEUMATIC
TEMP CONTROL AIR LH
RECIRCULATION TRIM AIR VALVE
DUCT FAN MODUL
OVHT
FWD PASS ZONE SW 90C VALVE
AIR CYCLE
CONDENSER MASCHINE
UNPRESSURIZED
2 1
PRESSURIZED
PACK
AIR TEMP
DUCT TEMP BULB WATER BULB
CONTROL CABIN RAM AIR REHEATER
CONDITIONED AIR TO ACTUATOR SEC WATER
INDIVIDUAL GASPER EXTRACTOR PRIMARY
AIR OUTLET WATER SPRAY SECONDARY HEAT EXCHANGER
HOT AIR NOZZLE HEAT EXCHANGER
WARM AIR
COOL AIR 1 200C COMPRESSOR OUTLET
COLD AIR 2 100 C TURBINE INLET RAM AIR INLET
CONDITIONED AIR 3 110 C RAM AIR TEMP SENSOR
trols. Pack Trip caused by Compressor Discharge, or Turbine Inlet, or Pack Will extinguish when MASTER CAUTION is reset.
Discharge Temperature exceeding Limit. Pack Valve closes automatically. Temperature Selector
MASTER CAUTION Light and AIR COND annunciator will illuminate.
AUTO
During MASTER CAUTION Light Recall, indicates Failure of either Primary
− Provides automatic Temperature Control for associated Zone. Rotating
or Standby Pack Control. Will extinguish when Master Caution is reset.
the Control towards C (cool) or W (warm) sets the desired Temperature
Trip Reset Switch from 18 C to 30 C.
PRESSED:If the Fault Condition has been corrected, resets BLEED TRIP OFF
OFF, PACK and ZONE TEMP Lights. Lights remain illuminated until reset. − Closes the associated Trim Air Modulating Valve.
AIR TEMP
SOURCE
RECIRCULATION FAN SELECTOR
L RECIRC FAN R RECIRC FAN
SWITCH
OFF OFF
AIR TEMP
AUTO AUTO PASS
CAB
FWD
60 80 S
60 AFT AFT
U D
OVHT 40 TEMP
DUCT
80 P U F
40 PRESS P C W
TEMPERATURE
PSI 20 L T D R
INDICATOR
20 0 100 Y P
CONT A
TEST C L
CAB C
K
TRIM AIR
L PACK R PACK
ISOLATION OFF
OFF VALVE OFF
PACK TRIM AIR SWITCH
AUTO OPEN AUTO
SWITCH ON
HIGH AUTO HIGH
RESET
TRIP RESET
OFF OFF
SWITCH C W C W C W
OFF OFF OFF
ON ON
1 APU 2 P5 TEMPERATURE CONTROL PANEL
BLEED
115v ac power goes through these relay contacts to supply a retract signal to up is faired (closed). This is to decrease drag.
the left ram air actuator:
Ram BITE enable (K15 − NORMAL) Training Information Point
Ram mod control (K5 − OPEN) If the DOOR FULL OPEN LIGHT is on during flight cruise mode, it may be one
of these three possible problems:
Pack air/ground (K10 − GROUND)
The ram air system may have a blockage
Ram air actuator disable (K16 — MODULATE).
The heat exchangers are dirty
When the actuator is in the fully retracted position, the S1 switch opens to re-
move power to the motor. Electrical failure.
115V AC
XFR POWER IN
AIR COND
BUS 1
RAM AIR
MOD − L
MODULATE
28V DC AIR RETRACT
BUS 1
OPEN
GND
PSEU
S2 S3
CLOSE EXTEND
UP K7 PACK VALVE (CLOSE)
CLOSED RELAY
For Training Purposes Only
OPEN CLOSE
NOT UP
LEFT ACAU RETRACT
FLAPS SW
(OPEN)
28/16V DC RAM DOOR
MASTER DIM FULL OPEN B S1 S4
SECT 1
A/C PANEL (P5)
P6 CB PANEL LEFT RAM AIR ACTUATOR
Reheater
The reheater increases the temperature of the air in the air conditioning pack
before it enters the turbine of the air cycle machine. This increases the effi-
ciency of the turbine. The primary purpose of the reheater is to increase the
turbine efficency of the air cycle machine. Bleed air leaving the water extractor
duct enters the reheater on the first of two passes through the unit. This air
For Training Purposes Only
warms the air coming from the water extractors (second pass) before entering
the turbine. The air exiting the reheater (first pass) then enters the condenser.
The reheater is a a plate−fin, single−pass, crossflow, air−to−air heat exchanger.
It is made of aluminum.
OUTLET TO
HOT AIR INLET AIR CYCLE
FROM SECONDARY MACHINE
CONDENSER HEAT EXCHANGER TURBINE
OUTLET TO
CONDENSER
EXTRACTOR)
COLD INLET
(FROM TURBINE)
1 STANDBY TCV
DOWNSTREAM HOT OUTLET
1 THE UPSTREAM SENSE PORT IS LOCATED ON SENSE PORT (TO WATER
THE HOT INLET SIDE OF THE CONDENSER EXTRACTOR)
CONDENSER
Figure 52 Condenser & Reheater
13.12.01 Page: 105
AIR CONDITIONING B737−800
COOLING
21−50
EXTRACTOR
DRAIN LINE
INLET PORTS
For Training Purposes Only
WATER DRAIN
SPRAY NOZZLE
WATER EXTRACTOR DUCT
Figure 53 Water Extractor Duct
29.10.98 Page: 107
AIR CONDITIONING B737−800
COOLING
21−50
Functional Description
The pack temperature sensors are thermistor devices. Their resistance
changes with temperature. The temperature sensor resistance is the feedback
to the pack/zone controller. The pack/zone controller uses the feedback to con-
trol the discharge temperature of the air conditioning system.
Each pack temperature sensor has two sense elements. One element to give
feedback to each of the two pack/zone temperature controllers. One element
gives pack temperature feedback to the auto (normal) channel of its related
pack/zone temperature controller. The other element gives pack temperature
feedback to the standby channel of the opposite pack/zone temperature con-
troller.
