You are on page 1of 166

Power System Quality and

Reliability

HARMONICS AND ITS


TREATMENT IN POWER
SYSTEMS
OUTLINE OF PRESENTATION

1. DEFINITIONS
2. CATEGORIES OF POWER QUALITY VARIATIONS
3. HARMONIC DISTORTION SOURCES IN INDUSTRIAL POWER
SYSTEMS
4. EFFECTS OF HARMONICS ON ELECTRICAL EQUIPMENT
5. HARMONIC MEASUREMENTS IN INDUSTRIAL POWER SYSTEMS
6. HARMONIC STANDARDS
7. HARMONIC MITIGATING TECHNIQUES
8. GENERAL PASSIVE AND ACTIVE FILTER DESIGN PROCEDURES
9. DESIGN EXAMPLES
10. CONCLUSIONS

2 HarmonicAnalysis PQR
1. DEFINITIONS

What are Harmonics?


Definition:

Harmonics are integral multiples of some fundamental


frequency that, when added together, result in a distorted
waveform.

The “first harmonic” is really just the fundamental frequency.


The second is twice that frequency, the third is three times, and
so on. Thus for a power system, the fifth harmonic would be
300 Hz.
Harmonics may appear in any system that oscillates at a given
frequency (e.g. light waves, sound pressure waves, mechanical
vibrations, etc.
3 HarmonicAnalysis PQR
Harmonics
⚫ It is a steady state periodic phenomenon that produces
continuous distortion in voltage and current waveform.
⚫ It is normally caused by saturable devices, power
electronics devices and non linear consumer loads.
⚫ Total Harmonic Distortion (THD) is a measure of
harmonic voltage/current. The THD in a voltage

waveform is defined as  n
V 2

n=2
THD =
V1
Where, Vn is the magnitude of nth harmonic voltage and V1
is the magnitude of fundamental voltage.

4
PQR
HarmonicAnalysis
What Causes Harmonics?

Non-Linear Loads

Current is not proportional to the applied voltage

5
PQR
HarmonicAnalysis
Linear vs. Non-linear loads and current waveforms

Linear loads and current waveforms.


Pure resistance, inductance, and
capacitance are all linear.
What that means:
If a sine wave voltage of a certain
magnitude is placed across a
circuit containing pure resistance,
the current in the circuit follows
Ohm's Law: I = E÷ R.
The relationship of volts and
amperes is a straight line.
The current will always be a sine
wave of the same frequency.
72
6
PQR
HarmonicAnalysis
Linear vs. Non-linear loads and current waveforms

Solid state electronics is based


on the use of semiconductors.
These materials are totally
different in that their response
to voltage is not a straight line.
What this means:
With a nonlinear load, you
cannot easily predict the
relationship between voltage
and current — unless you have
an exact curve for each device.
With equipment containing
many solid-state devices, such
an approach is impossible.
73
7
PQR
HarmonicAnalysis
Effect of harmonics on waveform

180 Out
of Phase

In
Phase
When a waveform is identical from one waveform to the next, it can be represented as a sum
of pure sine waves in which the frequency of each sinusoid is an integer multiple of the
fundamental frequency of the distorted wave.
The sum of the sinusoids created by harmonics can be analyzed using the Fourier series concept
74
8
PQR
HarmonicAnalysis
Harmonics

• Harmonics: Frequency components that are


integer multiples of the fundamental line
frequency

• fundamental frequency is 50 Hertz


– 3rd Harmonic is 3 x 50Hz or 150Hz
– 5th Harmonic is 5 x 50Hz or 250Hz, etc.

75
9
PQR
HarmonicAnalysis
What do harmonics do?

• Harmonics are carried through the system from the source


and can nearly double the amount of current on the neutral
conductor in three phase four wire distribution systems.

• Distorted currents from harmonic-producing loads also


distort the voltage as they pass through the system
impedance. Therefore, a distorted voltage can be
presented to other end users on the system.

• Overall electrical system and power quality is affected by


the introduction of harmonics.
76
10
PQR
HarmonicAnalysis
Sources of Harmonics

• Solid State Electronic Devices which contain a poor


power supply
– Computers (PCs/CPUs)
– Video display terminals
 Laser Printers – File Servers
 Copy Machines – Battery Chargers
 Solid State UPS Units
• Solid State Devices (Fluorescent lighting ballasts)
• Rectifiers (AC-DC Converters)
• VFDs
• Welding Units
•PQR
11
Arc Furnaces HarmonicAnalysis
Effects of Harmonics

• Overheated Transformers and Motors


– Increases Hysteresis (magnetization) losses in
steel and iron cores of transformers, motor and
magnetic trip units of circuit breakers
(Equipment inefficiencies and overheating)
• Heating of Neutral Conductors
• Low Voltage at End Loads

79
12
PQR
HarmonicAnalysis
Effects of Harmonics (cont)
• Operation Problems of Relays and Circuit
Breakers
– Thermal/Magnetic Trip Circuit Breakers
• Fuses & bimetal strips respond to True RMS
• Harmonic currents increase eddy current
losses in the core steel of the metallic strip.
• This causes an overprotection situation…
Increased losses generate additional heat,
this effect the thermal trip of the unit.

80
13
PQR
HarmonicAnalysis
Effects of Harmonics (cont)

• Operation Problems of Relays and Circuit Breakers


– Electronic Trip Circuit Breakers
• Magnitude and phase angle(s) of harmonic
current(s) in relationship to the fundamental
current can cause:
– Overprotection: Peak current sensing > True RMS
– Under protection: Peak current sensing < True RMS
• Changing power system loads will vary the
magnitude and phase angle, resulting in inaccurate
and unpredictable sensing units and overload
protection

14
PQR
HarmonicAnalysis
Effects of Harmonics (cont)
• Communication Problems
– If sharing common parallel path, potential for
harmonics to have inductive coupling effect on
unshielded cabling
• Current Measurement Problems (distorted waveform)
• Unreliable Operation of Electronic Equipment
– Mis-operation of electronic equipment that
measures frequency or uses the zero crossing point
of a sine wave.
– Control of Speed and Voltage Problems on
Emergency Generators (supplying power)
– Computer (PC/CPU) data errors / data loss
– Affects power supplies and sensitive electronics

PQR 15
HarmonicAnalysis
Harmonics

Fig. Harmonic-generating load causing voltage distortion at the point


of common coupling (PCC). The AC source is modeled as an ideal
voltage source in series with a resistance Rs and a reactance jXs.
PQR 16
HarmonicAnalysis
Harmonics

17
PQR
HarmonicAnalysis
Harmonics

Single phase,
two-pulse diode
rectifier with
capacitive DC-link

Phase voltage
(continuous) and
phase current
(pulsed) to a
television receiver

18
PQR
HarmonicAnalysis
Harmonics

86
19
PQR
HarmonicAnalysis
Harmonic wave and its expansion using Fourier

Frequency spectrum

20 HarmonicAnalysis PQR
Effect of harmonics on waveform

180 Out
of Phase

In
Phase

The above is an integer harmonic. Depending on the type of


loads, subharmonics or interharmonics are also generated. 21
PQR
HarmonicAnalysis
Spectrum of a Typical Distorted Voltage
Waveform
(a) Distorted Waveform
1.5 (b) Spectrum of (a)

1
1

0.5
0.8
THD= 43.83%

Harmonics Magnitudes (pu)


Voltage (pu)

0.6
0
Fundamental

-0.5 0.4

-1 0.2

-1.5
0 0.005 0.01 0.015 0.02 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Time(s)
Harmonics Number

22
PQR
HarmonicAnalysis
• Although easy to measure, the THD does not show
the interference impact of the signal.
• Total Demand Distortion (TDD) is a measure of the
THD taking into account the circuit rating. As the
circuit rating versus load current rises, TDD drops
TDD = THD x (Fundamental load current/circuit
rating)

23
PQR
HarmonicAnalysis
What do harmonics do?
⚫ Harmonics are carried through the system from the source
and can nearly double the amount of current on the neutral
conductor in three phase four wire distribution systems.
⚫ Distorted currents from harmonic-producing loads also
distort the voltage, which appear to other end users on the
system.
⚫ Overall electrical system performance and power quality is
affected by the introduction of harmonics, such as
• Overheating of Transformers, Capacitors and Motors
• Mal-operation Relays and Circuit Breakers
• Communication Interference Problems
• Unreliable Operation of Electronic Equipment
• Computer (PC/CPU) data errors / data loss
24
PQR
HarmonicAnalysis
Order of typical harmonics generated by non-
linear loads?

25
PQR
HarmonicAnalysis
2. Power-Quality Standards

•IEEE Standards 519-defines acceptable power


quality
•IEEE Standards 1159-defines the measurement
of power-quality “events”

26 PQR HarmonicAnalysis
Power-Quality Standards IEEE 519

27
PQR
HarmonicAnalysis
Power-Quality Standards

• ISC maximum short-circuit current at PCC.


• IL maximum demand load-current (fundamental frequency
component) at PCC
.PQR 95
28

HarmonicAnalysis
What kind of Power Quality Effects?

