You are on page 1of 7

Frequency Domain Spectroscopy

Abstract Frequency domain spectroscopy (FDS) is a non-


destructive method of assessing the insulation condition of
high voltage equipment, especially oil-paper insulation
system of transformers. It is a reliable tool for predictive
maintenance of such equipment in the field. In this method
each test object is considered as a black box accessible only
through its termi-nals. Consequently this method identifies
the global changes in the insulation condition and is not
suitable for identifying any local defect in the insulation
system. FDS results are affected by the geometry of the
insulation system, i.e. the relative dimensions of spacers,
barriers and oil ducts. The external factors that affect FDS
most are operating temperature and weather condi-tions like
rain. For on-site testing significant errors can be introduced
in FDS measurement, if certain precautions are not taken,
particularly when different equipments are connected in
parallel with the transformer. Mathematical modeling is
important for the interpretation of FDS results for the
estimation of moisture content in solid insulation.
Basic Theory of Frequency Domain Spectroscopy

Effect of Moisture in Insulation

FDS results are significantly influenced by the presence of Researchers have found that the dielectric dissipation factor Advantages and Disadvantages of Dielectric Response
moisture in insulation. In gen-eral, a higher dielectric as well as the capacitance val-ues increases with aging. Measurements in Time-Domain and Frequency-
dissipation factor is obtained with the increase of moisture Higher capacitance means higher permittivity and hence Domain
content in cellulose insulation. Fig. 1.5(a) shows that at poor insu-lation condition. Thus from FDS results different
frequencies lower than 0.01Hz a sharp rise of real part of aging conditions can be detected particular-ly at low Dielectric response measurement techniques in time domain,
complex permittivity occurs in the case of pressboard frequencies. This fact can be seen from Fig 1.6(a) and (b) viz. PDC and RVM, as well as that in frequency domain
samples having moisture content >2%. From 1.5(b) it may be where the tan and capacitance values of oil impregnated provide useful information on the condition of transformer
seen that the dielectric losses in impregnated pressboard paper insulation have been found to increase with ag-ing at insula-tion. Practical experience shows that all the three
increases considerably with the increase in moisture content frequencies below 0.1Hz. techniques rank the transformers in the same order. Salient
particularly for frequencies low-er than 100Hz. For features of the three measurement techniques are discussed
frequencies higher than 10kHz, the difference between the below. RVM being a high input impedance method, leakage
loss curves of pressboards having different moisture content current, e.g. surface leakage over the bushings, affect the
becomes insignificant. measurement. RVM has been found to be more sensitive to
systematic er-rors and the interpretation of RVM results is
not always unambiguous, especially in the pres-ence of
multiple peaks in RVM spectrum for old transformers.
Moreover, RVM considers in-sulation.

Effect of Insulation Aging


geometry and oil conductivity only to a limited extent. It Terminology Conventional Impulse Withstand Voltages: This is the peak
takes very long time to rec-ord the complete polarization value of the switching or lightning impulse test voltage at
spectrum. A more practical approach has been suggested in which an insulation shall not show any disruptive discharge
in which three recovery voltage measurements are when subjected to a specified number of applications of this
recommended to be taken with charging times 10s, 100s and impulse under specified conditions. Conventional Maximum
1000s. Impulse Voltage: This is the peak value of the switching or
Interpretation of PDC results is straightforward and it lightning overvoltage which is adopted as the maximum
Factor of Earthing: This is the ratio of the highest r.m.s. overvoltage in the conventional procedure of insulation co-
provides moisture content in solid in-sulation and both oil
phase-to-earth power frequency voltage on a sound phase ordination.
and paper conductivities. Other diagnostic parameters like
during an earth fault to the r.m.s. phase-to-phase power
tan and po-larization spectra can be calculated from PDC Statistical Impulse Withstand Voltage: This is the peak value
frequency voltage which would be obtained at the selected
results. But, drift and jitter free voltage source is required for of a switching or lightning impulse test voltage at which
location without the fault. This ratio characterises, in general
accurate analysis. Since the currents are low, the insulation exhibits, under the specified conditions, a 90%
terms, the earthing conditions of a system as viewed from
measurements are affected by offset currents and probability of withstand. In practice, there is no 100%
the selected fault location. Effectively Earthed System : A
interference in the field. But it is possible to implement probability of withstand voltage. Thus the value chosen is
system is said to be effectively earthed if the factor of
guarded meas-urement to eliminate the surface leakage that which has a 10% probability of breakdown.Statistical
earthing does not exceed 80%, and non-effectively earthed if
currents from measurements. Another important as-pect of Impulse Voltage: This is the switching or lightning
it does.
PDC measurement is the switching transients at the start of overvoltage applied to equipment as a result of an event of
polarization and depolari-zation which means that the first [Note: Factor of earthing is 100% for an isolated neutral one specific type on the system (line energising, reclosing,
few seconds are difficult to measure, which in turn makes the system, while it is 57.7% (corresponding to 1/%3) for a solidly fault occurrence, lightning discharge, etc), the peak value of
lower limit of the equivalent frequency about 1Hz. earthed system. In practice, the effectively earthed which has a 2% probability of being exceeded.
condition is obtained when the ratio x0/x1 < 3 and the ratio
Interpretation of FDS results is also straightforward. It could Rated Short Duration Power Frequency Withstand Voltage:
r0/x1 < 1.
separate real and imaginary parts of complex capacitance This is the prescribed r.m.s. value of sinusoidal power
and complex permittivity. It also provides the moisture Insulation Level: For equipment rated at less than 300 kV, it frequency voltage that the equipment shall withstand during
content in solid insulation and diagnostic quantity like C- is a statement of the Lightning impulse withstand voltage and tests made under specified conditions and for a specific time,
ratio. FDS method is relatively insensitive to interference due the short duration power frequency withstand voltage. usually not exceeding one minute.
to its inherent small bandwidth. For equipment rated at greater than 300 kV, it is a statement Protective Level of Protective Device: These are the highest
of the Switching impulse withstand voltage and the power peak voltage value which should not be exceeded at the
frequency withstand voltage. terminals of a protective device when switching impulses and