Pack Temperature Bulb
For Training Purposes Only
DUAL ELEMENT
O−RING PROBE
ELECTRICAL
CONNECTOR
COLLECTOR
STATIC SWIRL
VANES PERFORATED
For Training Purposes Only
COLLECTOR
RING
CONDENSER
OUTLET
CONDENSER CONNECTION
CONDITIONED
INLET AMBIENT AIR CHECK VALVE TURBINE
CONNECTION VENT DELTA P MUFF
AMBIENT
SERVO
VENT
POPPET
VISUAL POSITION
INDICATOR
ELECTRIC
MOTOR HIGH PRESSURE LOW PRESSURE
DELTA P SERVO DELTA P SERVO
REFERENCE
PRESSURE TORQUE MOTOR
FULL OPEN REGULATOR
LIMIT SWITCH ACTUATOR FLAPPER
ASSEMBLY
FULL CLOSE SUPPLY
LIMIT SWITCH AMBIENT NOZZLE
VENT
AMBIENT
MANUAL OUTPUT VENT
OVERRIDE SHAFT CHAMBER A
POPPET
PRIMARY WORM VALVE
GEAR SHAFT VENT RESTICTOR
SLIP OPEN
CLUTCH CHAMBER
BUTTERFLY
PNEUMATIC
ACTUATOR AMBIENT
AIR
FLOW VENT
For Training Purposes Only
INLET DISK
TRAILING
PACK TEMPERATURE CONTROL VALVE PROBE OPEN STOP
ADJUSTMENT
OPEN
Location
There are two mix manifold temperature sensors. They are similar in design
and operation. They are on the upper aft wall of the mix manifold. Access is
through the center aft bulkhead panel in the forward cargo compartment.
Physical Description
The mix manifold temperature sensors have these parts:
Sense element
Case with mounting boss
Electrical connector.
Functional Description
The mix manifold temperature sensors are thermistor devices. Their resistance
changes with temperature.
The temperature sensor resistance is the feedback to the pack/zone controller.
The pack/zone controller uses the feedback to prevent freezing temperatures
in the air conditioning distribution system. Freezing temperatures in the dis-
tribution ducts can cause moisture in the duct joints to freeze. The ice forma-
tion and expansion in the ducts can cause damage.
The packs supply pressurized air through the check valve to the distribution
system. The check valve prevents airflow from the pressurized distribution sys-
tem to the unpressurized air conditioning compartment. This is for single pack
operation or a pack system duct leak.
SENSE ELEMENT
Maintenance Practices
The trim air system can be disabled by closing the manual override on the trim
air pressure regulating valve. This removes valve actuation pressure through
the solenoid assembly, and manually closes the valve assembly.
For Training Purposes Only
TO RIGHT
SERVO REGULATOR PACK VALVE CABINE PRESSURE
SENSE PORT
ACTUATOR
RIGHT PACK
POPPET
VALVE MIX MANIFOLD AREA
SOLENOID
VALVE SOLENOID VALVE
CONTROL
ORIFICE
RELIEF VALVE
VISUAL POSITION INDICATOR PRESSURE BULKHEAD
AND MANUAL OVERRIDE
CLOSED
DOWNSTREAM
PRESSURE
SENSE PORT
For Training Purposes Only
CAM OPEN
FOLLOVER
MANUAL OVERRIDE CAM
MANUAL OVERRIDE
POSITION
INDICATOR
For Training Purposes Only
FLOW ARROW
TRIM AIR MODULATING VALVE
Figure 59 Trim Air Modulating Valve
29.10.98 Page: 119
AIR CONDITIONING B737−800
TEMPERATURE CONTROL
21−60
is used in each supply duct to the passenger cabins and control cabin zone.
The zone duct overheat switch activates at 90C. If the switch is activated, − FWD zone temperature sensor installed at body station 416
airplane control logic will instruct the appropriate trim air modulating valve to − AFT zone temperature sensor installed at body station 272G+13
close. The zone temperature sensor fans provide a constant air flow across Both assemblies are on the right side of the airplane.
the zone temperature sensors and the bulbs.The control cabin (flight deck)
The zone temperature sensor fans provide a constant air flow across the zone
zone temperature sensor assembly is located to the left side of the P5 over-
temperature sensors and the bulbs.
head panel. The passenger compartment zone temperature sensor assem-
blies are mounted in the bullnose area below the passenger service units.
Both assemblies are on the right side of the airplane.
DIFFUSOR/ HOSE
DUCT SENSORS CONNECTION
AND SWITCHES
PRIMARY
CONTROL CABIN
DUCT TEMP. SENSOR
CONTROL CABIN
DUCT TEMP. BULB
For Training Purposes Only
TEMP. CONTROL
TEMP. CONTROL
Front face BITE on the pack/zone controllers isolates system faults to the LRU
level.
WARNING: Before you do a bite test, make sure the ram air inlet area is clear. LEFT AUTO RIGHT AUTO
PACK CONTROL PACK CONTROL
During the bite test sequence, the ram air inlet deflector door and
modulating panels operate. This can cause injury to persons
and/or damage to equipment.
For Training Purposes Only
A BITE test instruction placard is on the top of each controller face. A lamp test RIGHT STANDBY LEFT STANDBY
switch verifies controller power and operation of the green and red GO/NO GO PACK CONTROL PACK CONTROL
lights. Four BITE TEST switches sequence the BITE checks and clear (reset)
the controller memory registers.
NOTE: Drive signals from the pack/zone controllers to the temperature control LEFT RAM AIR RIGHT RAM AIR
CONTROL CONTROL
valves must pass through protective circuits in the air conditioning accessory
units (ACAUs). The pack/zone controller BITE tests do not do a test of the
ACAU protection circuitry. Failure in the ACAU circuitry may cause false valve LEFT PACK/ZONE CONTROLLER RIGHT PACK/ZONE CONTROLLER
failure bite indications.
TEMPERATURE CONTROL
Air conditioning begins when one or both of the pack switches on the P5 over-
head panel is positioned to AUTO or HIGH. This commands the respective
pack valve(s) to open allowing bleed air to enter the pack. The flow rate at
which bleed air enters the air conditioning system is determined by the settings
on the P5 overhead panel. Downstream of the pack valve, the bleed air is di-
verted to a cooling pack system and a trim air system. The trim air system con-
sists of a trim air pressure regulating and shut off valve, three trim air modula-
ting valves, two trim air check valves, and various thermal sensing units.
