You are on page 1of 2

IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS VOL. PAS-85, NO.

8 AUGFUST, 1966

Tests for Damaging Corona for Oil-Insulated


Power Transformers
IEEE COMMITTEE REPORT

FOREWORD vulnerable to corona, and there may be some qtuestion as to


THIS is presented as a progress report on the develop- the value of such a test procedure in this case, as well as
ment of tests to determine the presence of damaging certain other cases.
corona in oil-immersed power transformers. One of the several mitigating circumstances in the prob-
The demand for such tests is based on the possibility lem is that neither oil-insulated nor dry-type transformers
that transformer insulation can be damaged and ultimately have always been free from corona, even under operating
fail if there is corona under operating conditions. The fact conditionis. Corona in small voids in materials resistant
that a transformer withstands the usual low frequency and to corona does not prevent successful operation. Another
impulse tests may not insure that local corona in some circumstance is that corona under test voltage conditions
areas cannot result in progressive damage and ultimate may not mean that corona exists under operating condi-
failure. In fact, since the ratio between the test voltage tions. For many years corona sometimes occurred on tests
and service voltage has decreased, failures resulting from to an extent which marked the insulation, but the clear-
this have occurred. ances were such that the urits operated for many years.
The problems in the development of a suitable corona These conditions lead to some of the controversial points
test include: 1) the determination of the level of corona of view.
which may cause progressive damage, and 2) the test Another problem is that determination of the presence
procedure for measuring the corona level, both of which of corona does not give its location, and it may be very
are controversial subjects. difficult to find. Means are available which can be very
There has been tentative agreement that radio influence helpful in some cases, but which in other cases leave the
voltage (RIV) measurements are sufficiently sensitive to location doubtful. This, of course, means that at the
make measurements which would provide reasonable in- present time the tests can be a difficult problem for the
surance against progressive corona damage. The actual manufacturer.
values of RIV have not been agreed upon, nor even the PROPOSED PROCEDURE FOR CORONA TESTS ON POWER
detailed procedure as to the test voltages at which readings TRANSFORMERS
should be obtained. There is some agreement that a
relatively small RIV number should not be exceeded at Internal corona measurements, when required, shall be
125 or 150 percent of the normal operating voltage, but made during the induced potential test at a voltage level to
this is still being discussed in the Working Group. There be specified. The RIV generated by the corona shall be
is also a question as to whether measurements should be taken as an indication of the corona. The general method
made during the normal induced test with the required of measurement and calibration procedures are described
test voltage from terminal to ground, during the normal in a NE-MA publication.1
induced test with the required test voltage from terminal Internal corona measurements, when specified, shall be
to terminal, or during a separa-te induced test for this made during the induced-potential test.
specific purpose. The magnitude of corona shall be determined by meas-
There has been progress, however, in the procedure for uring, at the terminal of the winding under test, the RIV
making the RIV measurements, and this has been gen- generated by the corona.
erally agreed upon in the Working Group. The publication A Radio Noise and Field Strength Meter, conforming to
of this agreemernt for educational purposes and general in- ASA Standard C63.2, shall be used to measure the RIV
formation was requested by the Subcommittee on Dielec- generated by the corona. The measurement shall prefer-
tric Tests and the Transformers Committee. ably be made at a frequency of one megacycle per second,
The procedure for making corona tests is at present although any frequency from 0.85 to 1.15 megacycles per
limited to oil-insulated transformers. It should be noted second may be used.
that dry-type transfornmers may use materials extremely The general method and procedure shall conformi with
the recommendations of the mentioned NEMA publica-
Manuscript received May 11, 1966. tion except that the radio noise (RN) meter can be coupled
Members of the Working Group on the Revision of Dielectric to the terminal of the winding under test through a coup-
Tests of the IEEE Transformers Committee are F. J. Vogel, Chair-
man, E. J. Adolphson, S. Bennon, C. H. Bjorquist, V. F. Christen, C.
C. Honey, N. A. Hills, G. W. Iliff, D. C. Johnson, R. B. Kaufman,
D. M. MacGregor, L. B. Rademacher, C. L. Rose, R. C. Thomas, and 1 " Methods of measurement of radio influence voltage (RIV)
H. J. Weber. of high-voltage apparatus," NEMA Standards publication 107, 1964.
892
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS VOLJ. PAS-85, N O. 8 AUGUST, 1966

