Professional Documents
Culture Documents
Adequate clearance shall be provided from adjacent pipes or structure to allow for removal or
rotation of blinds. A table is presented to quickly determine installation envelope for NPS 2” to
12”; Class 150, Class 300, Class 600, Class 900, Class 1500, Class 2500 spectacle blinds. This is
illustrated by simple hypothetical example showing different piping configurations/cases to find
out pipe spacing.
Spectacle blinds (Figure 1) are usually required to isolate individual pieces of equipment at
shutdown, to positively block off selected process lines at process unit limits and where segregation
of fluids is required. However, these are difficult to handle in the larger sizes/higher flange rating
(Note-1), and instead separate spacers and blanks are used. Moreover, adequate clearance shall be
provided from adjacent pipes or structure to allow for removal or rotation of blinds. A table is
presented to quickly determine installation envelope for NPS 2” to 12”; Class 150, Class 300, Class
600, Class 900, Class 1500, Class 2500 spectacle blinds. This is illustrated by simple hypothetical
example showing different piping configurations/cases to find out pipe spacing.
= 45°, 67.5°, 75°, 78.75°, 81° depending on Flange size and Rating
C A C
R1 = (2 + 2 ) + 2 cos θ…………………………………………………………………………………………………………………Eq 1
Similarly
C A C
R2 = (2 + 2 ) − 2 cos θ……………………………………………………………………………………………………………….Eq 2
Please note that installation envelope is (vertical) axis asymmetric and require different clearance
(more horizontal clearance on the right side as compared to the left side). Consider following
dimensions to calculate pipe spacing as illustrated by the example at the end of article.
Consolidated Table
Similar tables can be developed for Class 300, Class 600, Class 900, Class 1500, Class 2500 spectacle
blind. See Table-2 for consolidated dimensions required for installing Spectacle Blind for various
Flange Ratings, size ranging from 2” to 12”.
NPS R1 R2 R1 R2 R1 R2 R1 R2 R1 R2 R1 R2
2" 153 66 142 93 142 93 184 121 184 121 190 124
3" 196 89 189 125 189 125 214 141 226 148 255 167
4" 217 145 227 151 245 162 264 174 270 177 305 200
6" 276 184 293 224 316 240 343 260 339 257 411 271
8" 344 230 360 275 379 288 425 324 422 320 468 354
10" 396 303 411 335 457 372 497 405 519 395 576 436
12" 475 363 479 391 510 433 557 473 600 488 663 503
Table 2 Consolidated Dimensions for installation of Spectacle Blind, Dimensions R1 & R2 (dimensions
in mm except NPS)
Illustrated Example
Figure 2 is self-explanatory and shows pipe spacing for three different configuration/cases. For Case
3, flanges (and spectacle blinds) in adjacent lines must be staggered to optimize spacing. So, the
correct spacing, dimension B, is SB1 + G + P2 (instead of SB1 + G + F2).
Figure 3 Pipe Spacing with Spectacle Blinds-Different Cases
Conclusion / Take-away
It is evident that the distance between a flange and any obstruction shall allow for the removal or
turning of a blind, if present. Table 2 quickly determine installation envelope for spectacle blind and
eliminates preparing scaled sketch by Piping Designer and/or doing trigonometric calculation by
Piping Engineer.
Notes
1. As a guideline, Spectacle blinds should be used in the following sizes:
2. Whenever possible, Spectacle blinds should be put on the outside edge of the pipe sleeper
or pipe rack to ease their installation/removal, to minimize pipe sleeper width and
minimize/avoid platform access.
References
1. Piping Handbook, page C.337, 7th Edition by Mohinder L. Nayyar, McGraw Hill.
2. ASME B16.48, Line Blanks
Source
https://www.linkedin.com/pulse/clearance-swinging-spectacle-blind-jamshaid-abid-pmp