These components in conjunction with the pack/zone temperature controllers
provide a three zone temperature control system. The temperature control sy-
stem has an selectable range of 18C to 30C. The primary control for the trim
air system is an ON/OFF switch on the P5 overhead panel. The ON/OFF
switch is the only control for the trim air pressure regulating and shut off valve.
This valve allows bleed air into the trim air system.
For Training Purposes Only
TRIM AIR
ON
OFF
C W C W C W
OFF OFF OFF
DUCT
DEMAND COOLEST DEMAND M 1442/M1443
SIGNAL WINS PACK/ZONE
CONTROLLER
DUCT
DEMAND S R PACK
VALVE
TEMP SENSOR
RIGHT PACK
M TRIM AIR
MOD VALVE
AFT PASS ZONE
TRIM AIR
MIX PRESS S L PACK
MANIFOLD S REGUL VALVE VALVE
For Training Purposes Only
TEMP SENSOR M
TRIM AIR
FWD PASS ZONE MOD VALVE
LEFT PACK
M
TEMP SENSOR
TRIM AIR
CONTROL CABIN MOD VALVE
FLT COMPT TEMP BACK UP FLT ZONE CONTROL PRIMARY FLT ZONE CONTR0L FLT COMPT TEMP SELECTOR
SELECTOR
D
DUCT DUCT
DEMAND
2C − 71C
2C − 71C
DEMAND
LIMIT
LIMIT
TEMP SENSOR
AFT PASS ZONE CONTROL FWD PASS ZONE CONTROL
COOLEST LEFT AUTO PACK CONTROL RIGHT AUTO PACK CONTROL COOLEST
B DEMAND DEMAND E
WINS WINS
AFT PASS ZONE FWD PASS ZONE
TEMP SELECTOR COOLEST LEFT STBY COOLEST TEMP SELECTOR
RIGHT STBY
DEMAND PACK DEMAND PACK PACK PACK DEMAND DEMAND
WINS 2C − 63C DEMAND DEMAND 2C − 63C WINS
For Training Purposes Only
2C
D A 2C
L− MIX MANIFOLD RIGHT PACK LEFT PACK
SENSOR E STBY TCV STBY TCV R− MIX MANIFOLD
LOGIC LOGIC B
LEFT STBY PACK CONTROL SENSOR
F RIGHT STBY PACK CONTROL C
M1442 LEFT PACK/ZONE CONTROLLER M1443 RIGHT PACK/ZONE CONTROLLER
Figure 64 Pack/Zone Temperature Control
13.12.01 Page: 129
AIR CONDITIONING B737−800
TEMPERATURE CONTROL
21−60
TRIM AIR
ON
OFF
C W C W C W
OFF OFF OFF
DUCT
DEMAND COOLEST DEMAND
SIGNAL WINS M1442/M1443
PACK/ZONE
CONTROLLER
DUCT
DEMAND S R PACK
VALVE
TEMP SENSOR
RIGHT PACK
M TRIM AIR
MOD VALVE
AFT PASS ZONE
TRIM AIR
MIX PRESS S L PACK
MANIFOLD S REGUL VALVE VALVE
For Training Purposes Only
TEMP SENSOR M
TRIM AIR
FWD PASS ZONE MOD VALVE
LEFT PACK
M
TEMP SENSOR
TRIM AIR
CONTROL CABIN MOD VALVE
TRIM AIR
ON
OFF
C W C W C W
OFF OFF OFF
DUCT
DEMAND AVERAGE M1442/M1443
PACK/ZONE
CONTROLLER
DUCT
DEMAND S R PACK
TEMP SENSOR VALVE
RIGHT PACK
M TRIM AIR
MOD VALVE
AFT PASS ZONE
TRIM AIR
MIX PRESS S L PACK
MANIFOLD S REGUL VALVE VALVE
For Training Purposes Only
TEMP SENSOR M
TRIM AIR
FWD PASS ZONE MOD VALVE
LEFT PACK
M
TEMP SENSOR
TRIM AIR
CONTROL CABIN MOD VALVE
Duct temperature sensor interface satisfy the flight compartment zone duct demand. The right pack/zone control-
ler controls the right pack to satisfy the coolest temperature requirements for
Cabin temperature selector
the passenger compartments.
Cabin temperature selector interface
Zone trim air modulating valve
Zone trim air modulating valve driver.
115V AC
XFR BUS 2
FLT DECK ZONE
TEMP VLV CONTROL
L PACK VALVE
28V DC OVHT
BAT BUS
R PACK VALVE ZONE
TEMP K21
28V DC LIGHT ALT PWR
BUS 1 L PACK VALVE ALT
28V DC K6 FLT DK
BUS 2 R PACK VALVE ALT ZONE OVHT CLOSE
P6 CB PANEL NORM
NORM
K21 ALT PWR
OPEN
ON
LOGIC SAME AS
OFF RIGHT PZC
INOP
TRIM AIR SW INOP CLOSE
K3 FLT K3 FLT DK
AUTO DK INOP INOP ENABLE
BACKUP FLT
COMPT R ACAU (E4−1) K4 FLT DECK FULL CLOSE
ZONE CONTROL TRIM AIR OFF
OFF
LEFT PZC L ACAU (E4−1)
(E3−3) A B C
A FULL OPEN
B
FAULT =
CLOSE
For Training Purposes Only
115V AC
XFR BUS 2
FWD PASS ZONE
TEMP VLV CONT
28V DC
BAT BUS
R PACK VALVE
28V DC
OVHT
BUS 1
R PACK VALVE ALT ZONE
TEMP K21
P6 CB PANEL LIGHT ALT PWR
K1 PASS
ON ZONE OVHT CLOSE
NORM
OFF
TRIM AIR SW
AUTO OPEN
ZONE CONT
ENABLE/OFF
OFF GND = OFF FAULT = OPEN
BITE
1 INOP CLOSE
K1 PASS
INOP ENABLE
K2 PASS FULL CLOSE
CABIN TEMP TRIM AIR OFF
SELECTOR
L R ACAU (E4−1)
P5 PANEL
O FULL OPEN
DRIVER
G
For Training Purposes Only
I
C
DUCT TEMP SENSOR FULL CLOSE
FLIGHT COMP. AND FWD PASS. ZONE IND. SYSTEM Cabin temperature sensor interface and selector
The system provides an indication of an overheat condition in the zone supply Cabin temperature sensor and selector interface
ducts or the failure of the temperature control system. Cabin temperature sensor interface and selector interface.