⚫ Harmonic Distortion

– AFDs, DC Drives, UPSs, DC power supplies (computers,


duplicators, fax’s) will cause current (and voltage)
harmonics
⚫ Single phase – 3rd, 6th, etc (triplens) can cause
transformer neutral conductor overheating
⚫ Three phase – 5th, 7th, 11th, 13th, etc can cause
equipment malfunctions
⚫ Big questions – “How much?” and “How much is too
much?”

29 HarmonicAnalysis PQR
Harmonic Voltage Limit as per IEEE-519
(utilities’ responsibility)

Bus Voltage Maximum Maximum


Individual THD (%)
Harmonic
Component (%)
69 kV and below 3.0% 5.0%

115 kV to 161 kV 1.5% 2.5%

Above 161 kV 1.0% 1.5%

30 HarmonicAnalysis PQR
Harmonic Current Limit as per IEEE-519
(customers’ responsibility)
SCR h<11 11<h<17 17<h<23 23<h<35 35<h TDD
=Isc/IL
<20 4.0 2.0 1.5 0.6 0.3 5.0

20 -50 7.0 3.5 2.5 1.0 0.5 8.0

50 -100 10.0 4.5 4.0 1.5 0.7 12.0

100 -1000 12.0 5.5 5.0 2.0 1.0 15.0

>1000 15.0 7.0 6.0 2.5 1.4 20.0

Values shown are in % of “average maximum load current”


SCR = short circuit ratio (short circuit current at point of common
coupling divided by customer average maximum load current)
TDD = Total Demand Distortion (uses maximum load current as the
base, rather than the fundamental current)
31 HarmonicAnalysis PQR
Indian standards on harmonic limits

CBIP Report No. 251


⚫ Total Harmonic Distortion (THDV) = 9% in 0.4 <
U < 45 kV
APERC
⚫ The cumulative (THDv) at the Point of
Commencement of Supply for each consumer
connected at 33kV shall be limited to 8% (as per
Grid Code)
⚫ The cumulative (THDv) at the Point of
Commencement of Supply for each consumer
connected at 11kV shall be limited to 8% (as per
Grid Code)
32 HarmonicAnalysis PQR
WAVE FORM DISTORTION
Periodic Waveforms and Harmonics: periodic waveform can be
broken up into a series of sine waves at the proper amplitudes and phase.

⚫ Any periodic waveform can be expressed as a sum of sine and/or


cosine waves, with the proper amplitude, frequency, and phase
relationships between the waves.

⚫ For instance, a square wave can be represented by the infinite Fourier


series:

33
PQR
HarmonicAnalysis
WAVEFORM DISTORTION: Square Wave

34
PQR
HarmonicAnalysis
WAVEFORM DISTORTION: Root-mean square

• Root-mean square: Root-mean square is a


measure of the heating value of a periodic
waveform when this periodic waveform
drives a resistive load.
• Mathematically, the root-mean square or
rms of a periodic voltage waveform is
expressed as:

35
PQR
HarmonicAnalysis
Harmonics
Harmonics
It is also common to use a single quantity, the Total Harmonic
Distortion (THD), as a measure of the effective value of harmonic
distortion.
2
n=nmax
 Vn 
THD =    x100  5%
n=2  V1 
Where V1-Fundamental frequency voltage component Vn=nth harmonic voltage
component

The Total Demand Distortion (TDD) is the same term as the Total
Harmonic Distortion except that the distortion is expressed as a
percent of some rated load current rather than as a percent of the
fundamental current magnitude.
36
PQR
HarmonicAnalysis
How can Harmonics be Reduced?

• Isolate harmonic loads on separate circuits


• Filter capacitor banks: a circuit capable of selectively
filtering one frequency or range of frequencies out of a
mix of different frequencies is called a filter circuit, or
simply a filter.
• Harmonic mitigating transformers
– Used to cancel out specific harmonics by making one
voltage circuit 180 degrees out-of-phase

3737
PQR
HarmonicAnalysis
How can Harmonics be Reduced?

• PROPER GROUNDING
– Neutral to ground conductor connection at one location;
at main panel or transformer secondary
– Run power and control conductors in separate raceways
– Sensitive loads should not share neutral and ground
conductors.
– Avoid using conduit as the ground return path, run
dedicated ground wire with circuit conductors

3838
PQR
HarmonicAnalysis
Low pass filter:
• A low-pass filter is a circuit offering easy passage to
low-frequency signals and difficult passage to high-
frequency signals.
• The inductor’s impedance increases with increasing
frequency. This high impedance in series tends to block
high-frequency signals from getting to the load.

3939
PQR
HarmonicAnalysis
Low pass filter:
• The capacitor’s impedance decreases with
increasing frequency. This low impedance in
parallel with the load resistance tends to short out
high-frequency signals, dropping most of the
voltage across series resistor.

4040
PQR
HarmonicAnalysis
High pass filter:
• High-pass filter’s task is just the opposite of a low-
pass filter: to offer easy passage of a high-
frequency signal and difficult passage to a low-
frequency signal.

4141
PQR
HarmonicAnalysis
High pass filter:
• This high impedance in series tends to block low-
frequency signals from getting to load. The inductor’s
impedance decreases with decreasing frequency.

4242
PQR
HarmonicAnalysis
Passive filters

• Shunt passive filters. The most common type of passive


filter is the single-tuned “notch” filter. The notch filter is
series-tuned to present a low impedance to a particular
harmonic current and is connected in shunt with the power
system. Thus, harmonic currents are diverted from their
normal flow path on the line through the filter.

4343
PQR
HarmonicAnalysis
Passive filters
• Shunt passive filters. The filter is usually placed as shown in
Figure to divert a selected portion of the harmonic currents
produced by the nonlinear load.
• The filter is usually made up of one or more sections, as shown in
Figure. The single- tuned RLC filter for each harmonic frequency
is the most common. The impedance Z of the single-tuned section
shown in Figure is given by:

• The resistance R is due to the winding loss and the core loss of the
inductor. The quality factor, or Q of an inductor, is given by:

44
44
• Typical
PQR values of Q for filter inductors are 25 to 45 at 50 Hz.
HarmonicAnalysis
Passive filter

Passive filter is tuned to a harmonic order near the one to be eliminated. A number of
parallel-connected filters may be used when a significant reduction in distortion over a
104
45
range
PQRof orders is required.
HarmonicAnalysis
Passive filters

• Series passive filters. Unlike a notch filter which is


connected in shunt with the power system, a series
passive filter is connected in series with the load.
• The inductance and capacitance are connected in
parallel and are tuned to provide a high impedance at a
selected harmonic frequency.

4646
PQR
HarmonicAnalysis
Multi-section filters
• The filter is designed to attenuate higher-order
harmonics such as the 5th, 7th, and 11th that are
generated by the nonlinear load.

4747
PQR
HarmonicAnalysis
Passive filters
• Line reactor: One of the simplest harmonic filters is
the line reactor shown as the three-legged inductor in
Figure. This magnetic component is often used in the
line in series with motor controllers and other
converters that draw significant harmonic current.
The reactor presents high impedance to high
frequency currents while passing the fundamental.

4848
PQR
HarmonicAnalysis
Active filters
• Active filters are relatively new types of devices for
eliminating harmonics. They are based on sophisticated
power electronics and are much more expensive than
passive filters.
• They can also address more than one harmonic at a time
and combat other power quality problems such as flicker.
• The basic idea is to replace the portion of the sine wave
that is missing in the current in a nonlinear load. An
electronic control monitors the line voltage and/or
current, switching the power electronics very precisely to
track the load current or voltage and force it to be
sinusoidal
109
49
PQR
HarmonicAnalysis
Active Filter

The active filter


injects, in opposite
phase, the
harmonics drawn
by the load, such
that the line current
Is remains
sinusoidal.

5050
PQR
HarmonicAnalysis
Harmonics and transformers

Transformer overheating and potential


insulation failure result from several
conditions caused by harmonics:

Increased skin and proximity effects

Harmonics circulating in the primary


winding

AFC AFC Increased hysteresis losses

Increased eddy current losses

DC in the primary windings

51 HarmonicAnalysis PQR
Harmonics and transformers

Many transformers are rated by


“K factor” which simply describes
their ability to withstand harmonics.

Transformers may also be derated


to compensate for the additional
heating caused by harmonics.

Improved transformer designs have


also been developed, with oversized
AFC AFC
neutral busses, special cores, and
specially designed coils.

52 HarmonicAnalysis PQR
Harmonics and power-correction capacitors

Power correction capacitors can cause


series and parallel resonance effects on
a power system.

If a harmonic is generated which excites


a system resonance, amplification of that
harmonic may occur.

Calculation of the harmonic resonance frequency for the system can


give an indication of potential resonance problems.

53 HarmonicAnalysis PQR
Harmonics and Power-correction Capacitors

EXAMPLE:

Assume a 1500 kVA supply xfmr,


1500 kVA with a 5.75% impedance.
5.75%

Also assume 600 kVA of power


600 kVAC correction capacitors on the system

The harmonic resonance frequency is defined by:

kVAsc 1500 / 0.0575 = 6.6


hr = =
kVAC 600

54 HarmonicAnalysis PQR
Attenuation of Harmonics

Inductive Reactance

Method: Add a line reactor or isolation transformer


to attenuate harmonics.

