Professional Documents
Culture Documents
FDS results are significantly influenced by the presence of Researchers have found that the dielectric dissipation factor Advantages and Disadvantages of Dielectric Response
moisture in insulation. In gen-eral, a higher dielectric as well as the capacitance val-ues increases with aging. Measurements in Time-Domain and Frequency-
dissipation factor is obtained with the increase of moisture Higher capacitance means higher permittivity and hence Domain
content in cellulose insulation. Fig. 1.5(a) shows that at poor insu-lation condition. Thus from FDS results different
frequencies lower than 0.01Hz a sharp rise of real part of aging conditions can be detected particular-ly at low Dielectric response measurement techniques in time domain,
complex permittivity occurs in the case of pressboard frequencies. This fact can be seen from Fig 1.6(a) and (b) viz. PDC and RVM, as well as that in frequency domain
samples having moisture content >2%. From 1.5(b) it may be where the tan and capacitance values of oil impregnated provide useful information on the condition of transformer
seen that the dielectric losses in impregnated pressboard paper insulation have been found to increase with ag-ing at insula-tion. Practical experience shows that all the three
increases considerably with the increase in moisture content frequencies below 0.1Hz. techniques rank the transformers in the same order. Salient
particularly for frequencies low-er than 100Hz. For features of the three measurement techniques are discussed
frequencies higher than 10kHz, the difference between the below. RVM being a high input impedance method, leakage
loss curves of pressboards having different moisture content current, e.g. surface leakage over the bushings, affect the
becomes insignificant. measurement. RVM has been found to be more sensitive to
systematic er-rors and the interpretation of RVM results is
not always unambiguous, especially in the pres-ence of
multiple peaks in RVM spectrum for old transformers.
Moreover, RVM considers in-sulation.
lightning impulses of standard shape and rate values are In order to avoid insulation failure, the insulation level of
applied under specific conditions. different types of equipment connected to the system has to
be higher than the magnitude of transient overvoltages that
appear on the system. The magnitude of transient over-
voltages are usually limited to a protective level by protective
devices. Thus the insulation level has to be above the
protective level by a safe margin. Normally the impulse
insulation level is established at a value 15-25% above the
protective level.
Consider the typical co-ordination of a 132 kV transmission
line between the transformer insulation, a line gap (across an
insulator string) and a co-ordinating gap (across the
transformer bushing). In co-ordinating the system under
consideration, we have to ensure that the equipment used
are protected, and that inadvertent interruptions are kept to
a minimum. The co-ordinating gap must be chosen so as to
provide protection of the transformer under all conditions.
However, the line gaps protecting the line insulation can be
set A typical set of characteristics for insulation co-ordination
by conventional methods, in which lightning impulse voltages
are the main source of insulation failure, is shown in the
figure 1.3.
For the higher system voltages, the simple approach used
above is inadequate. Also, economic considerations dictate
that insulation co-ordination be placed on a more scientific
(a) Rated Voltage less than 1 kA 50 % of discharge currents are less than 0.5 The power frequency spark over voltage should generally be
The designated maximum permissible r.m.s. value of power kA greater than about 1.5 times the rated voltage of the
frequency voltage between line and earth terminals. (C) Discharge Voltage (or Residual voltage) arrestor, to prevent unnecessary sparkover during normal
switching operations.
This is generally selected corresponding to 80% of the system The Discharge voltage is the voltage that appears between
phase-to-phase voltage for effectively earthed systems and the line and earth terminals of the surge diverter during the (e) Impulse spark over voltage
corresponding to 100% of the system phase-to-phase voltage passage of discharge currents. The impulse spark over voltage is the highest value of voltage
for non-effectively earthed systems. [Note: A surge diverter The discharge voltage of the selected arrestor should be attained during an impulse of a given waveshape and
of a higher rating may sometimes have to be chosen if some below the BIL of the protected equipment by a suitable polarity, applied between the line and earth terminals of a
of the other required criteria are not satisfied by this margin (generally selected between 15% and 25%). surge diverter prior to the flow of discharge current.
diverter]. The impulse spark over voltage is not a constant but is
The discharge voltage of an arrestor at nominal discharge
(b) Discharge Current current is not a constant, but also depends on the rate dependant on the duration of application. Thus it is common
The surge current that flows through the surge diverter after to define a wavefront impulse sparkover voltage in addition
of rise of the current and the waveshape. Typically, an to the impulse spark-over voltage.
spark over. increase of the rate of rise from 1 kA/µs to 5 kA/µs would
Nominal discharge current: This is the discharge current increase the discharge voltage by only about 35 %.
having a designated crest value and waveshape, which is The dependence of the discharge voltage on the discharge
used to classify a surge diverter with respect to durability and current is also small. Typically, an increase of discharge
protective characteristics. current from 5 kA to 10 kA would increase the discharge
The standard waveform for the discharge current is taken as voltage by about 15% for Silicon Carbide arrestors and by
8/20 µs). he nominal value of discharge current is selected about 2% for Zinc Oxide arrestors. {The discharge voltage is
from the standard values 10 kA (station type), 5 kA more often referred to as the residual discharge voltage].
(intermediate line type), 2.5 kA (distribution type) and 1.5 kA (d) Power frequency spark over voltage ;- The power
(secondary type), depending on the application. The highest frequency spark over voltage is the r.m.s. value of the lowest
ratings are used for. power frequency voltage, applied between the line and earth
99 % of discharge currents are less than 10 kA 95 % of terminals of a surge diverter, which causes spark-over of all
discharge currents are less than 5 kA 90 % of discharge the series gaps.
currents are less than 3 kA 70 % of discharge currents are
at the terminal increases with separation for typical rates of rise to what is called “displacement current” in addition to
rise. normal conduc-tion current. In other words, the nature of
this displacement current is dependent on polariza-tion of
the dielectric material which in turn depends on the
condition of the material under consideration.