The backup flight compartment FAULT switch is set by these backup flight
Power Interruption compartment failures:
Power interruption indication is provided by two power interrupt indication re- Cabin temperature sensor
lays, K1 and K2. If there is a power interruption, the ZONE TEMP light on the
P5 panel comes on immediately. The zone temperature control system is reset Cabin temperature sensor interface
after power has been restored. Duct temperature sensor
Duct temperature sensor interface
Overheat Indication
Cabin temperature selector
Overheat protection is provided by overheat switches in the flight compartment
supply duct and in the supply ducts for the passenger cabin. Cabin temperature selector interface
If there is an overheat condition, the ZONE TEMP light on the P5 panel comes Zone trim air modulating valve
on immediately. Push the TRIP RESET switch on the P5 panel after the duct Zone trim air modulating valve driver.
has cooled to reset the zone temperature control system.
Passenger Compartment Temperature Control System Failure Indication
Flight Compartment Temperature Control System Failure Indication A failure of the passenger zone temperature control causes the ZONE TEMP
A failure of the primary or backup flight compartment temperature control or a light to come on only when the master caution system is recalled. This shows
malfunction in the system causes the ZONE TEMP light to come on only when that a BITE check of the controllers is necessary.
the master caution system is recalled. This shows that a BITE check of the The passenger compartment FAULT switch is set by these passenger compart-
controllers is necessary. If there is a complete loss of temperature control for ment failures:
the flight compartment, the ZONE TEMP light comes on immediately and can- Cabin temperature sensor
not be reset.
Cabin temperature sensor interface
The primary flight compartment INOP switch is set by these primary flight
compartment failures: Duct temperature sensor
Cabin temperature sensor Duct temperature sensor interface
Cabin temperature sensor interface Cabin temperature selector
Cabin temperature selector interface
For Training Purposes Only
K6 FLIGHT
AIR COND PACK DECK ZONE
CONT VALVES OVHT RELAY
LEFT
LEFT ACAU
P6 CB PANEL
K1 1 MD&T ZONE TEMP
BACKUP FLIGHT
COMPT INOP FWD PASS COMPT FAULT
GROUND = INOP
For Training Purposes Only
OPEN = FAULT
RECALL=1 RESET=0
BACKUP FWD PASS
COMPT FAULT PRIMARY FLIGHT COMPT INOP
GROUND = FAULT ANTI−ICE ENG OPEN = INOP
MASTER FIRE
HYD OVERHEAD CAUTION WARN
Monitor
Overheat protection for the cooling pack is provided by three thermal switches:
compressor discharge overheat, 200C.
turbine inlet overheat, 100C.
pack discharge overheat 120C.
If an overheat is sensed, the PACK light will illuminate simultaneously with the
Master Caution system. The pack temperature control system may be reset
after the cooling pack has cooled by pushing the TRIP RESET switch on the
P5 panel.
A single failure of the pack control will illuminate the PACK light only when the
Master Caution system is recalled. This indicates a failed system and the re-
quirement to perform a Bite check on the controller. If both auto and standby
control fail, the PACK light will illuminate immediately.
For Training Purposes Only
L PACK/ENG
28V DC BLEED AIR OVHT
BAT BUS
250F (121C)
AIR COND PACK L PACK DISCHARGE
CONT VALVES TRIP RESET OVHT SWITCH
LEFT SWITCH
P6 CB PANEL
210F (99C)
L TURBINE INLET
K1 POWER OVHT SWITCH
K8 PACK
INTERRUPT OVHT
INDICATION RLY RELAY
390F (199C)
MD&T L COMP DISCHARGE
PACK OVHT SWITCH
LEFT
L PACK LIGHT ACAU
P5 PANEL
BITE
STBY PACK FAULT
GROUND = FAULT
RIGHT PACK/ZONE
TEMPERATURE CONTROLLER
RECALL=1 RESET=0
PACK INOP
OPEN = INOP
ANTI−ICE ENG
MASTER FIRE
HYD OVERHEAD WARN
CAUTION
For Training Purposes Only
P7 PANEL
21−20 DISTRIBUTION
CONDITIONED AIR DISTRIBUTION
A system of ducts distributes the conditioned air from the packs to outlets in
the flight and passenger compartments.
Subsystem Features
The conditioned air distribution system begins at the mix manifold which is lo-
cated in the air conditioning distribution bay aft of the forward cargo compart-
ment.
The flight compartment air distribution system consists of a duct originating
from the left pack input into the mix manifold. The duct goes forward under the
floor of the passenger compartment on the left side of the airplane. In the lower
nose compartment, the duct branches into several risers and goes vertically
into the flight compartment ceiling, floor, and foot level outlets.
The passenger compartment distribution system receives conditioned air from
the mix manifold through four risers in the sidewalls. The risers discharge into
an overhead distribution duct running the full length of the passenger compart-
ment. Air discharges through outlets in the bottom of the duct, through flexible
hoses to over window outlets between the passenger service units (PSU’s) and
the sidewall panels, and around the aft entry light assembly.
During normal operation, two electrical recirculation fans draw air from the pas-
senger compartment and the equipment cooling system through filters. The
recirculation air is delivered to the mix manifold through check valves. The re-
circulation fans and check valves are identical and interchangeable. Care must
be taken to avoid reverse installation of the components. The recirculation rate
is approximately 47 m3 per minute. No recirculated air goes into the flight
compartment.
For Training Purposes Only
DIFFUSOR/HOSE
ASSEMBLIES
OVERHEAD
DISTRIBUTION
DUCTS
SIDEWALL
DIFFUSOR
OUTLETS
For Training Purposes Only
SIDEWALL
RISER DUCTS
MAIN
DISTRIBUTION
MANIFOLD
Figure 71 Distribution System General
24.4.98 Page: 143
AIR CONDITIONING B737−800
DISTRIBUTION
21−20
MIX MANIFOLD
The mix manifold receives conditioned air from both packs, the recirculation
fans, or from an external conditioned air source. The mix manifold routes the
air to the distribution system.