Benefits: Low cost.

Technically simple.

Concerns: Tends to offer reductions in only higher


order harmonics. Has little effect on the 5th
and 7th harmonics.

Because of the associated voltage drop,


there are limits to the amount of reactance
that may be added.
Line reactors are a good solution when a reduction of only a
55 few percent is necessary.
HarmonicAnalysis PQR
Attenuation of Harmonics
Passive Filters

Method: Provide a low-impedance path to ground


for the harmonic frequencies.
Benefits: May be tuned to a
frequency between two prevalent harmonics
so as to help attenuate both.
Concerns: Tuning the filters may be a labor-intensive
process.
Filters are difficult to size, because they offer
a path for harmonics from any source.
Quite sensitive to any future system changes.
A man-week of labor is not uncommon to properly install and tune passive filters.
If a filter is tuned to the 5th harmonic, for example, and some other facility on the
power grid begins to put 5th harmonics on the system, then this filter will be a path for
those currents as well!
Filters will likely have to be retuned at some later date if system changes are made.
56 HarmonicAnalysis PQR
Attenuation of Harmonics
Active Filters

Method: Inject equal and opposite harmonics onto the


power system to cancel those generated by
other equipment.
Benefits: Have proven very effective in reducing
harmonics well below required levels.

Concerns: The high performance inverter required for the


harmonic injection is costly.

Power transistors are exposed to conditions


of the line, so reliability may be a problem.

57 HarmonicAnalysis PQR
Attenuation of Harmonics
12-pulse Rectifiers
Method: Two separate rectifier bridges supply a single
DC bus. The two bridges are fed from phase-
shifted supplies.
Benefits: Very effective in the elimination of 5th and 7th
harmonics.
Stops harmonics at the source.
Insensitive to future system changes.

Concerns: May not meet the IEEE standards in every


case.
Does little to attenuate the 11th and 13th
harmonics.

Remember the “nk+/-1” rule. From this, it is seen that 12-pulse


drives still generate 11th, 13th, 23rd and 25th harmonics. In
some cases this may be enough to exceed IEEE limits.
58 HarmonicAnalysis PQR
Attenuation of Harmonics
18-pulse Rectifier

Method: An integral phase-shift transformer and rectifier


Input which draws an almost purely sinusoidal
waveform from the source.
Benefits: Meets the IEEE standards in every case!

Attenuates all harmonics up to the 35th.

Stops harmonics at the source.

Insensitive to future system changes.

Concerns: Can be expensive at smaller HP’s

The Clean Power Option is available only on Accutrol 700’s, from


100-600 hp.
59 HarmonicAnalysis PQR
Comparison of waveforms

6-pulse converter
note the level of distortion
and steep current rise.

12-pulse converter

the waveform appears more


sinusoidal, but still not very
smooth.

18-pulse converter

virtually indistinguishable
from the source current
waveform.

60 HarmonicAnalysis PQR
WHY HARMONIC ANALYSIS ?

When a voltage and/or current waveform is distorted, it causes abnormal


operating conditions in a power system such as:

⚫ Voltage Harmonics can cause additional heating in induction and


synchronous motors and generators.
⚫ Voltage Harmonics with high peak values can weaken insulation in cables,
windings, and capacitors.
⚫ Voltage Harmonics can cause malfunction of different electronic
components and circuits that utilize the voltage waveform for
synchronization or timing.
⚫ Current Harmonics in motor windings can create Electromagnetic
Interference (EMI).

61 HarmonicAnalysis PQR
⚫ Current Harmonics flowing through cables can cause higher heating over
and above the heating that is created from the fundamental component.
⚫ Current Harmonics flowing through a transformer can cause higher
heating over and above the heating that is created by the fundamental
component.
⚫ Current Harmonics flowing through circuit breakers and switch-gear can
increase their heating losses.
⚫ RESONANT CURRENTS which are created by current harmonics and
the different filtering topologies of the power system can cause capacitor
failures and/or fuse failures in the capacitor or other electrical equipment.
⚫ False tripping of circuit breakers ad protective relays.

62 HarmonicAnalysis PQR
HARMONIC SOURCES
a) Current Source nonlinear load

Thyristor rectifier for dc drives, Per-phase equivalent circuit


heater drives, etc. of thyristor rectifier
b) Voltage source nonlinear load

Diode rectifier for ac drives, Per-phase equivalent circuit


electronic equipment, etc of diode rectifier

63 HarmonicAnalysis PQR
INPUT CURRENT OF DIFFERENT
NOLINEAR LOADS

TYPE OF TYPICAL WAREFORM THD%


NONLINEAR LOAD

1.0

1-φ 0.5 80%


Uncontrolled (high 3rd
Current
0.0

Rectifier component)
-0.5

10 20 30 40
0
-1.0
Time (mS)

1.0
2nd, 3rd, 4th ,......
1-φ 0.5
harmonic
Current

Semicontrolled 0.0 components


Rectifier Bridge -0.5

10 20 30 40
0
-1.0
Time (mS)

1.0

6 –Pulse Rectifier 0.5

with output voltage 80%


Current

0.0
filtering and without -0.5
input reactor filter 0
10 20 30 40 5, 7, 11, ……….
-1.0
Time (mS)

64 HarmonicAnalysis PQR
1.0
6 - Pulse Rectifier
0.5
with output voltage 40%

Current
filtering and with 3% 0.0 5, 7, 11, ………..
reactor filter or with -0.5
continues output 0
10 20 30 40
-1.0
current Time (mS)

1.0

6 - Pulse Rectifier 0.5

with large output 0.0 Current 28%


inductor -0.5 5, 7, 11, ………..
0 10 20 30 40
-1.0 Time (mS)

1.0

0.5

12 - Pulse Rectifier 15%


Current

0.0

-0.5
11, 13, ………..
0 10 20 30 40
-1.0 Time (mS)

65 HarmonicAnalysis PQR
CURRENT HARMONICS GENERATED BY 6-PULSE CSI CONVERTERS
HARMONIC P.U PULSE
1 1.00
5 0.2
7 0.143
11 0.09
13 0.077
17 0.059
19 0.053
23 0.04
CURRENT HARMONICS GENERATED BY 12-PULSE CSI CONVERTERS
HARMONIC P.U PULSE IEEE 519 std
1 1.00 -
5 0.03-0.06 5.6%
7 0.02-0.06 5.6%
11 0.05-0.09 2.8%
13 0.03-0.08 2.8%
THD 7.5%-14.2% 7.0%
66 HarmonicAnalysis PQR
RECENT CURRENT MEASUREMENTS TAKEN IN AN
INDUSTRIAL PLANT WITH 600 KVA, 20 KV/400 V
DISTRIBUTION TRANFORMER

Current waveform and its respective spectrum


at the inputs of a motor drive system

67 HarmonicAnalysis PQR
Current waveform and its
respective spectrum at the
inputs of a motor drive system

68 HarmonicAnalysis PQR
Current waveform and its respective spectrum
at the secondary of the distribution transformer
( i.e. at the service entrance)

69 HarmonicAnalysis PQR
DEFINITIONS

f (t) = Fourier Series of a periodic function f (t)



f (t) = Co +  C h cos (hωt + θ h )
h =1 (1)

1 T
C o = o f ( t )dt , Ch = A 2h + B2h (2)
T
2 T
A h = o f ( t ) cos( hωt )dt (3)
T
2 T
Bh = o f ( t ) sin(hωt )dt (4)
T

h = harmonic order

70 HarmonicAnalysis PQR
THD υ % = Percentage of the Total Harmonic Distortion of
a nonsinusoidal voltage waveform

2
 Vh
h =2
=  100 (5)
V1
THD i % = Percentage of the Total Harmonic Distortion of
a nonsinusoidal current waveform

2
 Ih
= h =2
100 (6)
I1
Vh = hth harmonic component of the voltage

I h = hth harmonic component of the current


~ ~2
VH = RMS value of the voltage distortion =  h
V
h =2

71 HarmonicAnalysis PQR
~ ~2
IH = RMS value of the current distortion =  Ih
h =2
~
I= RMS value of a nonsinusoidal current =
~2 (7)
=  Ih
h =1
~
V= RMS value of a nonsinusoidal voltage =

~2
=  Vh
(8)
h =1
Drive kVA
THD υ % = HF   100 (9)
SC kVA

 h 2 I 2h / I1 (10)
HF = Harmonic Factor = h =5

72 HarmonicAnalysis PQR
Drive kVA = Full load kVA rating of the Drive system

SC kVA = Short Circuit kVA of the distribution system at


the point of connection

SINUSOIDAL VOLTAGE NONSINUSOIDAL CURRENT


~~
P = V Ii,1 cos φ1 (11)

~~ ~~
Q = V Ii,1 sin φ1 , S = V I (12)

D = Distortion VA = S2 − P2 − Q2 (13)

