Professional Documents
Culture Documents
19
Phase Sequences of Harmonics and
Interharmonics
20
Parallel Resonance
• Occurs when the system inductance reactance (X ) and
capacitance reactance (Xc) are equal at some
frequency(5th, 7th , etc.).
• Harmonic currents that flow between capacitors and the
system inductance are significantly amplified (up to 10
-15 times).
• Can lead to capacitor fuse blowing or failure and or
transformer overheating.
Series Resonance
Series Resonance
•A series combination of inductance and capacitance.
•Creates low impedance for harmonic currents at the
natural frequency.
•Results in high harmonic currents through the capacitors.
•Can result in a high voltage distortion level
IEEE Standard 519: Overview
• IEEE Standard 519 was created to establish limits for harmonic
distortion and provide direction on dealing with harmonics.
• Defines limits for harmonic currents and voltages.
• Limits are defined at the Point of Common Coupling (PCC)
• Titled “Recommended Practice and Requirements for
Harmonic Control in Electric Power Systems".
• Current standard was released in 2014.
IEEE Standard 519: Definitions
• Point of Common Coupling (PCC); It is defined as the
point in the power system closest to the user where the
system owner or operator could offer service to another
user. Frequently for service to industrial users (i.e.
manufacturing plants) via a dedicated service
transformer, the PCC is at the HV side of the
transformer. For commercial users (office parks,
shopping malls, etc.) supplied through a common service
transformer, the PCC is commonly at the LV side of the
transformer.
• The PCC is basically recognized as the point where any
harmonics could migrate onto the utility system and
cause problems for other customers.
Point of common coupling Examples
More on Point of Common Coupling
• Intention is to prevent high level of harmonics (such as
that generated by non-linear loads) generated by one
customer from causing distortion at other customers on
the power grid.
• In considering the primary side of a power transformer
(that supplies only one customer), the transformer’s
impedance will decrease the short circuit ratio.
• This results in an increase in the harmonic current limits.
• The voltage distortion will be higher at the secondary of
the transformer.
Short circuit ratio
Short circuit ratio (SCR) is often used as an index of the system strength.
IEEE Standard 519: Definitions
Short Circuit Ratio (ISC/IL): The ratio of the short circuit
current (ISC) available at the point of common coupling
(PCC) to the maximum fundamental load current (IL).
Maximum Load Current (IL): ls recommended to be the
average current of the maximum demand for the preceding
12 months. (Unfortunately, this value is inherently
ambiguous making it difficult to derive at the design stage
when measured load is not available).
Isc/IL Ratio – utility power load
• High Isc
• Minimal Voltage Distortion
Harmonic Indices
• Two important indices, THD and TDD, are used to
describe the effects of harmonics on power system
components and communication systems.
• These indices are used to measure the deviation of a
periodic waveform containing harmonics from a
perfect sine wave.
• For a perfect sine wave, the deviation (or the
distortion) is zero.
IEEE
IEEE standard specifies the allowable limits for voltage
and current distortion at various bus and system voltages.
These are given in Tables 1 and 2.The important
terminology used in this standard are explained below:
•The Point of Common Coupling (PCC) is the location of
the harmonic voltage and current distortion to be
calculated or measured.
•Total Harmonic Distortion (THD) is the total harmonic
voltage distortion calculated or measured at PCC.
•Total Demand Distortion (TDD) is the percentage of total
harmonic current distortion calculated or measured at PCC.
TDD and THD
Total Demand Distortion (TDD)
The ratio of the root-mean- square of the harmonic current
to the root-mean-square value of the rated or maximum
demand fundamental current, expressed as a percent.
39
Preventive Method (Harmonic Standards)
40
Preventive Method (Harmonic Standards)
41
Preventive Method (Harmonic Standards)
IEC 61000-3-6:Indicative values of planning levels for harmonic voltage
(in percent of the nominal voltage) in MV, HV and EHV power systems
Odd harmonics non Odd harmonics multiple
Even harmonics
multiple of 3 of 3
Order Harmonic voltage Order Harmonic Order Harmonic
h % h voltage % h voltage %
MV HV-EHV MV HV-EHV MV HV-EHV
5 5 2 3 4 2 2 1,6 1,5
7 4 2 9 1,2 1 4 1 1
11 3 1,5 15 0,3 0,3 6 0,5 0,5
13 2,5 1,5 21 0,2 0,2 8 0,4 0,4
17 1,6 1 >21 0,2 0,2 10 0,4 0,4
19 1,2 1 12 0,2 0,2
23 1,2 0,7 >12 0,2 0,2
25 1,2 0,7
>25 0,2 + 0,2 +
0,5(h/25) 0,5(h/25
)
NOTE – Total harmonic distortion (THD): 6,5% in MV networks 3% in HV networks.