Location
The mix manifold is located in the air conditioning distribution bay aft of the for-
ward cargo compartment. A−removable bulkhead separates the cargo
compartment from the air conditioning distribution bay.
Features
Ducts from the left and right packs enter the bottom of the mix manifold. Four
risers carry air from the top of the mix manifold, to the passenger compartment.
Temperature sensors on the top forward side of the manifold send signals to
the pack/zone controllers. Air from the recirculation fans enter the mix manifold
on the left and right sides. A duct on the bottom rear of the mix manifold con-
nects with the external conditioned air fitting. The external conditioned air fitting
is accessible on the bottom of the fuselage, forward of the air conditioning
doors. Air for the flight compartment does not enter the mix manifold but goes
from the left pack duct to the flight compartment.
For Training Purposes Only
TO FORWARD
TO AFT L−MIX MANIFOLD SENSOR PASSENGER
R−MIX MANIFOLD SENSOR
PASSENGER ZONE
ZONE
MIX MANIFOLD
RIGHT
RECIRCULATION TRIM AIR
FAN
LEFT
RECIRCULATION
FAN
For Training Purposes Only
FROM FROM
RH PACK DISCHARGE OVERHEAT RIGHT LEFT LH PACK DISCHARGE OVERHEAT
PACK PACK
SWITCH 120)( SWITCH 120)(
P5 PANEL
CONTROLS
LEFT RIGHT
PACK PACK
For Training Purposes Only
APU
ENGINE 1 ENGINE 2
The system gets triple redundant 28v dc power from these sources: The P5 overhead panel.
Battery bus, DC bus 1 and DC bus 2.
Data Input Interface
The flight crew makes these inputs to the cabin pressure control panel:
Pressurization mode
Flight altitude
Landing altitude.
28V DC A
BUS 1
PRESS CONT
AUTO 1
VALVE POSITION
28V DC B
BUS 2 PRESS CONT
AUTO 2 MANUAL
A AUTO A
MOTOR 1 C
CPC 1
T
STATIC PRESS MANUAL U
MODE VALVE
ALT, UN−CORR MO- A
FLT ALT ADIRU 2 ALT, BARO−CORR T
TOR
AIRSPEED
LAND ALT AUTO CABIN O
AUTO
MANUAL PRESSURE ENG 1 N2 MOTOR 2 R
CONTROL SENSE SMYDC 2
ENG 2 N1
ELACT2
CABIN PRESSURE
For Training Purposes Only
CPC 2
LEFT PACK VALVE
1
PSEU AIR/GROUND LOGIC OPEN/CLOSED RIGHT PACK VALVE
1 ACTIVE CONTROLLER CHANGES
WITH EVERY FLIGHT OR WITH
AN AUTOFAIL EVENT OVBD EXHAUST VALVE
Two selectors are used to set the flight altitude and the landing field altitude Training Information Point
into the system controller. The flight altitude selection is made in 500 foot incre-
The cabin pressure control module has integrated circuit electronics. It is an
ments. The flight altitude range begins at —1000 ft. and extends to 42,000 ft.
electro—static discharge sensitive (ESDS) device. Use proper care when you
The landing field altitude ranges from —1000 ft. to 14,000 ft. in increments of
handle it.
50 ft. The liquid crystal displays show the settings.
A three position toggle switch controls the aft outflow valve when in the manual
mode. It has three positions:
CLOSE NEUTRAL OPEN.
It is spring loaded to the neutral position. An aft outflow valve position indicator
shows the valve position in all modes of operation.
General Description
There are two cabin pressure controllers. The two controllers are identical and
interchangeable. The controllers use digital circuitry.
The controllers are part of a dual redundant system. They are active when the
system operates in the AUTO or ALTN modes. Only one controller operates
the outflow valve at any given time. The other controller acts as a backup.
The controllers have pin selectable control functions. This optimizes the system
for specific mission profiles.
Training Information Point
For Training Purposes Only
The cabin pressure controllers are electro static discharge sensitive (ESDS)
devices. Use ESDS safe practices when you handle the units.
CPC 2 CPC 1
CABIN PRESSURE
SENSOR
LED DISPLAY
FWD
GROUND TEST
YES NO
SYSTEM STATUS
CAUTION
SYSTEM TEST OBSERVE PRECAUTIONS
AND CLEAR FOR HANDLING
ELECTROSTATIC
SENSITIVE
MAIN MENUS DEVICES
GROUND TESTS
EXISTING FAULTS and FAULT HISTORY show faults. Each fault has fault
GROUND TEST has these two submenus: details. For more information on faults and fault details go to the Fault Isolation
DISPLAY TEST Manual.
SYSTEM TEST.
For Training Purposes Only
The DISPLAY TEST does a test of the LED display. The SYSTEM TEST does
a test of the cabin pressurization system.
SYSTEM STATUS
SYSTEM STATUS has these two submenus:
PRESENT STATUS
SYSTEM CONFIGURATION (SYSTEM CONFIG).
PRESENT STATUS shows the current inputs to the cabin pressure controllers.
SYSTEM CONFIG shows the system configuration.
EXISTING FAULTS
EXISTING FAULTS shows faults that are present. From the main menu EX-
ISTING FAULTS there are faults and fault details. Faults are maintenance
messages of the primary problem. For more information of a fault, there are
fault details.
From the EXISTING FAULTS menu, you push the YES button. If there are no
faults, the display shows NO FAULTS. To go back to the main menu, you push
the MENU button.
If there is a fault or faults, the first fault shows on the display. To see the next
fault you push the NO or down arrow button. If there are no more faults, the
display shows BOTTOM OF LIST for 2 seconds.
To see the fault details for one of the faults, push the YES button. Then the
display shows the fault details for that fault. If you push the NO or down arrow
button, the display shows the next fault detail for the same fault. If there are no
more fault details, the display shows BOTTOM OF LIST for 2 seconds.