lightning impulses of standard shape and rate values are In order to avoid insulation failure, the insulation level of
applied under specific conditions. different types of equipment connected to the system has to
be higher than the magnitude of transient overvoltages that
appear on the system. The magnitude of transient over-
voltages are usually limited to a protective level by protective
devices. Thus the insulation level has to be above the
protective level by a safe margin. Normally the impulse
insulation level is established at a value 15-25% above the
protective level.
Consider the typical co-ordination of a 132 kV transmission
line between the transformer insulation, a line gap (across an
insulator string) and a co-ordinating gap (across the
transformer bushing). In co-ordinating the system under
consideration, we have to ensure that the equipment used
are protected, and that inadvertent interruptions are kept to
a minimum. The co-ordinating gap must be chosen so as to
provide protection of the transformer under all conditions.
However, the line gaps protecting the line insulation can be
set A typical set of characteristics for insulation co-ordination
by conventional methods, in which lightning impulse voltages
are the main source of insulation failure, is shown in the
figure 1.3.
For the higher system voltages, the simple approach used
above is inadequate. Also, economic considerations dictate
that insulation co-ordination be placed on a more scientific

Conventional method of insulation co-ordination Statistical Method of Insulation Co-ordination


At the higher transmission voltages, the length of insulator nature of the overvoltage magnitudes and of electrical direct strikes only on a short length of line prior to the
strings and the clearances in air do not increase linearly with withstand strength of insulation. substation. This can be calculated as follows.
voltage but approximately to V1.6 The required number of The risk of failure of the insulation is dependant on the Consider a surge e approaching the terminal equipment.
suspension units for different overvoltage factors is shown. integral of the product of the overvoltage density function When the surge magnitude exceeds the critical voltage e0,
It is seen that the increase in the number of disc units is only f0(V) and the probability of insulation failure P(V). Thus the corona would occur, distorting the surge wavefront, as it
slight for the 220 kV system, with the increase in the risk of flashover per switching operation is equal to the travels. The minimum length of earth wire should be chosen
overvoltage factor from 2.0 to 3.5, but that there is a rapid area under the curve I f0(V)*P(V)*dV. such that in traversing that length, all voltage above the
increase in the 750 kV system. Thus, while it may be maximum surge that can arrive att the terminal has been
economically feasible to protect the lower voltage lines up to distorted by corona. [The maximum permissible surge
an overvoltage factor of 3.5 (say), it is definitely not corresponds to the incident voltage that would cause
economically feasible to have an overvoltage factor of more insulation failure at the terminal equipment.]
than about 2.0 or 2.5 on the higher voltage lines. In the
Modification of Waveshape by Corona
higher voltage systems, it is the switching overvoltages that is
predominant. However, these may be controlled by proper When a surge voltage wave travelling on an overhead line
design of switching devices. causes an electric field around it exceeding the critical stress
of air, corona will be formed. This corona formation
obviously extracts the energy required from the surge. Since
the power associated with corona increases as the square of
the excess voltage, the attenuation of the waveform will not
be uniform so that the waveform gets distorted. Further,
corona increases the effective radius of the conductor giving
rise to a greater capacitance for the outer layers. Since the
line inductance remains virtually a constant, the surge
associated with the outer layers of corona would have a
Length of Overhead Shielding Wire lower wave velocity than in the conductor itself. These
effects in practice give rise to a wavefront distortion and not
Evaluation of Risk Factor For reasons of economics, the same degree of protection is
a wavetail distortion, as shown in figure 10.7.
not provided throughout a transmission line. Generally, it is
The aim of statistical methods is to quantify the risk of failure found sufficient to provide complete protection against
of insulation through numerical analysis of the statistical