73 HarmonicAnalysis PQR
( )

~ ~ ~ ~2
D 2
= S − V 2 Ii,21 = V 2
2
 Ii,h (14)
h =2
P  Ii,1 
λ = True Power Factor = =   cos φ1 (15)
S  I 

= Distortion Factor  Displace ment Factor


NONSINUSOIDAL VOLTAGE AND NONSINUSOIDAL CURRENT

 
~ ~ ~ ~
P =  Vh Ih cos φ h , Q =  Vh Ih sin φ h (16)
h =1 h =1
 
D = Distortion Power =  SnmS*nm − S S*
 n m (17)
n m n m
n m n m

74 HarmonicAnalysis PQR
S2 = P 2 + Q 2 + D 2 (18)


S=
~ 2~ 2
V I = V ( ) (
~~ 2 ~~
 h h 1 I1 + V1 IH )2 + (V~H ~I1 )2 +
h =1

(~ ~
+ VH IH )
2
= S12 + S2N (19)
~~
S1 = Fundamenta l Apparent Power = V1 I1

SN = Nonfundame ntal Apparent Power

( ) (
~~ 2 ~ ~ 2 ~ ~ 2
S2N = V1 IH + VH I1 + VH IH) ( )

75 HarmonicAnalysis PQR
~~
V1 IH = Current Distortion Power
(20)

~ ~
VH I1 = Voltage Distortion Power (21)

~ ~
VH IH = Harmonic Apparent Power (22)

S2H = PH2 + N 2H = Total Harmonic Active Power +


(23)
+ Total Harmonic Non Active Power

XC = Reactance of the capacitor = (VL-L )2 / VAR 3−phase

76 HarmonicAnalysis PQR
Harmonic sequence is the phase rotation relationship with respect to
the fundamental component.

Positive sequence harmonics ( 4th, 7th, 10th , ……. (6n+1) th ) have


the same phase rotation as the fundamental component. These
harmonics circulate between the phases.

Negative sequence harmonics ( 2nd, 5th, 8th ……… (6n-1) th ) have


the opposite phase rotation with respect to the fundamental component.
These harmonics circulate between the phases.

Zero sequence harmonics ( 3rd, 6th, 9th, ….. (6n-3) th ) do not produce
a rotating field. These harmonics circulate between the phase and neutral
or ground. These third order or zero sequence harmonics, unlike positive
and negative sequence harmonic currents, do not cancel but add up
arithmetically at the neutral bus.

77 HarmonicAnalysis PQR
EXAMPLE 1
SINUSOIDAL VOLTAGE-NONSINIMUSOIDAL CURRENT

A periodic, sinusoidal voltage of instantaneous value v = 200 2 sin ωt


Is applied to a nonlinear load impedance. The resulting instantaneous current is
given by:  ( ) ( ) (
i = 2 20 sin ωt − 45o + 10 sin 2ωt + 60o + 10 sin 3ωt + 60o )
Calculate the components P, Q, D of the active power, apparent voltamperes and
hence calculate the displacement factor, the distortion factor and the power factor.
Solution
v = 200 2 sin ωt
 ( ) ( ) (
i = 2 20 sin ωt − 45o + 10 sin 2ωt + 60o + 10 sin 3ωt + 60o )
The presence of the nonlinearity causes frequency components of current (i.e. the
second and third harmonic terms) that are not present in the applied voltage.

The rms voltage and current at the supply are:


~
V = 200 V
~2
I = 20 2 + 10 2 + 10 2
= 6102 A2
78 HarmonicAnalysis PQR
The apparent voltamperes at the input is therefore given by
~ 2~ 2
S = V I = 200 2  6  10 2 = 24  10 6 (VA )2
2

In this example only the fundamental frequency components are common to


both voltage and current. Therefore, the real power P and the apparent
power Q are
~~
P = V I1 cos ψ1
ψ1 = displacement angle between the fundamental of
the voltage and the fundamental of the current
= 200  20 cos 45o
4000
= W
2
~~
Q = V I1 sin ψ1
= 200  20 sin 45o
4000
= VA
2
79 HarmonicAnalysis PQR
~
D2 = V 2 (~I − ~I )
2
1
2

~
= V2 (~I − ~I )
2 3
2

= 200 (10 + 10 ) = 8  10
2 2 2 6
(VA )2
~ ~
P 2 + Q2 + D2 = V 2 I 2
~~ ~
P V I1 cos ψ1  I1 
PF = power factor = = ~~ =  (cos ψ1 )
S VI  I
1
Displacement factor = cos ψ1 = = 0.707
2
I 20
Distortion factor = 1 = = 0.817
I 600
Therefore, the power factor is
1 2
PF = = 0.577
2 6
80 HarmonicAnalysis PQR
EXAMPLE 2
NONSINUSOIDAL VOLTAGE-RL LOAD

 (
A periodic, sinusoidal voltage given by v = 2 200 sin ωt + 200 sin 5ωt + 30o )
is applied to a series, linear, resistance-inductance load of resistance 4Ω and
fundamental frequency reactance 10Ω.
Calculate the degree of power factor improvement realizable by capacitance
Compensation when f1 = 50 HZ.

~
Solution. The rms terminal voltage V is given by

= 2002 + 2002
Therefore
~
V = 283V

Z1 = 4 + j10
Z1 = 10.8

1 = tan −1 (10 / 4) = 68.2o


81 HarmonicAnalysis PQR
 5 = 51 = 50
Z5 = 4 + j50
Z5 = 50
 5 = tan −1 (50 / 4) = 85.4o
The instantaneous load current is given by

i = 2
 200
(
sin t − 68.2o + )
200
( )
sin 5t + 30o − 85.4o 
 10.8 50 
~
The rms load current I is therefore given by

 ~ 2  ~ 2
~ 2 ~ 2 ~ 2  V1   V5 
I = I1 + I5 =   + 
 Z1   Z5 
= 18.522 + 42 = 359A 2

82 HarmonicAnalysis PQR
Apparent voltamperes S at the load terminals in the absence of capacitance is
therefore

S2 = V 2 I 2 = 28.72  106 (VA )


~ ~ 2

Average power P In this case is

n
~ ~ ~~ ~ ~
P =  Vn In cos  L = V1 I1 cos 1 + V2 I2 cos 2 + ...
1

= 200  18.52 cos 68.2o + 200  4  cos 85.4o


= 1440W

The power factor before compensation is therefore


P 1440
PF = = = 0.27
S 28.72  10 6

83 HarmonicAnalysis PQR
EXAMPLE 3
NONSINUSOIDAL VOLTAGE AND NONSINIMUSOIDAL CURRENT
A periodic, nonsinusoidal voltage with instantaneous value given by
 ( )
v = 2 200 sin ωt + 200 sin 2ωt - 30o is applied to a nonlinear impedance.
The resulting current has an instantaneous value given by
i = 2 20 sin (ωt − 45 ) + 10 sin (2ωt − 60 ) + 10 sin (3ωt + 60 )
L
o o o

Calculate the components SLR , SLX , SLD of the load apparent voltamperes
and compare thee with the classical values PL , Q L , D L respectively.

Solution.
 (
v = 2 200 sin ωt + 200 sin 2ωt - 30o )
iL = 2 20 sin (ωt − 45 ) + 10 sin (2ωt − 60 ) + 10 sin (3ωt + 60 )
o o o

Note that the presence of the load nonlinearity causes a frequency component
of load current (I.e. the third harmonic term) that is not present in the supply
voltage.

84 HarmonicAnalysis PQR
The rms voltage and current at the supply are given by
~
V 2 = 200 2 + 200 2 = 8  10 4 V 2
~2
IL = 202 + 102 + 102 = 6 102 A 2
~ and ~
The load apparent voltamperes SL therefore has a value defined in terms V IL
S2L = V 2 IL2 = 48 106 (VA )
~ ~ 2

Instantaneous expressions of the hypothetical currents i R , i X , i D are given by


i R = 2 20 cos 45o sin t + 10 cos 300 sin 2t − 30o ( )
~
( 2
) (
 ILR2 = 20 cos 45o + 10 cos 30o )
2
=
11
4
102 A 2


i X = − 2 20 sin 45o cos ωt + 10 sin 30 0 cos 2ωt − 30 o ( )
~2
 ILX ( 2
) (
= 20 sin 45o + 10 sin 30o ) 2 9
= 102 A 2
4
iD = 2 10 sin (3t + 60 ) o

~2
 ILD = 102 A 2

85 HarmonicAnalysis PQR
Note that current components i R , i X contain only those harmonic terms which
are common to both voltage and current. These are therefore consistent with the
n1 terms.
~ ~ ~
The rms load current components ILR , ILX , ILD are found, as expected to sum
~
to the total rms load current IL
~2 ~2 ~2  11 9  ~
ILD + ILR + ILD = 102 1 + +  = 6 102 = IL2
 4 4
Components SLR , SLX , SLD of the apparent voltamperes can now be obtained

= V ILR = 10  8 104 = 22 106 (VA )


2 ~ 2 ~ 2 11 2 2
S LR
4

= V ILX = 10  8 104 = 18 106 (VA )