For Training Purposes Only
FAULT HISTORY
FAULT HISTORY shows previous faults that are still in the memory and have
not been cleared.
From the FAULT HISTORY menu, push the YES button. If there are no faults,
the display shows NO FAULT HISTORY. To go back to the main menu, push
the MENU button.
If there are faults, the display shows FLIGHT 00. To show the next flight leg,
push the NO or down arrow button. Then the display shows the next flight leg.
If there are no more flight legs in memory, the display shows BOTTOM OF
LIST for 2 seconds. The controller can have up to 10 flight legs in memory.
Each flight leg can have faults and fault details. To show a fault for a flight leg,
push the YES button. The display shows the fault. If you push the NO or down
arrow button, the display shows the next fault. If there are no more faults, the
display shows BOTTOM OF LIST for 2 seconds.
To show fault details for each fault, push the YES button. If you want to see
more fault details you push the NO or down arrow button. If there are no more
fault details, the display shows BOTTOM OF LIST for 2 seconds.
For Training Purposes Only
SYSTEM TEST
SYSTEM TEST does a test of the cabin pressurization system.
From the GROUND TEST menu, push the YES button. The display shows
DISPLAY TEST. If you push the NO or down arrow button, the display shows
SYSTEM TEST.
When you push the YES button, the controller does a check to find if the sys-
tem is in auto mode. If the system is not in auto mode, the display shows SYS
IN MANUAL for two seconds. Then the display shows SELECT AUTO.
If you push the YES button when the system is in auto mode, the controller
does a check to find if the other controller is in BITE. If the other controller is in
BITE, the display shows these things:
BOTH SYS IN IBIT for two seconds
IBIT ABORTED for two seconds
SYSTEM TEST.
For each of these questions, it is necessary to push the YES or NO button. If
you push the YES button after each question, the display shows the next ques-
tion. If you push the YES button after the last question, the display shows
TESTING. Each of the 8 lower digits come on for 12 seconds, one digit at a
time. This takes approximately 100 seconds.
If there is no fault while in test, the display shows SYSTEM OK. Then the dis-
play shows, SYSTEM TEST AND CLEAR?. If you push the YES button, all
faults clear from fault history. If you push the NO button, the display shows
SYSTEM TEST.
If there is a fault during TESTING, the display shows nn EXIST FAULTS for 2
seconds. Then the display shows EXISTING FAULTS menu.
If you push the menu button at any time during the system test, the display
shows SYSTEM TEST.
For Training Purposes Only
DISPLAY TEST
DISPLAY TEST does a test of all 16 digits of the LED display.
From the GROUND TEST menu, push the YES button. The display shows
DISPLAY TEST. If you push the YES button, the test starts. Then four digits at
a time turn on for 2.5 seconds. After the test is complete, the display shows
DISPLAY TEST.
For Training Purposes Only
alternate modes of operation. valves. Do not reach through the outflow valve or put tools into it. Injury to per-
sons or damage to equipment may result.
Training Information Point
The valve mounting lug fittings let you remove and install the assembly from
outside the airplane.
MANUAL
DRIVE
MOTOR
ACTUATOR
ASSEMBLY
ELECTRONIC
ACTUATOR (2) POSITION
TRANSDUCER
VALVE COVER
AUTOMATIC
LINKAGE MODE MOTOR (2)
For Training Purposes Only
FORWARD GATE
FILTER
VALVE COVER
CONTROL
CHAMBER
VALVE GATE
DIAPHRAGM
DIAPHRAGM OPERATED
SENSOR CONTROL
VALVE GUIDE CABIN PRESSURE
VALVE GATE
VALVE SEAT
POPPET
DIAPHRAGM
For Training Purposes Only
CABIN PRESSURE
PEDESTAL
101035
AMBIENT SENSING
AND DISCHARGE PORT
Location
The negative pressure relief valve is on the lower aft fuselage, on the left side,
near the aft service door.
You access the valve from the aft cargo compartment.
General Description
The negative pressure relief valve is a mechanical device and operates inde-
pendently. It does not interface with other airplane pressurization systems and
requires no crew action.
The negative pressure relief valve is a flapper type valve. The valve hinges on
its top edge and opens inward. A spring on its hinge pin holds the valve closed.
Negative differential cabin-to-ambient pressure opens the valve. The valve
opens when pressure outside of the airplane is 1.0 psi more than the pressure
inside of the airplane (−1.0 psid).
A stand pipe can be attached to the relief valve assembly. The stand pipe
keeps water out of the airplane during ditching. Water enters the valve until the
weight of the water column in the stand pipe closes the valve.
For Training Purposes Only
NEGATIVE PRESS.
POSITION
RELIEF
VALVE DOOR
NORMAL
POSITION
Location
The cargo compartment blowout panels are in these places:
Cargo compartment ceilings
Cargo compartment bulkheads.
General Description
The cargo compartment blowout panels are held in place by frames.
During rapid decompression, the differential pressures push the panels out of
their frames. This lets pressures in the upper and lower fuselage lobes equalize
quickly. This prevents damage to flight critical structure.
The blowout panels on the cargo compartment bulkheads have grates. The
grates do not let baggage hit the blowout panels.
BLOWOUT
PANELS
AFT CARGO FWD CARGO
COMPARTMENT COMPARTMENT
PRESSURE
EQUALIZATION
BLOWOUT VALVE
PANELS
For Training Purposes Only
BLOWOUT
PANEL
CONTROL
MODULE
SELECTIONS
TOUCHDOWN
CRUISE SCHEDULE
CABIN PRESSURE CABIN PRESSURE
ROTATE CLIMB RATE DESCENT RATE
BEGIN
TAKEOFF
ROLL TAKEOFF
For Training Purposes Only
LANDING PRESSURE
TAKEOFF PRESSURE DIFFERENTIAL
DIFFERENTIAL (0.15 PSID)
(0.1 PSID)
AIRPLANE ALTITUDE
CABIN PRESSURE ALTITUDE
Flight phase.
The CPC compares the target pressure to the pressure at it’s sense port. If a
difference exists the CPC sends an open or close command to its drive elec-
tronics box on the aft outflow valve assembly. The drive electronics box oper-
ates its valve motor. The motor moves the outflow valve through a mechanical
drive train. In this way, the active controller modulates the aft outflow valve to
control cabin pressure and rate of pressure change.