An overhead earth wire provides considerable protection


against direct strikes. They also reduce induced
overvoltages. However, they do not provide protection
against surges that may still reach the terminal equipment.
Such protection may either be done by diverting the major
part of the energy of the surge to earth (surge diverters), or
by modifying the waveform to make it less harmful (surge
modifiers). .
Spark gaps for surge protection
The simplest and cheapest form of protection is the spark
gap. The selected gap spacing should no only be capable of
withstanding the highest normal power frequency voltage
but should flash-over when overvoltages occur, protecting
the equipment. Also, once a gap flashes over under a surge
voltage, the ionised gap allows a power frequency follow
through current, leading to a system outage. Thus rod gaps
are generally used as a form of back up protection rather
than the main form of protection.

Surge Protection Expulsion Tube Lightning Arrestor


An expulsion tube arrestor consists essentially of a spark gap Surge diverters (or lightning arrestors) generally consist of the voltage does not collapse to zero instantly due to the
arranged in a fibre tube, and another series external rod gap. one or more spark gaps in series, together with one or more voltage across the non-linear resistor. When the surge
A typical arrangement for a 33 kV expulsion tube, with the non-linear resistors in series. Silicon Carbide (SiC) was the voltage increases, there is a corresponding but rapid
external gap of the order of 50 mm and the internal gap of material most often used in these non-linear resistor surge decrease of the resistance discharging the surge energy to
about 180 mm is shown in figure 10.9. The purpose of the diverters. However, Zinc Oxide (ZnO) is being used in most earth. Once the surge passes through, the power frequency
external gap is to isolate the fibre tube from normal voltages modern day surge diverters on account of its superior volt- voltage remaining is insufficient to maintain a sufficient
thus preventing unnecessary deterioration. The high ampere characteristic. In fact the ZnO arrestor is often used current for the arc to continue. Thus the arcs extinguish and
temperature of the arc rapidly vaporises the organic gapless, as its normal follow current is negligibly small. The the gaps reseal. In the case of the ZnO arrestor, due to the
materials of the wall of the tube and causes a high gas volt-ampere characteristics of SiC and of ZnO non-linear negligible continuous power frequency current even in the
pressure (up to 7000 p.s.i.) to be built up. The high Figure elements are shown for comparison with that of a linear absence of a series gap, the series gap is sometimes
10.9 - Expulsion Tube pressure and the turbulence of the gas resistor. eliminated simplifying construction.
extinguishes the arc at a natural current zero, and the hot
gasses are expelled through the vent in the earthed
electrode. The power frequency follow current is interrupted
within one or two half cycles so that protective relays would
not operate causing unnecessary interruptions.

The problem is generally overcome by having high equal


resistances shunting the series gaps, ensuring a uniform
distribution.
Selection of Surge Diverters
Surge Diverters When a surge appears at a surge diverter terminal, within a
Surge diverters for a particular purpose are selected as
short time the breakdown voltage of the series gap is
follows.
reached, and the arrestor discharges. Unlike in the rod gap,