2 ~ 2~ 2 9 2 2
S LX
4

= 102  8 104 = 8 106 (VA )


~ ~2
S2LD = V 2 ILD
2

86 HarmonicAnalysis PQR
The component voltamperes are seen to sum to the total apparent voltamperes

S2LR + S2LX + S2LD = 10 6 (22 + 18 + 8)

= 48  10 6 (VA )2
= S2L
Components PL , Q L , D L of SL are found as follows:
2
 n
~ ~ 
PL =   Vn1 In1 cos ψ n1 
2 
 1 
( o
= 200  20  cos 45 + 200 10  cos 30 )
o 2

2
(
= 100 20 2 + 10 3 )
2

= 106 2 2 + ( 3 )2
( )
= 106 8 + 3 + 4 6 = 20.8 106  S2LR

87 HarmonicAnalysis PQR
2
 n
~ ~ 
Q L =   Vn1 In1 sin ψ n1 
2 
 1 
(
= 200  20  sin 45o + 200 10  sin 30o )2

( )
= 106 2 2 + 1 = 14.6 106  S2LX

D 2L = S2L − PL2 − Q 2L

= (48 − 20.8 − 14.6 )106 = 12.6  106 (VA )2  S2LD


From the possible compensation viewpoint it is interesting to note that SLX
and Q L differ by significant amount.
SLX could be defined as “that component of the load apparent voltamperes that
Is obtained by the combination of supply voltage harmonics with quadrature
Components of corresponding frequency load current harmonics”.

88 HarmonicAnalysis PQR
Similarly the definition of active voltamperes SLR could be given by “that
component of the load apparent voltamperes that is obtained by the combination
of supply voltage harmonics with in-phase components of corresponding
frequency load current harmonics”.

Both SLR and SLX are entirely fictitious and non-physical. The active

voltamperes SLR Is not to be compares in importance with the average power


PL which is a real physical property of the circuit. Term SLR Is merely the
analytical complement of term SLX

Term SLX the energy-storage reactive voltamperes, is that component

of the load apparent voltamperes that can be entirely compensated (for sinusoidal
supply voltage) or minimized (for nonsinusoidal supply voltage) by energy-storage

methods.

89 HarmonicAnalysis PQR
Voltage and current profiles in a
commercial building

90 HarmonicAnalysis PQR
HARMONIC STANDARDS
⚫ International Electrotechnical Commission (IEC) European
Standards.

- EN 61000-3-2 Harmonic Emissions standards were first published


as IEC 55-2 1982 and applied only to household appliances. It was
revised and reissued in 1987 and 1995 with the applicability
expanded to include all equipment with input current  16A per
phase. However, until January 1st, 2001 a transition period is in
effect for all equipment not covered by the standard prior to 1987.
- The objective of EN 61000-3-2 (harmonics) is to test the equipment
under the conditions that will produce the maximum harmonic
amplitudes under normal operating conditions for each harmonic
component. To establish limits for similar types of harmonics current
distortion, equipment under test must be categorized in one of the
following four classes.

91 HarmonicAnalysis PQR
CLASS-A: Balanced three-phase equipment and all other equipment
except that stated in one of the remaining three classes.
CLASS-B: Portable electrical tools, which are hand held during normal
operation and used for a short time only (few minutes)
CLASS-C: Lighting equipment including dimming devices.
CLASS-D: Equipment having an input current with special wave shape
( e.g.equipment with off-line capacitor-rectifier AC input
circuitry and switch Mode power Supplies) and an active
input power 600W.

- Additional harmonic current testing, measurement techniques and


instrumentation guidelines for these standards are covered in IEC
1000-4-7.

92 HarmonicAnalysis PQR
• IEEE 519-1992 United States Standards on harmonic limits

- IEEE limits service entrance harmonics.


- The IEEE standard 519-1992 limits the level of harmonics at the
customer service entrance or Point of Common Coupling (PCC).
- With this approach the costumer’s current distortion is limited based
on relative size of the load and the power supplier’s voltage
distortion based on the voltage level.

IEEE 519 and IEC 1000-3-2 apply different philosophies, which


effectively limit harmonics at different locations. IEEE 519 limits
harmonics primarily at the service entrance while IEC 1000-3-2 is
applied at the terminals of end-user equipment. Therefore, IEC limits
will tend to reduce harmonic-related losses in an industrial plant
wiring, while IEEE harmonic limits are designed to prevent
interactions between neighbors and the power system.

93 HarmonicAnalysis PQR
POWER QUALITY STANDARDS –
IEEE 519-1992 STANDARDS
TABLE I
CURRENT DISTORTION LIMITS FOR GENERAL DISTRIBUTION SYSTEMS
(120-69000 V)
Isc/IL <11 11<h<17 17<h<23 23<h<35 35<h TDD
<20* 4.0 2.0 1.5 0.6 0.3 5.0
20<50 7.0 3.5 2.5 1.0 0.5 8.0
50<100 10.0 4.5 4.0 1.5 0.7 12.0
100<1,000 12.0 5.5 5.0 2.0 1.0 15.0
>1,000 15.0 7.0 6.0 2.5 1.4 20.0
Source: IEEE Standard 519-1992.
Note: Even harmonics are limited to 25 percent of the odd harmonic limits above.
Current distortions that result in a direct current offset; for example, half wave
converters are not allowed.
Table I is for 6-pulse rectifiers. For converters higher than 6 pulse, the limits for
characteristic harmonics are increased by a factor o f q/6 , where q is the pule number,
provided that the
amplitudes of noncharacteristic harmonics are less than 25 percent.
*All power generation equipment is limited to these values of current distortion, regardless of
actual ISC/IL.
Where ISC = Maximum short circuit at PCC.
And IL = Average Maximum demand load current (fundamental frequency
component at PCC).
94 HarmonicAnalysis PQR
TABLE II
LOW VOLTAGE SYSTEM CLASSIFICATION AND DISTORTION LIMITS
IEEE 519-1992 STANDARTS

Special General Dedicated


Applications System System
Notch Depth 10% 20% 50%

THD (Voltage) 3% 5% 10%

Notch Area 16,400 22,800 36,500


(AN)*

Source: IEEE Standard 519-1992.


Note: The value AN for another than 480Volt systems should be
multiplied by V/480 .
The notch depth, the total voltage distortion factor (THD) and
the notch area limits are specified for line to line voltage.
In the above table, special applications include hospitals and
airports. A dedicated system is exclusively dedicated to converter load.
*In volt-microseconds at rated voltage and current.

95 HarmonicAnalysis PQR
TABLE III
LIMITS OF THD%
IEEE 519-1992 STANDARDS

SYSTEM Special General Dedicated


Nominal Voltage Application Systems Systems
120-600V 3.0 5.0 8.0

69KV and below - 5.0 -

96 HarmonicAnalysis PQR
TABLE IV
PROPOSED IEC 555-2 CLASS D STANDARDS for power from 50 to 600W

Harmonic Relative limits Absolute Limits


Milliamps/Watt Amps
3 3.4 2.30
5 1.9 1.14
7 1.0 0.77
9 0.5 0.40
11 0.35 0.33
13 linear 0.15 (15/n)
extrapolation

97 HarmonicAnalysis PQR
METHODOLOGY FOR
COMPUTING DISTORTION
Step 1: Compute the individual current harmonic distortion at each
dedicated bus using different Software programs (i.e. SIMULINK,
SPICE, e.t.c.) or tables that provide the current distortion of
nonlinear loads.
Step 2: Compute the voltage and current harmonic content at the Point of
Common Coupling (PCC) which is located at the input of the
industrial power system.
- Each individual harmonic current at the PCC is the sum of
harmonic current contribution from each dedicated bus.
- The load current at PCC is the sum of the load current
contribution from each dedicated bus.
- The maximum demand load current at PCC can be found by
computing the load currents for each branch feeder and multiply
by a demand factor to obtain feeder demand. Then the sum of all
feeder demands is divided by a diversity factor to obtain the
maximum demand load current.

98 HarmonicAnalysis PQR
Step 3: Choose a base MVA and base KV for the system use the following
equations in order to compute individual and total current and
voltage harmonic distortions at PCC and any other point within the
power system.
3
Ib= Base current in Amps = MVA b  10 (24)
Amps
3kVb

Zs = System impedance = MVA b p.u.


(25)
MVA sc
MVAb= Base MVA, MVAsc= short circuit MVA at the point of interest

VH= Percent individual harmonic voltage distortion =

I
= h (h ) (Zs )  100 Volts (26)
Ib

99 HarmonicAnalysis PQR
 2
  2  2
  Vh  1 2   Ih 
  h = 2 
THD υ % = h = 2   100 THD i % =  100 (27)
V1 I1
h = harmonic order

Ih
IH = Percent individual harmonic distortion =  100 (28)
IL
Isc = Short Circuit current at the point under consideration.