42
HARMONICS AND POWER FACTOR
• Power Factor Must include Distortion Factor (DF) to account
for harmonics.
• DF decreases as harmonics increases.
• True Power Factor may be lower when effects of harmonics
are considered.
HARMONICS AND POWER FACTOR
Harmonics in Rectifiers
The characteristic current harmonics produced are determined
by the pulse number:
Ih = l/ h
h = np±1
lh = magnitude of harmonic current
h = harmonic number
n = any positive integer
p = pulse number in the rectifier scheme
6-Pulse Rectifier
So, for a 6-pulse rectifier (p = 6), h = 5, 7, 11, 13, 17,
19, etc. (5th, 7th, 11th, 13th, 17th, 19th harmonics)
18-Pulse Rectifier
An 18-pulse rectifier would yield harmonic currents at the
17th, 19th, 35th, 37th, etc. harmonics)
Harmonics in Rectifiers
• 12-pulse, or better yet, 18-pulse drives are preferred over
6-pulse drives due to the reduction of harmonics.
• As a rule of thumb, the magnitudes of the harmonic
currents will be the fundamental current divided by the
harmonic number (i .e. the magnitude of the 5th
harmonic would be 1/5 of the fundamental current.
• Variable frequency drives (VFDs) also produce harmonic
currents at the output of the inverter which are seen by
the motor.
Harmonics Mitigation
• With the increasing demand of non-linear type of
equipment and loads, mitigation of harmonics becomes
more and more important.
• If harmonics study or testing indicates excessive
harmonic levels or a potentially harmful resonance
condition, mitigation must be considered.
• Depending on the situation, there are typically several
mitigation methods to choose from.
Harmonics Mitigation Methods
Harmonics Mitigation Methods
•Limit the amount of non-linear loading.
•Drive Isolation Transformers
•Line Reactors
•Replace 6-pulse drives with higher pulse drives, such as 12-
pulse
•or 18-pulse.
•Harmonic Trap Filters
- Active Filters
- Passive Filters
•Resonance problem indicates removal or relocation of power
factor correction capacitors (PFCCs).
Harmonics Mitigation - Harmonic Filters
• Generally, consist of one or more tuned LC legs which shunt
specifies harmonic currents away from the power system.
• Added benefit of supplying leading kVARs and thus provide
power factor correction.
Active Filter Front End with LCL Filter
• Active Filter Line Inverter (rectifier) removes low frequencies
(< 1kHz)
• LCL Filter (passive filter) removes high frequencies (>1 kHz).
(Current and voltage)
• No transformer required
• Not affected by line imbalance
Harmonics Mitigation - Parallel Active Filter
• Distorted current is sampled.
• Fast acting transistors are used to generate harmonic currents
and inject them 180 degrees out of phase.
• PROS:
— Sized to harmonic content only.
— Maintains good performance at light loads.
• CONS:
• Expensive
• Susceptible to background voltage THD and imbalance.
• Complexity requires start-up and regular service by
manufacturer.
Measuring Harmonics
• Harmonics can be measured or monitored using specific
metering equipment.
• Digital Oscilloscope: Wave shape, THD, and amplitude
of each harmonic.
• True RMS Multimeter: Gives correct readings for
distortion- free sine waves and typically reads low when
the current waveform is distorted.
• Instruments should comply with the IEC specifications
summarized in IEEE 519-2014. -
Harmonics Analysis and Modeling
• Harmonics analysis is a mathematical way of simulating or
predicting harmonic distortion levels and potential resonances
based on the power system data.
• The electrical distribution system is modeled using proven
engineering software, and a harmonics analysis is performed
in conjunction with other analysis, such as short-circuit, etc.
• Should be performed by a qualified person, preferably a
licensed electrical engineer.
Evaluating Harmonics
• During the design stage of the project, especially when
capacitor banks or harmonics generating equipment will be
use .
• When capacitor banks need to be incorporated into an
existing system.
• In the event that large non-linear loads will be added to a
large facility especially if the new loading comprises 25% or
more of the existing load.
• If the facility has a history of harmonic related problems, such
as brownouts, voltage flicker, capacitor fuses being blown,
etc.
Conclusions
• Harmonics can result in decreasing power system reliability.
• Understanding the causes, potential effects, and mitigation
methods can reduce or eliminate problems.
• Mitigation should be considered if non-linear loads are
significant portion of total system load.
• Applying the harmonic limits per IEEE 519 can be challenging.
• Mitigation methods can be determined with a proper
Harmonics Analysis.
• It is recommended that the Harmonics Analysis be performed
by qualified personnel.
• It is essential that a coordinated solution be provided which
meets the THD levels, system performance demands, and
power system requirements.