Outflow valve position feedback to the CPC verifies proper valve operation
(closed loop feedback).
28V DC
BUS 1 A
PRESS CONT
AUTO 1
VALVE POSITION
28V DC
BUS 2 B
PRESS CONT
AUTO 2 MANUAL
28V DC
BAT BUS ADIRU 1
PRESS CONT
MANUAL
CABIN
28V DC PRESSURE
BAT BUS SENSE SMYDC 1
PRESS CONT A
IND
P6 CB PANEL
ELACT1
A AUTO A
MOTOR 1 C
CPC 1
T
MANUAL U
VALVE
MODE MO- A
ADIRU 2 TOR T
FLT ALT
CABIN AUTO O
AUTO
LAND ALT PRESSURE R
SENSE MOTOR 2
SMYDC 2
ELACT2
CABIN PRESSURE
CONTROL MODULE OUTFLOW
For Training Purposes Only
B VALVE
B ASSEMBLY
CPC 2
LEFT PACK VALVE
1
PSEU AIR/GROUND LOGIC OPEN/CLOSED RIGHT PACK VALVE
1 ACTIVE CONTROLLER CHANGES
WITH EVERY FLIGHT OR WITH
AN AUTOFAIL EVENT OVBD EXHAUST VALVE
AUTO FAIL
The AUTO FAIL light gives the flight crew indication that the active CPC sys-
tem is inoperative.
Dual Channel Failure
The automatic pressurization control system has a dual redundant architecture.
One digital cabin pressure controller (CPC) is active and maintains pressuriza- These are the indications when both CPC systems fail:
tion control. The other CPC is a backup. If the active CPC channel fails, the The AUTO FAIL and master caution lights come on
system transfers pressurization control to the backup (alternate) CPC channel. The FLT ALT and LAND ALT displays show five dashes (-----).
The two CPCs automatically run start—up and continuous BITE tests. These If both CPCs fail, the ALT Light does not come on. This indicates that the sys-
tests check both systems to the LRU level. When the active CPC BITE detects tem cannot transfer control to an operative automatic channel.
a fault or failure, it transfers active control to the backup CPC.
If both automatic channels fail, you must use the MANUAL mode of pressuriza-
These things cause the auto fail function: tion control. The auto fail function does not transfer pressurization control to the
Power loss manual system. You must select MANUAL on the pressurization mode selec-
Cabin altitude rate of change is too high (>2,000 slfpm) tor. When you select MANUAL these things happen:
Cabin altitude is too high (>15,800 ft) Pressurization control transfers to the MANUAL system
Wiring failures The two CPC systems are disabled
Outflow valve component failures The P5−6 AUTO FAIL Light goes out
CPC failures. The P5−6 MANUAL Light comes on.
Cabin differential pressure is too high (>8.75psi).
Single Channel Failure
The system automatically transfers pressurization control to the backup chan-
nel if the active channel fails.
If the system is in the AUTO mode when an auto fail event occurs, these lights
come on:
The AUTO FAIL light
The Master Caution and AIR COND annunciator lights
For Training Purposes Only
28V DC
BUS 1 A
PRESS CONT
AUTO 1
28V DC
BUS 2 B
PRESS CONT
VALVE POSITION
AUTO 2
28V DC
BAT BUS
ADIRU 1
PRESS CONT
MANUAL
28V DC SMYDC 1
BAT BUS A
PRESS CONT A
IND
P6 CB PANEL
ELACT1
AUTO OFF SCHED
ALTN MANUA
FAIL DESCENT
A A G L G
AUTO AUTO A
FAIL
AUT MANUA CPC 1 MOTOR 1 C
O L
T
V
A MANUAL U
VALVE
FLT ALT
L
ADIRU 2 MOTOR A
V
E T
C
L O AUTO O
O P AUTO
S E R
E N
B SMYDC 2 MOTOR 2
ALTN
AUT MAN
ELACT2
LAND ALT
O
For Training Purposes Only
OUTFLOW
B VALVE
ASSEMBLY
Functional Description
If the airplane begins a descent before it reaches the FLT ALT selected on the
control module, these things happen:
The OFF SCHED DESCENT Light comes on
MASTER CAUTION and AIR COND annunciator lights come ON
The pressurization control system automatically schedules the cabin pres-
sure for return to take−off field.
The OFF SCHED DESCENT Light will go out if these conditions occur:
The airplane begins to climb again
The FLT ALT is reset to the current altitude
The pilot selects manual (MAN) mode
The airplane lands.
If the airplane aborts its mission, and diverts to an field other than the take−off
field, the flight crew must reset the pressure controller:
Select FLT ALT to 200 feet less than airplane altitude (flight cruise altitude
capture)
For Training Purposes Only
Set the landing altitude in the LND ALT window on the selector panel to the
landing field elevation.
The pressure control system cancels the off schedule descent feature for the
flight when the airplane reaches the FLT ALT set on the P5−6 control module.
CRUISE
FLT ALT
MISSION
ABORT − OFF SCHEDULE
BEGIN DESCENT LIGHT
DESCENT
V
BEGIN TAKEOFF RETURN A
TAKEOFF TO LAND L
ROLL FLT ALT
V
E
C
L O
O P
S E
E N
ALTN
AUTO MAN
LAND ALT
28V DC
BAT BUS
ELACT 1 A
MANUAL
PRESSURIZATION MOTOR
CONTROL − MAN BOOSTER C
AUTO
MOTOR 1
P6 CB PANEL T
OPEN U
MANUAL VALVE
MOTOR
A
T
AUTO
MOTOR 2 O
ELACT 2 R
CLOSE
OUTFLOW VALVE SW OUTFLOW VALVE
MANUAL
MANUAL
ALTN
AUTO CPC 1
For Training Purposes Only
PRESSURIZATION
MODE SELECTOR
28/16V DC MANUAL MANUAL
MASTER DIM G
SECT 1
Location
These components are on the cabin altitude panel (P5−17):
Pressure indicators
Warning circuits
Cutout switch.
The pressure switch is on the ceiling of the lower nose compartment.
