SYARAT – SYARAT TEKNIK DAN GAMBAR


BAB IV.3 : TECHNICAL SPECIFICATION

protection cubicles provided shall already be wired for the possible total
number of feeders.
Thus, later on, the respective prints, modules or parts for extensions can easily
be fitted to the protection system and no cubicle wiring at Site shall be
necessary.
Prior to manufacturing, the Contractor shall indicate the remaining extension
possibilities in the same cubicle(s) and the final quantity of provis ions for future
feeders shall be approved by the Engineer.

4.3.5.3 Bus Coupler/Sectionalizer Over Current


Three phase normal IDMT elements shall be provided for over current
protection. These IDMT elements shall comply with latest IEC and their curves
shall be such as to give tripping after three seconds for ten times the current
setting when a time multiplier setting of 100 % is applied.
The over current IDMT elements shall have current ranges from 50 % to 200
%, adjustable in steps of 1 %.
The time settings for over current IDMT elements shall be continuously
variable from 0 to 1.0 or, as an alternative, with steps of at least 0.05 from 0.05
to 1.0.
Each of the IDMT elements shall have separate trip and alarm contacts and
separate trip indicators. Separate contacts for the disturbance recorder shall
also be provided.

4.4 Teleprotection Schemes


It is required to provide (according to the requirement) direct and permissive -
transfer-trip signaling channels to send and receive signals associated with
over head lines, cable and breaker failure protection schemes. These
permissive and direct channels shall have transmission times of less than 20
ms.
A segregated alarm for all the signals transmitted or received in a
teleprotection scheme will be included in each of the related protection board.
For digital differential protection, direct digital communication links shall be
provided.
It shall be possible to test each individual channel separately and means shall
be provided to send and receive inter trip signals for test purposes without
removing any wire or permanent connection and without tripping the
associated circuit breaker.
All the interface wiring between the protection board and the respective
communication equipment shall be performed by the Contractor.
POR (permissive over reaching schemes) will always be provided with a weak
in-feed logic able to trip selectively the circuit breakers. Their logic will not be
only dependant of auxiliary contacts of the circuit breaker.
In the case of the direct tripping equipment it shall be designed not to cause a
trip out put under any of the following conditions.
• Removal of any printed circuit module in either transmitter or receiver

C & PE 28