IL = Estimated maximum demand load current

Isc MVA sc
S.C. Ratio = Short circuit Ratio = = (29)
I L MVA D

MVAD = Demand MVA

100 HarmonicAnalysis PQR


K Factor = Factor useful for transformers design and
specifically from transformers that feed
Adjustable Speed Drives
 2
 Ih 
=  (h ) 2
   (30)
h =1  IL 
ONCE THE SHORT CIRCUIT RATIO IS KNOWN, THE IEEE CURRENT
HARMONIC LIMITS CAN BE FOUND AS SPECIFIED IN TABLE I OF
THE IEEE 519-1992 POWER QUALITY STANDARDS

USING THE ABOVE EQUATIONS VALUES OF IDIVINDUAL AND


TOTAL VOLTAGE AND CURRENT HARMONIC DISTORTION CAN
BE COMPUTED AND COMPARED WITH THE IEEE LIMITS

101 HarmonicAnalysis PQR


Step 4: If the analysis is being performed for CSI-type drives then the area
of the voltage notch AN should also be computed.
- At this point an impedance diagram of the under analysis
industrial power system should be available.
- The Notch Area AN at the PCC can be calculated as follows.

AN = AN1 + AN2 + …………. V . microsec (31)

AN1 , AN2 , …… are the notch areas contribution of the different busses

Source inductance
A N1 = A NDR1
Source inductance + the sum of inductances from PCC to the drive

(32)

ANDR1 : Notch area at the input of the drive

102 HarmonicAnalysis PQR


Step 5: Determine preliminary filter design.

Step 6: Compute THDv and THDi magnitudes and impedance versus


frequency plots with filters added to the system, one at a time.
SIMULINK or PSPICE software programs can be used for final
adjustments.

Step 7: Analyze results and specify final filter design.

103 HarmonicAnalysis PQR


EXAMPLE OF A SYSTEM ONE LINE
DIAGRAM

104 HarmonicAnalysis PQR


System impedances diagram which can be used to
calculate its resonance using PSPICE or SIMULINK
programs

105 HarmonicAnalysis PQR


TYPES OF FILTERS
1) Parallel-passive filter for current-source nonlinear loads

• Harmonic Sinc
• Low Impedance
• Cheapest
• VA ratings = VT (Load Harmonic current + reactive current of the filter)

106 HarmonicAnalysis PQR


2) Series-passive filter for voltage-source nonlinear loads

• Harmonic dam
• High-impedance
• Cheapest
• VA ratings = Load current (Fundamental drop across filter + Load Harmonic Voltage)

107 HarmonicAnalysis PQR


3) Basic parallel-active filter for current source in nonlinear loads

108 HarmonicAnalysis PQR


4) Basic series-active filter for voltage-source in nonlinear loads

109 HarmonicAnalysis PQR


5) Parallel combination of parallel active and parallel passive

6) Series combination of series active and series passive

110 HarmonicAnalysis PQR


7) Hybrid of series active and parallel passive

8) Hybrid of parallel active and series passive

111 HarmonicAnalysis PQR


9) Series combination of parallel-passive and parallel-active

10) Parallel combination of series-passive and series-active

112 HarmonicAnalysis PQR


11) Combined system of series-active and parallel-active

12) Combined system of parallel-active and series-active

113 HarmonicAnalysis PQR


A SIMPLE EXAMPLE OF AN INDUSTRIAL
POWER DISTRIBUTION SYSTEM

114 HarmonicAnalysis PQR


HARMONIC LIMITS EVALUATION WHEN
POWER-FACTOR-CORRECTION CAPASITORS
ARE USED

- As it can be seen from the power distribution circuit the power-factor-


correction capacitor bank, which is connected on the 480 Volts bus, can
create a parallel resonance between the capacitors and the system
source inductance.
- The single phase equivalent circuit of the distribution system is shown
below.

Rtot Ltot IS If

C
VS Ih
AC Source Harmonic
Load

Z in
Using the above circuit the following equations hold:

115 HarmonicAnalysis PQR


2 R sys
kVLL   X 
R sys =  cos  tan −1  , R sys = (33)
MVA sc   R  2
α
2
kVLL  −1 X  Xsys
Xsys =  sin  tan   , Xsys = (34)
MVA sc   R  α 2

α = The turns ratio of the transformer at PCC

2
1000  kVLL (35)
R tr = R pu 
kVA tr

2
1000  kVLL (36)
X tr = X pu 
kVA tr

116 HarmonicAnalysis PQR


R tot = R sys + R tr (37)

X tot = Xsys + X tr (38)

2
1000  kVcap
Xc = (39)
kVAR cap

1
C= (40)
ωX c

1
Xc = (41)
ωC
X tot X tot
L tot = = (42)
ω 2 πf

117 HarmonicAnalysis PQR


The impedance Z looking into the system from the load, consists of the
in
parallel combination of source impedance R
tot + jX tot and the
capacitor impedance

Zin =
(R tot + jωL tot )  (− j / ωC)
1 (43)
R tot + jωL tot − j
ωC
1 1
ωo L tot = , fo = (44)
ωo C 2 πωo

The equation for Zin can be used to determine the equivalent system
impedance for different frequencies. The harmonic producing loads can
resonate (parallel resonance), the above equivalent circuit. Designating
the parallel resonant frequency by ωo (rad/sec) or f o (HZ) and equating
the inductive and capacitive reactances.

118 HarmonicAnalysis PQR


- Harmonic current components that are close to the parallel resonant frequency are amplified.
- Higher order harmonic currents at the PCC are reduced because the capacitors are low
impedance at these frequencies.
- The figure below shows the effect of adding capacitors on the 480 Volts bus for power factor
correction.

This figure shows that by adding some typical sizes of power factor correction capacitors will
result in the magnification of the 5th and 7th harmonic components, which in turns makes it
even more difficult to meet the IEEE 519-1992 harmonic current standards .
- Power factor correction capacitors should not be used without turning reactors in case the
adjustable speed drives are >10% of the plant load.
119 HarmonicAnalysis PQR
EXAMPLE
Let us examine an industrial plant with the following data:
- Medium voltage = 20KVLL
- Low voltage = 0.4 KVLL
- Utility three phase short circuit power = 250 MVA
- For asymmetrical current, the X ratio of system impedance = 2.4
R
The Transformer is rated:

1000 KVA, 20 KV-400 Y/230 V


Rpu = 1%, Xpu = 7%
- The system frequency is: fsys = 50 HZ.
- For power factor correction capacitors the following cases are examined:
a. 200 KVAR
b. 400 KVAR
c. 600 KVAR
d. 800 KVAR
120 HarmonicAnalysis PQR
The parallel resonant frequencies for every case of
power factor correction is calculated as follows:

R sys =
20 2
250
 
 cos tan −1(2.4 ) = 0.6154 Ω

 sin tan (2.4) = 1.4769 Ω


2
20 −1
Xsys =
250
20
α= = 50
0.4
R sys = 0.6154 50 2 = 0.000246 Ω

Xsys = 1.4769 50 2 = 0.000591Ω


1000  (0.4 )2
R tr = 0.01  = 0.00160 Ω
1000
1000  (0.4 )2
X tr = 0.07  = 0.0112 Ω
1000
121 HarmonicAnalysis PQR
R tot = 0.000246 + 0.0016 = 0.001846 Ω

X tot = 0.000591 + 0.0112 = 0.011791Ω


0.011791
L tot = = 37.55 10 − 6 H
2  π  50
Case a:
1000  (0.4 )2
Xc = = 0.8 Ω
200
1
C = = 3.98 10 −3 F
2π  50  0.8
1
fo = = 412 .18HZ
2 π  37.50  10 − 6  3.98  10 −3
For 200 KVAR, the harmonic order at which parallel resonance occurs is:

h = 412 .18 50 = 8.24

122 HarmonicAnalysis PQR


Case b:
1000  (0.4 )2
Xc = = 0.4 Ω
400
C = 7.96 10 −3 F
f o = 291 .45HZ
h = 5.83
Case c:

1000  (0.4 )2
Xc = = 0.267 Ω
600
C = 11.94 10−3 F
f o = 237 .97 HZ
h = 4.76
123 HarmonicAnalysis PQR
Case d:

1000  (0.4 )2
Xc = = 0.2 Ω
800
C = 15.92 10−3 F

f o = 206 .08HZ

h = 4.12

It is clear for the above system that in the 600 KVAR case, there
exists a parallel resonant frequency f o close to the 5th harmonic.

124 HarmonicAnalysis PQR


POWER FACTOR CORRECTION AND
HARMONIC TREATMENT
USING TUNED FILTERS

- Basic configuration of a tuned 3-φ capacitor bank for power factor


correction and harmonic treatment.

