Professional Documents
Culture Documents
8 AUGFUST, 1966
ling capacitor or through the capacitance tap of the bushing ing under test and the RIV reading of the RN meter
that constitutes the terminal. at its normal locationi in the circuit selected for the
If RIV is measured at the capacitance tap of the bush- corona test.
ing, a suitable device shall be used which can be tuned with The calibration ratio shall be determiined by:
the bushing tap-to-ground capacitance at the measuring
frequiency. This device shall conistitute all circuit elemeints 1) Application to the terminal under test of the output
from the capacitance tap of the bushing to the RN meter. of a sine-wave signal generator at approximately 100
The coaxial cable, an element of the device, may be of any microvolts at the measuring frequency.
suitable impedance and need not be terminated in its 2) Measurement of the voltage on the terminal with the
characteristic impedance. The purpose of the device is RN meter connected directly to the terminal.
to minimize the dividing effect of the bushing capaci- 3) MIeasurement, with the same RN meter, of the volt-
tances and to convey the RIV to the RN meter with age appearing in the test circuit at the location where
minimum attenuation. the RN meter will be connected during the corona
External shielding, as required, shall be used to avoid air measurement on the transformer. A second RN meter
corona. may be used, provided its relationship to the first RN
The test circuit components connected to the winding meter has been established.
under test will attenuate the observed RIV measure- 4) It shall be established that this calibration ratio re-
ments and add to the RIV background level. When the mains valid over the RIV range of interest.
voltage is applied directly to the winding under test, radio-
frequency chokes or tuned filters shall be used to isolate The ratio of the voltage measured with the RN meter at
the transformer under test and the RIV measuring circuit the terminal to the voltage measured with the RN meter
from the rest of the test circuit. at the normal location in the circuit, which has been
In either case, whether the coupling capacitor or the selected for the corona test on the transformer, will be
bushing capacitance tap is used to make the measurement, applied as a correction factor to the RIV reading obtained
it is niecessary to establish by a calibration procedure, the during the corona test to determine the actual RIV at the
relationship between the RIV at the terminal of the wind- terminal of the winding under test.
Abstract-The progress made to date in corona testing trans- INTRODUCTION AND BACKGROUND
formers at the factory is reviewed and the importance of sonic
detection and location of corona sources is shown. Major improve- THE CONCLUSION of the first phase of a program to
ments in sonic techniques are reported. Test curves of RIV vs. develop a practical transformer corona test was re-
transformer test voltage are given for units having defects. The ported in 1958 [1]. This work had been undertaken in
various corona test proposals being considered by the industry are recognition of the continuing trend to higher voltages,
described and discussed. The best assurance of product quality is
stated to be a corona test, using RIV and advanced sonic techniques, larger unit ratings and further reductions in insulation
made at full transformer induced test voltage with a limit of 1000 levels.
microvolts. The second phase of the program was reported in 1960
[2] and specific suggestions on the method, the test voltage
Paper 31 TP 66-79, recommended and approved by the Trans- level and limiting values were made. It was concluded that
formers Committee of the IEEE Power Group for presentation at the using a variation of the NEMTA RIV procedure, with the
IEEE Winter Power Meeting, New York, N. Y., January 30-Feb-
ruary 4, 1966. Manuscript submitted October 29, 1965; made avail- bushing capacitance tap, it was feasible to make RIV
able for printing December 13, 1965. measurements at full induced test voltage with a limit of
The authors are with the General Electric Company, Pittsfield,
Mass. 1000 microvolts.
893