R32 & R410A: PIPE THICKNESS


The recommended minimum pipe thickness of single split and multi-split refrigerant pipe:
Recommended Minimum
Refrigerant Pipe Diameter (mm / in)
Refrigerant Pipe Thickness (mm)
6.35 / 1/4”
9.52 / 3/8”
12.70 / 1/2” 0.61
15.88 / 5/8”
19.05 / 3/4”

R32 MULTI SPLIT INVERTER

MKM65PVM MKM80PVM MKM95PVM MKM105PVM

Max. pipe Total 60 70 70 80


length (m) For one room 30
Between
Max. indoor and 15
elevation outdoor units
(m) Between
7.5
indoor units

R410A MULTI SPLIT INVERTER

3MKS50ESG 3MKS71ESG 4MKS80ESG 5MKS100LSG

Max. pipe Total 50 60 70 80


length (m) For one room 25 30
Between
Max. indoor and 15
elevation outdoor units
(m) Between
7.5
indoor units
\ D’Info NO. CS 20-02 28 April 2020
No. CS 20-01

Example: Condominium with 4 rooms, installed with multi-split MKM105PVM

*Piping length for simulation only

Bedroom A 2 m < 30 m
Bedroom B 3 m < 30 m
Bedroom C 4 m < 30 m
Max. piping length (m)
Bedroom D 5 m < 30 m
Living Room 8 m < 30 m
Total 2+3+4+5+8 = 22 m < 80 m
\ D’Info NO. CS 20-02 28 April 2020
No. CS 20-01

R32 SINGLE SPLIT INVERTER


WALL MOUNTED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.0 FTKG28QV1L RKG28FV1D 9,500 (4,400-10,200) 20 15 6.35 / 1/4” 9.52 / 3/8”
1.5 FTKG35QV1L RKG35FV1D 12,100 (4,400-13,000) 20 15 6.35 / 1/4” 9.52 / 3/8”
2.0 FTKG50QV1L RKG50CV1D 19,000 (4,700-21,200) 30 20 6.35 / 1/4” 12.70 / 1/2”
2.5 FTKG60QV1L RKG60CV1D 22,500 (5,800-23,500) 30 20 6.35 / 1/4” 12.70 / 1/2”
3.0 FTKU71AV1L RKU71FV1D 24,000 (6,600–24,500) 30 20 6.35 / 1/4” 12.70 / 1/2”
4.0 FAA100BVMA RZF100CVM 34,100 (17,100-38,200) 50 30 9.52 / 3/8” 15.88 / 5/8”

CEILING CASSETTE
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
2.0 FCF50CVM RZF50CVM 17,100 (10,900-19,100) 50 30 9.52 / 3/8” 15.88 / 5/8”
2.5 FCF60CVM RZF60CVM 20,500 (10,900-20,500) 50 30 9.52 / 3/8” 15.88 / 5/8”
3.0 FCF71CVM RZF71CVM 24,200 (10,900-27,300) 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FCF100CVM RZF100CVM 34,100 (17,100-38,200) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FCF125CVM RZF125CVM 42,700 (19,500-47,800) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.5 FCF140CVM RZF140CVM 47,800 (21,200-52,900) 50 30 9.52 / 3/8” 15.88 / 5/8”

CEILING DUCTED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
2.0 FBA50BVMA RZF50CVM 17,100 (10,900-19,100) 50 30 9.52 / 3/8” 15.88 / 5/8”
2.5 FBA60BVMA RZF60CVM 20,500 (10,900-20,500) 50 30 9.52 / 3/8” 15.88 / 5/8”
3.0 FBA71BVMA RZF71CVM 24,200 (10,900-27,300) 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FBA100BVMA RZF100CVM 34,100 (17,100-38,200) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FBA125BVMA RZF125CVM 42,700 (19,500-47,800) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.5 FBA140BVMA RZF140CVM 47,800 (21,200-52,900) 50 30 9.52 / 3/8” 15.88 / 5/8”

CEILING EXPOSED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
2.0 FHA50BVMA RZF50CVM 17,100 (10,900-19,100) 50 30 9.52 / 3/8” 15.88 / 5/8”
2.5 FHA60BVMA RZF60CVM 20,500 (10,900-20,500) 50 30 9.52 / 3/8” 15.88 / 5/8”
3.0 FHA71BVMA RZF71CVM 24,200 (10,900-27,300) 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FHA100BVMA RZF100CVM 34,100 (17,100-38,200) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FHA125BVMA RZF125CVM 42,700 (19,500-47,800) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.5 FHA140BVMA RZF140CVM 47,800 (21,200-52,900) 50 30 9.52 / 3/8” 15.88 / 5/8”
\ D’Info NO. CS 20-02 28 April 2020
No. CS 20-01

