SYSTEMS INPUT
Heat Detector Activation
Smoke Detector Activation
Deluge System Alarm Signal
10 Fire Alarm AC Power Failure
Manual Call Point Activation
Detector Removal From Base
11 Fire Alarm System Low Battery
protection systems)
CAUSE AND EFFECT MATRIX
Smoke Detector Activation -Preaction panel 3
Smoke Detector Activation -Preaction panel 2
Smoke Detector Activation -Preaction panel 1
Zone Control Valve Activation (Tamper Switch)
sequence of operations of life safety systems & fire
(One method to define and determine the required
A
Activate Common Alarm Signal Indicator
B
Actuate Audible Alarm Signal
C
Activate Common Supervisory Signal Indicator
D
Actuate Audible Supervisory Signal
E
Activate Common Trouble Signal Indicator
F
Actuate Audible Common Trouble Signal
CONTROL UNIT ANNUNCIATION
Activate Building Alarm
H
Activate Voice Evacuation System
I
Display/Print Change of Status
J
Indicate Fire Alarm Signal on Mimic Panel
K
Indicate General Supervisroy Signal on Mimic Panel
NOTIFICATION
Indicate General Trouble Signal on Mimic Panel
M
24/7 Panel
N
Building FACP
O
curtain fully open
P
FIRE display on on access control
Q
Shutdown of Music System
K-28-FAY HEALTH POLY CLINIC SYSTEMS OUTPUT
Shutdown All Air Handling Units (FCUs)
S
Release Magnetic Locks of all door Doors
T
Release to Open of the Sliding Door
U
Release to Open of the Sliding Door
V
Emergency and exit lights
REQUIRED FIRE SAFETY CONTROL
W
`