(a) Rated Voltage less than 1 kA 50 % of discharge currents are less than 0.5 The power frequency spark over voltage should generally be
The designated maximum permissible r.m.s. value of power kA greater than about 1.5 times the rated voltage of the
frequency voltage between line and earth terminals. (C) Discharge Voltage (or Residual voltage) arrestor, to prevent unnecessary sparkover during normal
switching operations.
This is generally selected corresponding to 80% of the system The Discharge voltage is the voltage that appears between
phase-to-phase voltage for effectively earthed systems and the line and earth terminals of the surge diverter during the (e) Impulse spark over voltage
corresponding to 100% of the system phase-to-phase voltage passage of discharge currents. The impulse spark over voltage is the highest value of voltage
for non-effectively earthed systems. [Note: A surge diverter The discharge voltage of the selected arrestor should be attained during an impulse of a given waveshape and
of a higher rating may sometimes have to be chosen if some below the BIL of the protected equipment by a suitable polarity, applied between the line and earth terminals of a
of the other required criteria are not satisfied by this margin (generally selected between 15% and 25%). surge diverter prior to the flow of discharge current.
diverter]. The impulse spark over voltage is not a constant but is
The discharge voltage of an arrestor at nominal discharge
(b) Discharge Current current is not a constant, but also depends on the rate dependant on the duration of application. Thus it is common
The surge current that flows through the surge diverter after to define a wavefront impulse sparkover voltage in addition
of rise of the current and the waveshape. Typically, an to the impulse spark-over voltage.
spark over. increase of the rate of rise from 1 kA/µs to 5 kA/µs would
Nominal discharge current: This is the discharge current increase the discharge voltage by only about 35 %.
having a designated crest value and waveshape, which is The dependence of the discharge voltage on the discharge
used to classify a surge diverter with respect to durability and current is also small. Typically, an increase of discharge
protective characteristics. current from 5 kA to 10 kA would increase the discharge
The standard waveform for the discharge current is taken as voltage by about 15% for Silicon Carbide arrestors and by
8/20 µs). he nominal value of discharge current is selected about 2% for Zinc Oxide arrestors. {The discharge voltage is
from the standard values 10 kA (station type), 5 kA more often referred to as the residual discharge voltage].
(intermediate line type), 2.5 kA (distribution type) and 1.5 kA (d) Power frequency spark over voltage ;- The power
(secondary type), depending on the application. The highest frequency spark over voltage is the r.m.s. value of the lowest
ratings are used for. power frequency voltage, applied between the line and earth
99 % of discharge currents are less than 10 kA 95 % of terminals of a surge diverter, which causes spark-over of all
discharge currents are less than 5 kA 90 % of discharge the series gaps.
currents are less than 3 kA 70 % of discharge currents are
at the terminal increases with separation for typical rates of rise to what is called “displacement current” in addition to
rise. normal conduc-tion current. In other words, the nature of
this displacement current is dependent on polariza-tion of
the dielectric material which in turn depends on the
condition of the material under consideration.

A polarization current measurement is usually stopped if the


1.2 Basic Theory of Time Domain Dielectric Response current becomes either stable due to 0 or becomes very
Separation limit for lightning arrestors
low. If the test object is now short-circuited at t = tc, the
Measurement
Best protection is obtained for terminal equipment by placing depolari-zation or discharging current flows as idepol(t).
the arrestor as near as possible to that equipment. When For proper utilization of time-domain dielectric response
According to the superposition principle, sudden reduction of
arrestors must be separated from the protected equipment, measurement, one should under-stand the physics behind
the voltage U0 to zero can be regarded as a negative step
additional voltage components are introduced, which add the processes. However, the physical mechanism of dielectric
voltage at time t = tc . Then we get for t (t0 + tc)
instant by instant to the discharge voltage. The maximum re-sponse of oil-paper insulation of transformer is very
voltage at the terminal of a line as a result of the first complex, as it includes moisture migra-tion through cellulose
reflection of a travelling wave may be expressed depending on moisture potential and moisture equilibrium
mathematically as within transformer, adsorption of water vapour in cellulose
material and mechanisms of bubbles evolution. Any dielectric
Ea is the discharge voltage at the arrestor, and de/dt is the
material, under the influence of an electric field, results in a
rate of rise of the wavefront. When the value of $ is not
relative shift of positive and negative charges in the material.
known, it may generally be assumed as equal to 1 without
This phenomenon is called dielectric polariza-tion which gives
much loss of accuracy. Figure 10.12 shows how the voltage