R32 SINGLE SPLIT NON INVERTER


WALL MOUNTED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.0 FTV28PV1L RV28FV1P 9,500 25 15 6.35 / 1/4” 9.52 / 3/8”
1.5 FTV35PV1L RV35FV1P 12,000 25 15 6.35 / 1/4” 9.52 / 3/8”
2.0 FTV50PV1L RV50CV1P 18,000 30 15 6.35 / 1/4” 12.70 / 1/2”
2.5 FTV60PV1L RV60CV1P 22,000 30 15 6.35 / 1/4” 12.70 / 1/2”

CEILING CASSETTE
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
2.0 FCC50AV1M RC50AV1M 18,500 35 20 6.35 / 1/4” 12.70 / 1/2”
2.5 FCC60AV1M RC60AV1M 24,000 35 20 6.35 / 1/4” 12.70 / 1/2”
3.0 FCC85AV1M RC85AV1M 30,000 50 30 9.52 / 3/8” 15.88 / 5/8”
3.5 FCC100AV1M RC100AV1M 36,000 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FCC125AV1M RC125AY1M 42,000 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FCC140AV1M RC140AY1M 48,000 50 30 9.52 / 3/8” 15.88 / 5/8”

CEILING DUCTED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
2.0 FDMC50AV1M RC50AV1M 18,500 35 20 6.35 / 1/4” 12.70 / 1/2”
2.5 FDMC60AV1M RC60AV1M 23,500 35 20 6.35 / 1/4” 12.70 / 1/2”
3.0 FDMC85AV1M RC85AV1M 30,000 50 30 9.52 / 3/8” 15.88 / 5/8”
3.5 FDMC100AV1M RC100AV1M 36,000 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FDMC125AV1M RC125AY1M 42,000 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FDMC140AV1M RC140AY1M 48,000 50 30 9.52 / 3/8” 15.88 / 5/8”
6.0 FDMC160AV1M RC160AY1M 55,000 50 30 9.52 / 3/8” 19.05 / 3/4”

CEILING EXPOSED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
2.0 FHC50AV1M RC50AV1M 18,500 35 20 6.35 / 1/4” 12.70 / 1/2”
2.5 FHC60AV1M RC60AV1M 23,500 35 20 6.35 / 1/4” 12.70 / 1/2”
3.0 FHC85AV1M RC85AV1M 29,500 50 30 9.52 / 3/8” 15.88 / 5/8”
3.5 FHC100AV1M RC100AV1M 36,000 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FHC125AV1M RC125AY1M 42,000 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FHC140AV1M RC140AY1M 46,000 50 30 9.52 / 3/8” 15.88 / 5/8”
6.0 FHC160AV1M RC160AY1M 55,000 50 30 9.52 / 3/8” 19.05 / 3/4”
\ D’Info NO. CS 20-02 28 April 2020
No. CS 20-01

R410A SINGLE SPLIT INVERTER


WALL MOUNTED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.0 FTK10QV1L RK10FV1 9,500 (4,400-10,200) 20 10 6.35 / 1/4” 9.52 / 3/8”
1.5 FTK15QV1L RK15FV1 12,100 (4,400-13,000) 20 10 6.35 / 1/4” 12.70 / 1/2”
2.0 FTK20QV1L RK20CV1 18,500 (4,700-21,200) 30 10 6.35 / 1/4” 12.70 / 1/2”
2.5 FTK25QV1L RK25CV1 22,000 (5,800-23,000) 30 10 6.35 / 1/4” 15.88 / 5/8”
3.0 FTKS71JVMG9 RKS71JVMG 24,200 (9,200-29,700) 30 15 9.52 / 3/8” 15.88 / 5/8”
3.5 FTKS85JVMG9 RKS85JVMG 29,000 (10,200-33,100) 30 20 9.52 / 3/8” 15.88 / 5/8”
4.0 FAQ100CVEA RZR100MVM 34,100 (17,100-38,200) 50 30 9.52 / 3/8” 15.88 / 5/8”