The warning horn is in the aural warning box on the control stand.
Pressure Indication
The cabin altimeter/differential pressure indicator shows these things:
Cabin pressure altitude (short needle and inner scale)
Cabin−to−ambient differential pressure (long needle and outer scale).
The cabin rate of climb indicator shows the rate of change in cabin pressure
altitude.
Warning System
The aural signal is an intermittent beep.
The cabin altitude warning switch is an aneroid type switch.
For Training Purposes Only
When the cabin altitude reaches 10,000 ft above mean sea level the pressure
warning switch closes. This energizes the warning circuit and causes the inter-
mittent warning horn to sound.
The cutout push-button switch allows the crew to deactivate the warning alarm
until the next high cabin altitude event.
Operation
The cabin altitude pressure switch is a normally open contact aneroid type
switch. The switch will close if the cabin pressure altitude is 10,000 feet or
higher. When the switch closes, these things happen:
The switch grounds the horn circuit, which energizes the system
The aural warning module makes an intermittent beep alarm.
When you press the HORN CUTOUT switch on the P-5 panel, these things
happen:
The K1 relay energizes through the closed pressure switch
When K1 energizes the aural warning circuit OPENS and removes the
ground signal to the aural warning module
The horn circuit loses power and the horn goes off
K1 latches itself through the pressure switch.
When the cabin altitude descends below 10,000 feet., the pressure warning
switch opens, and these things happen:
K1 de-energizes
The warning circuit is reset for the next event.
For Training Purposes Only
28V DC
BAT BUS
AURAL
WARN
28V DC
BAT BUS
PRESS
WARN
M315 AURAL WARNING
P6 CB PANEL ALTITUDE MODULE (P9)
HORN
CUTOUT
K1 CUTOUT
RELAY
(FWD EE COMPT)
June 2004
Page i
TABLE OF CONTENTS
TEMPERATURE CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 CABIN ALTITUDE WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
PACK/ZONE TEMPERATURE CONTROL . . . . . . . . . . . . . . . . . . . . . . 128
UNBALANCED COOLEST MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
UNBALANCED AVERAGE MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
FLIGHT COMP. TEMP. CONTROL SYSTEM . . . . . . . . . . . . . . . . . . . . . 134
PASS. COMPARTMENT TEMP. CONTROL SYSTEM . . . . . . . . . . . . . 136
FLIGHT COMP. AND FWD PASS. ZONE IND. SYSTEM . . . . . . . . . . 138
LIGHT INDICATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
21−20 DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
CONDITIONED AIR DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
MIX MANIFOLD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
RIGHT RECIRCULATION FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
LEFT RECIRCULATION FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
21-30 PRESSURIZATION CONTROL . . . . . . . . . . . . . . . . . . . . . . . . 148
PRESS. CONTROL — GENERAL DESCRIPTION . . . . . . . . . . . . . . . . 150
PRESS. CONTROL MODULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
CABIN PRESSURE CONTROLLER (CPC) . . . . . . . . . . . . . . . . . . . . . . 154
CABIN PRESSURE CONTROLLER BITE . . . . . . . . . . . . . . . . . . . . . . . 156
EXISTING FAULTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
FAULT HISTORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
DISPLAY TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
AFT OUTFLOW VALVE ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
POSITIVE PRESSURE RELIEF VALVE . . . . . . . . . . . . . . . . . . . . . . . . . 166
SAFETY RELIEF VALVE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . 168
NEGATIVE PRESSURE RELIEF VALVE . . . . . . . . . . . . . . . . . . . . . . . . 170
CARGO COMP. BLOWOUT PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
AUTO MODE FLIGHT PROFILE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
AUTO MODE FUNCTIONAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . 176
AUTO FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
OFF SCHEDULED DESCENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
MANUAL MODE FUNCTIONAL DESCRIPTION . . . . . . . . . . . . . . . . . . 182
MANUAL MODE CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
CABIN PRESS. IND. AND ALT. WARN. SYST. . . . . . . . . . . . . . . . . . . . 186
June 2004
Page iii
TABLE OF FIGURES
Figure 71 Distribution System General . . . . . . . . . . . . . . . . . . . . . . . 143
Figure 72 Mix Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Figure 73 Right Recirculation Fan Circuit . . . . . . . . . . . . . . . . . . . . . 147
Figure 74 Pressurization Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Figure 75 Press. Control Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Figure 76 Press. Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Figure 77 Cabin Press. Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Figure 78 CPC-Bite (Main Menu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Figure 79 CPC-Bite (Existing Faults) . . . . . . . . . . . . . . . . . . . . . . . . . 159
Figure 80 CPC-Bite (Fault History) . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Figure 81 CPC-Bite (Ground Tests) System Test . . . . . . . . . . . . . . 163
Figure 82 CPC-Bite (Ground Test) Display Test . . . . . . . . . . . . . . . 165
Figure 83 Aft Outflow Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Figure 84 Pressure Relief Valve Schematic . . . . . . . . . . . . . . . . . . . 169
Figure 85 Negative Pressure Relief Valve . . . . . . . . . . . . . . . . . . . . 171
Figure 86 Blowout Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Figure 87 Auto Mode Flight Profil . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Figure 88 Auto Mode Functional Schematic . . . . . . . . . . . . . . . . . . . 177
Figure 89 Auto Fail Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Figure 90 Off Schedule Descent Circuit . . . . . . . . . . . . . . . . . . . . . . 181
Figure 91 Press. Contr. Manual Mode . . . . . . . . . . . . . . . . . . . . . . . . 183
Figure 92 Manual Mode Elec. Schematic . . . . . . . . . . . . . . . . . . . . . 185
Figure 93 Cabin Pressure & Altitude Warning System . . . . . . . . . . 187
Figure 94 Cabin Altitude Warning Circuit . . . . . . . . . . . . . . . . . . . . . 189
June 2004
Page iv
For:batch
Printed on:Mon, May 30, 2005 07:36:38
From book:B737-6 21 JAR B1 E
Document:DB
Last saved on:Mon, May 30, 2005 07:35:16
Document:01/21-00/L1/L3D/B1/B2
Last saved on:Mon, May 30, 2005 07:35:23