⚫ Simple and cheap filter


⚫ Prevents of current harmonic magnification

125 HarmonicAnalysis PQR


- IN ORDER TO AVOID HARMONIC MAGNIFICATION WE CHOOSE A
TUNED FREQUENCY < FITH HARMONIC (i.e 4.7)
- The frequency characteristic of the tuned filter at 4.7 is shown below

As it can be seen from the above figure significant reduction of the 5th
harmonic is achieved. Moreover, there is some reduction for all the other
harmonic components.
126 HarmonicAnalysis PQR
The single phase equivalent circuit of the power distribution system
with the tuned filter is shown below

Using the above circuit the following equations hold:

127 HarmonicAnalysis PQR


1
f os = = Resonant frequency of the series filter (45)
1
2 π(Lf  C ) 2
Lf =
1
=
2 πf  X c
=
f 1000 kVcap 2 ( ) (46)
C  (2 πf os )2
(2πf os ) 2π  (f os )2  kVAR cap
2

The new parallel combination is having resonant frequency when


1
ωo L tot + ωo L f − =0 (parallel resonance)
ωo C
1
fo = = resonance frequency of the
1
2π(L tot + Lf )  C 2 equivalent distribution circuit
(47)

Also
R tot + jωL tot
If = I h 
R tot + jωL tot + ωL f − 1 ωC
(48)

128 HarmonicAnalysis PQR


j (ωLf − 1 / ωC )
Is = I h  (49)
R tot + j ωL tot + ωLf − 1 ωC

Vh = Is  (R tot + jωL tot ) (50)

(R tot + jωL tot )   jωLf


1 
−j
Zin =  ω C =
1
R tot + jωL tot + jωLf − j
ωC

(R tot + jωL tot )   jωL f 1 


−j
=  ωC  (51)
 1 
R tot + j  ωL tot + ωL f − 
 ω C 

129 HarmonicAnalysis PQR


As it was discussed before Selecting f o = 235 HZ or 4.7 th harmonic

With KVcap= 0.4 , KVARcap= 600

50 1000  (0.4)2
Lf = = 68.45 10 −6 H = 38.45μH
2  π  (235 )2  600
The new parallel combination is having resonant frequency:
1
fo =
2 π (L tot + Lf )  C
with L tot = 37.55 10 −6 H we have
Lf = 38.45 10−6 H
C = 11.94 10−3 F
1
fo = = 167 .16 HZ
2  π  76 10 − 6 11.94 10 −3
h = 167.16 / 50 = 3.43 (without Lf was 4.76)

130 HarmonicAnalysis PQR


The following table shows the variation of Parallel resonant frequency
With and without resonant inductor

Parallel Resonant f0
KVAR C(mF) Without Lf With Lf
200 3.98 8.80 115.3μH 4.08

400 7.96 6.22 57.7μH 3.66


600 11.94 5.08 38.45μH 3.43
800 15.92 4.40 29.5μH 3.08

131 HarmonicAnalysis PQR


SIMULATED RESULTS USING
MATLAB/SIMULINK
T1
i
+
-
C motor . +
v
-
380kw/490rpm V

Bus Bar (horiz)2 compens

T
Ground (input)

+ Gnd
v
-
200m cable 4x240 50m cable 4x1 V1
Ground (output)1
Voltage Measurement3
+
v
-

+
Current Measurement4

-
i
voltage

Series RLC Branch


Scope3
Source

Scope1
i
-

itot
+

Scope2 +
i
Scope4
-

Source1 Current Measurement6 Scope


Bus Bar (horiz)3

chock2%5
chock2%3 chock2%1
AC Voltage Source
Ground (input)8
Ground (input)5 Ground (input)4

Ground (output)
Current Measurement5
i i
+ +
- -
Current Measurement3

Bus Bar (horiz)7 Bus Bar (horiz)5

AC Current Source7 AC Current Source4

Series RLC Branch3 AC Current Source5 Series RLC Branch2


AC Current Source8
AC Current Source6 AC Current Source3

Bus Bar (horiz)6 Bus Bar (horiz)4

Ground (input)3 Ground (input)2


+

Current Measurement1
-
i

Bus Bar (horiz)1

AC Current Source1

AC Current Source2 Series RLC Branch1

AC Current Source

Bus Bar (horiz)

Ground (input)1

132 HarmonicAnalysis PQR


SIMULINK RESULTS

133 HarmonicAnalysis PQR


SIMULINK RESULTS

134 HarmonicAnalysis PQR


ACTIVE FILTERING

Parallel type Series type

135 HarmonicAnalysis PQR


RESULTS OF ACTIVE FILTERING
2500
30
1500 25

500 20
I

[% I1]
[A] 15
-500
10
-1500
5

-2500 0
0 5 10 15 20 25 30 35 40 2 5 8 11 14 17 20 23
Time [ms] Harmonics

Input current of a 6-pulse Rectifier driving a DC machine without any input filtering
5000
35%
30%
2500
I Dynacomp [A]

25%
20%

[%I1]
0
15%

-2500 10%
5%
-5000 0%
0 10 20 30 40 2 5 8 11 14 17 20 23
Time [ms] Harmonics
Input current with Active Filtering

136 HarmonicAnalysis PQR


1000 14
12
500
10
U [V]

[% U1]
0
6
-500 4
2
-1000 0
0 5 10 15 20 25 30 35 40 2 5 8 11 14 17 20 23
Time [ms] Harmonics
Typical 6-pulse drive voltage waveform
1000 14
12
500
10
U [V]

[% U]
0
6
-500 4
2
-1000 0
0 5 10 15 20 25 30 35 40 2 5 8 11 14 17 20 23
Time [ms] Harmonics

Voltage source improvement with active filtering

137 HarmonicAnalysis PQR


SHUNT ACTIVE FILTERS
By inserting a parallel active filter in a non-linear load location we can
inject a harmonic current component with the same amplitude as that of
the load in to the AC system.

LF

Equivalent circuit
138 HarmonicAnalysis PQR
ADVANTAGES OF THE SHUNT OR PARALLEL
ACTIVE FILTER

⚫ Low implementation cost.


⚫ Do not create displacement power factor problems and utility loading.
⚫ Supply inductance LS, does not affect the harmonic compensation of
parallel active filter system.
⚫ Simple control circuit.
⚫ Can damp harmonic propagation in a distribution feeder or between
two distribution feeders.
⚫ Easy to connect in parallel a number of active filter modules in order to
achieve higher power requirements.
⚫ Easy protection and inexpensive isolation switchgear.
⚫ Easy to be installed.
⚫ Provides immunity from ambient harmonic loads.

139 HarmonicAnalysis PQR


WAVEFORMS OF THE PARALLEL ACTIVE
FILTER

Source voltage

Load current

Source current

A. F. output current

140 HarmonicAnalysis PQR


PARALLEL ACTIVE FILTER EQUATIONS
IC = GI L (52)

G1 = 0 G h =1
ZL VS
IS =  I LH + (53)
Z Z
ZS + L ZS + L
1− G 1− G
ZL
1− G 1 VS
IL =  I LH +  (54)
ZL 1 − G Z + ZL
ZS + S
1− G 1− G
ZL
If  ZS h (55)
1− G h
Then the above equations become

I C = I Lh (56)
VSh
ISh  (1 − G )I LHh + (1 − G ) 0 (57)
ZL
141 HarmonicAnalysis PQR
VSh
I Lh = I LHh + (58)
ZL
Equation (55) is the required condition for the parallel A.F. to cancel
the load harmonic current. Only G can be predesign by the A.F. while
Zs and ZL are determined by the system.
For pure current source type of harmonic source ZL  ZS
and consequently equations (53) and (55) become
IS
= (1 − G )
(59)
I LH

1 − G h  1 (60)

ZS = Source impedance
I LH = Is the equivalent harmonic current source

Z L = Equivalent load impedance

G = equivalent transfer function of the active filter


Equation (59) shows that the compensation characteristics of the A.F. are not
influenced by the source impedance, Zs. This is a major advantage of the A.F.
with respect to the passive ones.
142 HarmonicAnalysis PQR
VdC

• The DC bus nominal voltage, VdC, must be greater than or equal to line voltage
peak in order to actively control i C .
• The selection of the interface inductance of the active filter is based on the
compromise of keeping the output current ripple of the inverter low and the same
time to be able to track the desired source current.
• The required capacitor value is dictated by the maximum acceptable voltage
ripple. A good initial guess of C is: 
2
t VdC − Vφn

max i Cdt
0 Also LF  3
diφL
C
 ΔvCmax max
V dt
nφ = peak line-neutral voltage

CdV = DC voltage of the DC bus of the inverter


Lφi = Line phase current
xamC vΔ = maximum acceptable voltage ripple,

C i = Phase current of the inverter

143 HarmonicAnalysis PQR


P-Q THEORY

For identifying the harmonic currents in general the method of computing


instantaneous active and reactive power is used.
Transformation of the three-phase voltages v u , v v and v w and the three-
phase load currents i Lv , i Lu and i Lw into α-β orthogonal coordinate.

 vu 
vα  2 1 − 1/ 2 − 1/ 2   
v  =    vv 
 β 3 0 3/2 − 3 / 2
 v w 

i 
i Lα  2 1 − 1/ 2 − 1/ 2   Lu 
i  =    i Lv 
 Lβ  3 0 3/2 − 3 / 2
i Lw 

144 HarmonicAnalysis PQR


Then according to p - q theory, the instantaneous real power p L and the
instantaneous imaginary (reactive) power q L are calculated.

p L   v α vβ  i Lα 
q  =  − v v α  i Lβ 
 L  β

where


p L = pL + p L + ~
pL = DC + low frequency comp. + high freq. comp.


q L = qL + q L + ~
qL = DC + low frequency comp. + high freq. comp.