Time Domain Response Measurements


Polarization and depolarization current measurements
Two resistors of this circuit represent the protection
resistances, which will not influence the recorded currents.
The sample under test has two electrodes marked HV and LV.
LV is per-manently connected with electrometer, a type of
precision ammeter (and also voltmeter on requirement).
During charging or polarization, the switch S connects at
position 2 due to which the polarization current ipol(t) flows Concept of RV spectra and the central time constant
under the influence of the applied step voltage U0. Recovery
During recovery voltage measurement, the current density is According to the methodology of RV measurement, as stated
Voltage Measurement
zero as this voltage needs to be measured by open circuit in Section 1.3.2, the charging time is increased gradually with
condition. Thus equation 1.4 can be solved with j(t) = 0. If the As per the basic theory of recovery voltage measurement, the corresponding increase in discharging time from a small
con-ductivity 0, permittivity 0 are known, then the the charging (polarization) and dis-charging (depolarization) initial value and a different peak value of recovery voltage,
recovery voltage depends on the response function f(t,) process can be performed using the same circuit as that of Vrecovery(peak) is obtained in each step. Peak values
which in turn depends on the characteristics of the dielectric Fig. 1.3. The difference is in the time where the discharging obtained for different charging times (tch) can be plotted to
material. Hence recovery voltage measurement is another time is much less than the charging time according to the yield a Vrecov-ery(peak) vs. tch curve, which is called
important parameter in time domain dielectric spec- requirement. A typical case may be discharging time ( recovery voltage spectrum. This recovery voltage spec-trum
troscopy. tdischarge) = half of charging time (i.e. tch/2). To measure is also analyzed for condition monitoring. The charging time
the voltage, the electrometer should be able to change its corresponding to the peak
mode from ammeter to voltmeter at the proper instant of
time.
Time Domain Response of Transformer Insulation insulation by preparing oil impregnated pressboard samples
with accelerated aging. Due to aging, the slope of the initial
In electric utilities around the world, significant proportion of
part of both polarization and depolarization current becomes
power transformers are being operating beyond their design
lower compared to unaged insu-lation. One of the
life. Sudden failure of such transformers operating at a
explanations may be that, due to aging, the migration of
pivotal position may cause total power disruption resulting in
interfacial charges becomes sluggish through the oil and
substantial loss of money and time. At present, emphases are
consequently, the overall rate of polarization becomes
given on non-invasive methods for condition assessment of
slower. This results in lower slope in the obtained current. An
oil-paper insulation of power transformers. As explained in
approximate assessment of the dielectric condition can be
the aforesaid sections, the methodology of PDC and RVM is
made by visualization of the curves. The closer the curve
best suited in assessment of condition in transformer
peak (CTC) is towards the small time constant, the worse is
insulation by time domain response measurement in
the condition of the dielectric. It may be noted here that, the
dielectric spectroscopy. Henceforth, in the subsequent sec-
degeneration of cellulose insulation produce water as an end
tions, results of PDC and RVM will be dealt with composite
product of the chemical reaction, which contributes to the
oil-paper insulation as dielectric under test. Before
moisture content of the cellulose insulation (mainly paper).
performing the test, HV and LV is short circuited for a sub-
Hence, the paper moisture content reflects the aging
stantial period of time such that the test object is completely
condition of insulation.
“discharged”. Otherwise some polarization will exist in the
insulation that may adversely affect the obtained results. To
prove the effectiveness of the PDC and RVM methodologies,
transformer models are con-structed in the laboratory using
CIGRE standards. Various parameters like temperature, oil
conductivity, moisture content in paper, artificial aging effect
are varied in the model for a comprehensive study of the
phenomena involved.
Effect of Insulation Aging
Nature of polarization and depolarization current varies
significantly with overall aging of the oil-paper insulation. J. L.
Wei et al studied the aging characteristics of oil-paper