ling capacitor or through the capacitance tap of the bushing ing under test and the RIV reading of the RN meter
that constitutes the terminal. at its normal locationi in the circuit selected for the
If RIV is measured at the capacitance tap of the bush- corona test.
ing, a suitable device shall be used which can be tuned with The calibration ratio shall be determiined by:
the bushing tap-to-ground capacitance at the measuring
frequiency. This device shall conistitute all circuit elemeints 1) Application to the terminal under test of the output
from the capacitance tap of the bushing to the RN meter. of a sine-wave signal generator at approximately 100
The coaxial cable, an element of the device, may be of any microvolts at the measuring frequency.
suitable impedance and need not be terminated in its 2) Measurement of the voltage on the terminal with the
characteristic impedance. The purpose of the device is RN meter connected directly to the terminal.
to minimize the dividing effect of the bushing capaci- 3) MIeasurement, with the same RN meter, of the volt-
tances and to convey the RIV to the RN meter with age appearing in the test circuit at the location where
minimum attenuation. the RN meter will be connected during the corona
External shielding, as required, shall be used to avoid air measurement on the transformer. A second RN meter
corona. may be used, provided its relationship to the first RN
The test circuit components connected to the winding meter has been established.
under test will attenuate the observed RIV measure- 4) It shall be established that this calibration ratio re-
ments and add to the RIV background level. When the mains valid over the RIV range of interest.
voltage is applied directly to the winding under test, radio-
frequency chokes or tuned filters shall be used to isolate The ratio of the voltage measured with the RN meter at
the transformer under test and the RIV measuring circuit the terminal to the voltage measured with the RN meter
from the rest of the test circuit. at the normal location in the circuit, which has been
In either case, whether the coupling capacitor or the selected for the corona test on the transformer, will be
bushing capacitance tap is used to make the measurement, applied as a correction factor to the RIV reading obtained
it is niecessary to establish by a calibration procedure, the during the corona test to determine the actual RIV at the
relationship between the RIV at the terminal of the wind- terminal of the winding under test.

Transformer Corona Testing


J. R. MlEADOR, FELLOW, IEEE, R. B. KAUFAIAN, FELLOW, IEEE, AND
H. H. BRUSTLE, SENIOR MEMBER, IEEE

Abstract-The progress made to date in corona testing trans- INTRODUCTION AND BACKGROUND
formers at the factory is reviewed and the importance of sonic
detection and location of corona sources is shown. Major improve- THE CONCLUSION of the first phase of a program to
ments in sonic techniques are reported. Test curves of RIV vs. develop a practical transformer corona test was re-
transformer test voltage are given for units having defects. The ported in 1958 [1]. This work had been undertaken in
various corona test proposals being considered by the industry are recognition of the continuing trend to higher voltages,
described and discussed. The best assurance of product quality is
stated to be a corona test, using RIV and advanced sonic techniques, larger unit ratings and further reductions in insulation
made at full transformer induced test voltage with a limit of 1000 levels.
microvolts. The second phase of the program was reported in 1960
[2] and specific suggestions on the method, the test voltage
Paper 31 TP 66-79, recommended and approved by the Trans- level and limiting values were made. It was concluded that
formers Committee of the IEEE Power Group for presentation at the using a variation of the NEMTA RIV procedure, with the
IEEE Winter Power Meeting, New York, N. Y., January 30-Feb-
ruary 4, 1966. Manuscript submitted October 29, 1965; made avail- bushing capacitance tap, it was feasible to make RIV
able for printing December 13, 1965. measurements at full induced test voltage with a limit of
The authors are with the General Electric Company, Pittsfield,
Mass. 1000 microvolts.
893

You might also like