145 HarmonicAnalysis PQR


~
The conventional active power is corresponding to p L, the conventional reactive
~
power to q L and the negative sequence to the 2 f components of p L and q L .

The commands of the three-phase compensating currents injected by the


shunt active conditioner, i Cu , iCv and iCware given by:

 iCu   1 0  −1
   2    vα v β   p 
 i Cv  = 3  − 1/ 2 3/2  
- vβ v α  q 
i  − 1 / 2 − 3 / 2 
 Cw 

p = Instantaneous real power command

q = Instantaneous reactive power command

146 HarmonicAnalysis PQR


Substituting

p = ~
pL 

 ~   Current Harmonics compensation is achieved
q = qL 

p = ~
pL 

  ~   Current Harmonics and low frequency variation
q = q L + qL 
 Components of reactive power compensation


p = p L + ~
pL 
 Current Harmonics and low frequency variation
  
q = q L + ~
Components of active and reactive power compensation
qL 

147 HarmonicAnalysis PQR


HARMONIC DETECTION METHODS

i) Load current detection iAF= iLh


It is suitable for shunt active filters which are installed near
one or more non-linear loads.

ii) Supply current detection iAF= KS iSh


Is the most basic harmonic detection method for series
active filters acting as a voltage source vAF.

iii) Voltage detection


It is suitable for shunt active filters which are used as
Unified Power Quality Conditioners. This type of Active
Filter is installed in primary power distribution systems. The
Unified Power Quality Conditioner consists of a series and a
shunt active filter.

148 HarmonicAnalysis PQR


SHUNT ACTIVE FILTER CONTROL

a) Shunt active filter control based on voltage detection

149 HarmonicAnalysis PQR


Using this technique the three-phase voltages, which are detected at the point of
installation, are transformed to v d and v q on the dq coordinates. Then two first
order high-pass filters of 5HZ in order to extract the ac components v d and ~
~ vq
from v d and v q . Next the ac components are applied to the inverse dq
transformation circuit, so that the control circuit to provide the three-phase
harmonic voltages at the point of installation. Finally, amplifying each harmonic
voltage by a gain Kv produces each phase current reference.

iAF = K V  v h

The active filter behaves like a resistor 1/KV ohms to the external circuit for
harmonic frequencies without altering the fundamental components. 
The current control circuit compares the reference current i AF with the actual
current of the active filter i AF and amplifies the error by a gain KI . Each phase
voltage detected at the point of installation, v is added to each magnified error
signal, thus constituting a feed forward compensation in order to improve current
controllability. As a result, the current controller yields three-phase voltage

references. Then, each reference voltage v i is compared with a high frequency
triangular waveform to generate the gate signals for the power semiconductor
devices.

150 HarmonicAnalysis PQR


b) Reference current calculation scheme using source currents (is),
load currents (iL) and voltages at the point of installation (vS).

151 HarmonicAnalysis PQR


3-φ HYBRID ACTIVE-PASSIVE FILTER

Compensation of current harmonics and displacement power


factor can be achieved simultaneously.

152 HarmonicAnalysis PQR


In the current harmonic compensation mode, the active filter improves the
filtering characteristic of the passive filter by imposing a voltage harmonic
waveform at its terminals with an amplitude
VCh = KI Sh

153 HarmonicAnalysis PQR


If the AC mains voltage is pure sinusoidal, then

 ZF 
ISh
=
ZF   Lh K + Z + Z 
 I
h = 2 F S
I Lh K + Z F + ZS THD i =
IS1

• THDi decreases if K increases.


• The larger the voltage harmonics generated by the active filter a better filter
compensation is obtained.
• A high value of the quality factor defines a large band width of the passive
filter, improving the compensation characteristics of the hybrid topology.
• A low value of the quality factor and/or a large value in the tuned factor
increases the required voltage generated by the active filter necessary to
keep the same compensation effectiveness, which increases the active
filter rated power.

154 HarmonicAnalysis PQR


Displacement power factor correction is achieved by controlling the voltage
drop across the passive filter capacitor.

VC = βVT

Displacement power factor control can be achieved since at fundamental


frequency the passive filter equivalent impedance is capacitive.

155 HarmonicAnalysis PQR


HYBRID ACTIVE-PASSIVE FILTER

Single-phase equivalent circuit Single-phase equivalent circuit


for 5th Harmonic

156 HarmonicAnalysis PQR


This active filter detects the 5th harmonic current component that flows
into the passive filter and amplifies it by a gain K in order to determine its
voltage reference which is given by

vAF = K  i F5
As a result, the active filter acts as a pure resistor of K ohms for the 5th
harmonic voltage and current. The impedance of the hybrid filter at the 5th
harmonic frequency, Z5 is given by

1
Z5 = j5ωL F + + rf + K
j5ωC F

K0 The active filter presents a negative resistance to the external


Circuit, thus improving the Q of the filter.

1
K = − rF VBUS5 = 0 , IS5 = VS5
j5ωL T

157 HarmonicAnalysis PQR


CONTROL CIRCUIT

The control circuit consists of two parts; a circuit for extracting the
5th current harmonic component from the passive filter iF and a circuit
that adjusts automatically the gain K. The reference voltage for the
active filter 
v AF = K  i F5

HARMONIC-EXTRACTING CIRCUIT
The extracting circuit detects the three-phase currents that flow into
the passive filter using the AC current transformers and then the α-β
coordinates are transformed to those on the d-g coordinates by
using a unit vector (cos5ωt, sin5ωt) with a rotating frequency of
five times as high as the line frequency.

158 HarmonicAnalysis PQR


SERIES ACTIVE FILTERS

By inserting a series Active Filter between the AC source and the load
where the harmonic source is existing we can force the source current to
become sinusoidal. The technique is based on a principle of harmonic
isolation by controlling the output voltage of the series active filter.

Equivalent Circuit

159 HarmonicAnalysis PQR


- The series active filter exhibits high impedance to harmonic current
and consequently blocks harmonic current flow from the load to the
source.

VC = Output vol tage of the A.F. = KGI S (61)

ZL I L VS
IS = + (62)
ZS + ZL + KG ZS + ZL + KG

G = Equivalent transfer function of the detection circuit of


harmonic current, including delay time of the control
circuit.

G1 = 0 , G h =1 (63)

160 HarmonicAnalysis PQR


K = A gain in pu ohms

The voltage distortion of the input AC source VSh is much smaller


than the current distortion.

If K  Z L h and K  ZS + ZL h (64)

Then

VC = ZL I Lh + VSh (65)

IS  0 (66)

161 HarmonicAnalysis PQR


HYBRID SERIES AND SHUNT
ACTIVE FILTER

At the Point of Common Coupling provides:

• Harmonic current isolation between the sub transmission and the


distribution system (shunt A.F)
• Voltage regulation (series A.F)
• Voltage flicker/imbalance compensation (series A.F)

162 HarmonicAnalysis PQR


SELECTION OF AF’ S FOR SPECIFIC APPLICATION CONSIDERATIONS
AF Configuration with higher number of * is more preferred
Compensation for Active Filters
Specific Application
Active Active Hybrid of Hybrid of
Series Shunt Active Series Active Shunt
and Passive and Active
Shunt Series
Current Harmonics ** *** *
Reactive Power *** ** *
Load Balancing *
Neutral Current ** *
Voltage Harmonics *** ** *
Voltage Regulation *** * ** *
Voltage Balancing *** ** *
Voltage Flicker ** *** *
Voltage Sag&Dips *** * ** *

163 HarmonicAnalysis PQR


CONCLUSIONS
⚫ Solid State Power Control results in harmonic pollution above the tolerable limits.
⚫ Harmonic Pollution increases industrial plant downtimes and power losses.
⚫ Harmonic measurements should be made in industrial power systems in order (a) aid
in the design of capacitor or filter banks, (b) verify the design and installation of
capacitor or filter banks, (c) verify compliance with utility harmonic distortion
requirements, and (d) investigate suspected harmonic problems.
⚫ Computer software programs such as PSPICE and SIMULINK can be used in order to
obtain the harmonic behavior of an industrial power plant.
⚫ The series LC passive filter with resonance frequency at 4.7 is the most popular filter.
⚫ The disadvantages of the the tuned LC filter is its dynamic response because it cannot
predict the load requirements.
⚫ The most popular Active Filter is the parallel or shunt type.
⚫ Active Filter technology is slowly used in industrial plants with passive filters as a
hybrid filter. These filters can be used locally at the inputs of different nonlinear loads.
⚫ Active Filter Technology is well developed and many manufactures are fabricating
Active filters with large capacities.
⚫ A large number of Active Filters configurations are available to compensate harmonic
current, reactive power, neutral current, unbalance current, and harmonics.
⚫ The active filters can predict the load requirements and consequently they exhibit very
good dynamic response.
⚫ LC tuned filters can be used at PCC and the same time active filters can be used
locally at the input of nonlinear loads.

164 HarmonicAnalysis PQR


HarmonicAnalysis
NEXT

LECTURE FOUR

RELIABILTY
166 HarmonicAnalysis PQR

You might also like