10.3 Impulse Voltage Withstand Test 2.9 Fifty-Percent Dry Impulse Flashover Voltage — seconds. The test voltage shall be maintained at this value for
10.3.1 The insulator shall be tested dry under the The impulse voltage which, under the conditions one minute [see IS : 2071 ( Part II )-1974†]. The insulator shall
conditions prescribed in Appendix B. prescribed in 10.3 has a 50 percent probability of not flashover or puncture during the application of the test
10.3.2 The impulse generator shall be adjusted to producing a flashover on the insulator. voltage.
produce a standard 1.2/50 impulse wave of peak value 2.10 Wet Power-Frequency Withstand Voltage — The 10.4.5 To provide information when specially requested, the
equal to the specified value of the impulse withstand specified power-frequency voltage which the insulator wet flashover voltage of the insulator may be determined by
voltage corrected for atmospheric conditions in shall withstand (wet) under the conditions prescribed in increasing the voltage gradually from about 75 percent of the
accordance with Appendix A. 10.4 for the specified time (one minute) without wet withstand voltage to reach the flashover voltage in not
10.3.3 Five such impulse voltage waves shall be applied flashover or puncture. less than five seconds. The flashover voltage shall be the
to the insulator. If there is no flashover or puncture, the 2.11 Wet Power-Frequency Flashover Voltage — The arithmetic mean of five consecutive readings and the value
insulator shall be considered to have passed the test. If arithmetic mean value of the measured power frequency after correction to standard atmospheric conditions (see
during the application of these five waves puncture voltages which cause flashover of the insulator under Appendix A) shall be recorded.
occurs The insulator shall be considered to have passed the conditions prescribed in 10.4. 9. Wet tests
this test only if during this new series of tests there is no
10.4 Wet Power-Frequency Voltage Withstand Test The preferred wet test procedure, described in 9.1. is
flashover or puncture.
10.3.4 The insulator shall be capable of passing the 10.4.1 The insulator shall be arranged as prescribed in intended to simulate the effect of natural rain on external
impulse voltage withstand' test with voltages of both Appendix B. insulation and is a revision of earlier test methods. It is
recommended for tests with all types of test voltages and on
positive and negative polarity. However, when it is 10.4.2 Before the commencement of the test, the insulator
all types of apparatus, but either of the alternative test
evident which polarity will give the lower breakdown shall be exposed to the artificial rain produced in accordance
methods given below are permitted if specified by the
voltage, it shall suffice to test with that polarity. with 9.1 of IS : 2071 ( Part I )-1993* for at least one minute
before application of voltage and then throughout the test. relevant Technical Committee.
10.3.5.1 The impulse flashover voltages to be recorded shall
10.4.3 The test voltage to be applied to the insulator shall be Two earlier test methods. not intended to simulate natural
be the positive and negative 50 percent impulse flashover
the specified value of the wet power-frequency withstand rain, are described in 9.2. They have been in use for many
voltage as measured above and corrected in accordance with
voltage adjusted for atmospheric conditions at the time of years for tests with alternating voltages on apparatus having
Appendix A.
test (see Appendix A). Um up to 420 kV and many test data obtained by these
10.3.5.2 The insulator shall not be damaged by these tests, but methods exist.
slight marks on the surface of the insulating parts or chipping 10.4.4 A voltage of about 75 percent of the test voltage as
of the cement or other material used for assembly shall be determined in 10.4.3 shall be applied and then increased
permitted gradually to reach the test voltage in a time not less than five
For a.c. apparatus of large dimensions, such as those having distance between the uppermost Point of the insulator metal
Um higher than 800 kV, no appropriate wet test procedure is work and the supporting structure shall be not less than 1
available at present. metreB-2.1.2 The diameter of the conductor shall be about
The relevant Technical Committee shall specify the 1.5 percent of the length of the string insulator unit or
arrangement of the test object during the test procedure. insulator string with a minimum of 25 mm.

9.1 Standard wet test procedure B-2.1.3 The length of the conductor shall be at least 1.5 times
that of the string insulator unit or insulator string, and it shall
The test object shall be sprayed with water of prescribed extend at least 1 metre on each side of the vertical axis.
resistivity and temperature (see table 1) falling on it as
droplets (avoiding fog and mist) and directed so that the B-2.1.4 Precautions shall be taken to avoid flashover from the
vertical and horizontal components of the spray intensity are ends of the conductor.B-2.1.5 The test voltage shall be
approximately equal. These intensities are measured with a applied between the conductor and earth.B-2.2 Rigid
divided collecting vessel having openings of 100 cm* to 750 InsulatorB-2.2.1 The insulator shall be mounted on an
cm*, one horizontal and one vertical, the vertical opening earthed metallic vertical pin, with a smooth surface and a
facing the spray. diameter not less than 16 mm.

The position of the test object relative to the vertical and B-2.2.3 If the rigid insulator is provided with means of
horizontal rain components shall be specified clamping, conductor shall be placed in the clamp.

by the relevant Technical Committee. B-2.2.4 The test voltage shall be applied between the
conductor and earth. NOTE — When to agreed, tests may
In general, the reproducibility of wet test results is less than also be made under conditions reproducing service
that for other high voltage discharge or withstand tests. To conditions as closely as possible, taking account of all factors
minimize the dispersion the following precautions shall be which may influence flashover voltage.
taken:
B-2. METHODS OF SUPPORT
B-2.1 String Insulator Unit and Insulator String
B-2.1.1 The string insulator unit or insulator string shall be
suspended vertically by means of an earthed wire rope or
other suitable conductor from a supporting structure. The

You might also like