10.3 Impulse Voltage Withstand Test 2.9 Fifty-Percent Dry Impulse Flashover Voltage — seconds. The test voltage shall be maintained at this value for
10.3.1 The insulator shall be tested dry under the The impulse voltage which, under the conditions one minute [see IS : 2071 ( Part II )-1974†]. The insulator shall
conditions prescribed in Appendix B. prescribed in 10.3 has a 50 percent probability of not flashover or puncture during the application of the test
10.3.2 The impulse generator shall be adjusted to producing a flashover on the insulator. voltage.
produce a standard 1.2/50 impulse wave of peak value 2.10 Wet Power-Frequency Withstand Voltage — The 10.4.5 To provide information when specially requested, the
equal to the specified value of the impulse withstand specified power-frequency voltage which the insulator wet flashover voltage of the insulator may be determined by
voltage corrected for atmospheric conditions in shall withstand (wet) under the conditions prescribed in increasing the voltage gradually from about 75 percent of the
accordance with Appendix A. 10.4 for the specified time (one minute) without wet withstand voltage to reach the flashover voltage in not
10.3.3 Five such impulse voltage waves shall be applied flashover or puncture. less than five seconds. The flashover voltage shall be the
to the insulator. If there is no flashover or puncture, the 2.11 Wet Power-Frequency Flashover Voltage — The arithmetic mean of five consecutive readings and the value
insulator shall be considered to have passed the test. If arithmetic mean value of the measured power frequency after correction to standard atmospheric conditions (see
during the application of these five waves puncture voltages which cause flashover of the insulator under Appendix A) shall be recorded.
occurs The insulator shall be considered to have passed the conditions prescribed in 10.4. 9. Wet tests
this test only if during this new series of tests there is no
10.4 Wet Power-Frequency Voltage Withstand Test The preferred wet test procedure, described in 9.1. is
flashover or puncture.
10.3.4 The insulator shall be capable of passing the 10.4.1 The insulator shall be arranged as prescribed in intended to simulate the effect of natural rain on external
impulse voltage withstand' test with voltages of both Appendix B. insulation and is a revision of earlier test methods. It is
recommended for tests with all types of test voltages and on
positive and negative polarity. However, when it is 10.4.2 Before the commencement of the test, the insulator
all types of apparatus, but either of the alternative test
evident which polarity will give the lower breakdown shall be exposed to the artificial rain produced in accordance
methods given below are permitted if specified by the
voltage, it shall suffice to test with that polarity. with 9.1 of IS : 2071 ( Part I )-1993* for at least one minute
before application of voltage and then throughout the test. relevant Technical Committee.
10.3.5.1 The impulse flashover voltages to be recorded shall
10.4.3 The test voltage to be applied to the insulator shall be Two earlier test methods. not intended to simulate natural
be the positive and negative 50 percent impulse flashover
the specified value of the wet power-frequency withstand rain, are described in 9.2. They have been in use for many
voltage as measured above and corrected in accordance with
voltage adjusted for atmospheric conditions at the time of years for tests with alternating voltages on apparatus having
Appendix A.
test (see Appendix A). Um up to 420 kV and many test data obtained by these
10.3.5.2 The insulator shall not be damaged by these tests, but methods exist.
slight marks on the surface of the insulating parts or chipping 10.4.4 A voltage of about 75 percent of the test voltage as
of the cement or other material used for assembly shall be determined in 10.4.3 shall be applied and then increased
permitted gradually to reach the test voltage in a time not less than five
For a.c. apparatus of large dimensions, such as those having distance between the uppermost Point of the insulator metal
Um higher than 800 kV, no appropriate wet test procedure is work and the supporting structure shall be not less than 1
available at present. metreB-2.1.2 The diameter of the conductor shall be about
The relevant Technical Committee shall specify the 1.5 percent of the length of the string insulator unit or
arrangement of the test object during the test procedure. insulator string with a minimum of 25 mm.
9.1 Standard wet test procedure B-2.1.3 The length of the conductor shall be at least 1.5 times
that of the string insulator unit or insulator string, and it shall
The test object shall be sprayed with water of prescribed extend at least 1 metre on each side of the vertical axis.
resistivity and temperature (see table 1) falling on it as
droplets (avoiding fog and mist) and directed so that the B-2.1.4 Precautions shall be taken to avoid flashover from the
vertical and horizontal components of the spray intensity are ends of the conductor.B-2.1.5 The test voltage shall be
approximately equal. These intensities are measured with a applied between the conductor and earth.B-2.2 Rigid
divided collecting vessel having openings of 100 cm* to 750 InsulatorB-2.2.1 The insulator shall be mounted on an
cm*, one horizontal and one vertical, the vertical opening earthed metallic vertical pin, with a smooth surface and a
facing the spray. diameter not less than 16 mm.
The position of the test object relative to the vertical and B-2.2.3 If the rigid insulator is provided with means of
horizontal rain components shall be specified clamping, conductor shall be placed in the clamp.
by the relevant Technical Committee. B-2.2.4 The test voltage shall be applied between the
conductor and earth. NOTE — When to agreed, tests may
In general, the reproducibility of wet test results is less than also be made under conditions reproducing service
that for other high voltage discharge or withstand tests. To conditions as closely as possible, taking account of all factors
minimize the dispersion the following precautions shall be which may influence flashover voltage.
taken:
B-2. METHODS OF SUPPORT
B-2.1 String Insulator Unit and Insulator String
B-2.1.1 The string insulator unit or insulator string shall be
suspended vertically by means of an earthed wire rope or
other suitable conductor from a supporting structure. The