CEILING CASSETTE
COOLING CAPACITY. MAX. PIPE MAX. PIPE SIZE (mm)
HP FCU CU
at 19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.0 FFR10CV1 RR10DV1 9,500 (3,650-12,000) 15 10 6.35 / 1/4” 9.52 / 3/8”
1.5 FFR15CV1 RR15DV1 12,500 (4,800-14,000) 15 10 6.35 / 1/4” 12.70 / 1/2”
2.0 FCQ50KAVEA RZR50MVM 17,100 (7,900-19,100) 50 30 9.52 / 3/8” 15.88 / 5/8”
2.5 FCQ60KAVEA RZR60MVM 20,500 (8,900-21,500) 50 30 9.52 / 3/8” 15.88 / 5/8”
3.0 FCQ71KAVEA RZR71MVM 24,200 (10,900-27,300) 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FCQ100KAVEA RZR100MVM 34,100 (17,100-38,200) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FCQ125KAVEA RZR125MVM 42,700 (19,500-47,800) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.5 FCQ140KAVEA RZR140MVM 47,800 (21,200-52,600) 50 30 9.52 / 3/8” 15.88 / 5/8”

CEILING DUCTED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.0 FDMR10CV1M RR10DV1 9,200 (4,100-10,500) 15 10 6.35 / 1/4” 9.52 / 3/8”
1.5 FDMR15CV1M RR15DV1 12,500 (4,600-14,000) 15 10 6.35 / 1/4” 12.70 / 1/2”
2.0 FBQ50EVE RZR50MVM 17,100 (7,900-19,100) 50 30 9.52 / 3/8” 15.88 / 5/8”
2.5 FBQ60EVE RZR60MVM 20,500 (8,900-21,500) 50 30 9.52 / 3/8” 15.88 / 5/8”
3.0 FBQ71EVE RZR71MVM 24,200 (10,900-27,300) 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FBQ100EVE RZR100MVM 34,100 (17,100-38,200) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FBQ125EVE RZR125MVM 42,700 (19,500-47,800) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.5 FBQ140EVE RZR140MVM 47,800 (21,200-52,600) 50 30 9.52 / 3/8” 15.88 / 5/8”

CEILING EXPOSED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.5 FLR15EV1 RR15DV1 12,500 (5,400-14,000) 15 10 6.35 / 1/4” 12.70 / 1/2”
2.0 FHQ50DAVMA RZR50MVM 17,100 (7,900-19,100) 50 30 9.52 / 3/8” 15.88 / 5/8”
2.5 FHQ60DAVMA RZR60MVM 20,500 (8,900-21,500) 50 30 9.52 / 3/8” 15.88 / 5/8”
3.0 FHQ71DAVMA RZR71MVM 24,200 (10,900-27,300) 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FHQ100DAVMA RZR100MVM 34,100 (17,100-38,200) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FHQ125DAVMA RZR125MVM 42,700 (19,500-47,800) 50 30 9.52 / 3/8” 15.88 / 5/8”
5.5 FHQ140DAVMA RZR140MVM 47,800 (21,200-52,600) 50 30 9.52 / 3/8” 15.88 / 5/8”
\ D’Info NO. CS 20-02 28 April 2020
No. CS 20-01

R410A SINGLE SPLIT NON INVERTER


WALL MOUNTED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.0 FTN10PV1L RN10FV1 9,500 25 15 6.35 / 1/4” 9.52 / 3/8”
1.5 FTN15PV1L RN15FV1 12,000 25 15 6.35 / 1/4” 12.70 / 1/2”
2.0 FTN20PV1L RN20CV1 18,000 30 15 6.35 / 1/4” 12.70 / 1/2”
2.2 FTN25PV1L RN25CV1 22,000 30 15 6.35 / 1/4” 15.88 / 5/8”
2.5 FTN25PV1L RN25CHV1 24,000 35 15 6.35 / 1/4” 15.88 / 5/8”
3.0 FTN30PSV1L RN30CV1 30,000 45 25 9.52 / 3/8” 15.88 / 5/8”
3.5 FTN35PSV1L RN35DV1 33,000 50 30 9.52 / 3/8” 15.88 / 5/8”

CEILING CASSETTE
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.0 FFN10CV1 RN10FV1 9,500 20 10 6.35 / 1/4” 9.52 / 3/8”
1.5 FFN15CV1 RN15FV1 12,500 20 10 6.35 / 1/4” 12.70 / 1/2”
2.0 FCN20FV1 RN20CV1 18,500 30 15 6.35 / 1/4” 12.70 / 1/2”
2.5 FCN25FV1 RN25CV1 23,000 30 15 6.35 / 1/4” 15.88 / 5/8”
2.8 FCN30FV1 RN28CV1 28,000 45 25 9.52 / 3/8” 15.88 / 5/8”
3.0 FCN30FV1 RN30CV1 30,000 45 25 9.52 / 3/8” 15.88 / 5/8”
3.5 FCN35FV1 RN35DV1 36,000 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FCN40FV1 RN40DY1 42,000 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FCN50FV1 RN50DY1 46,000 50 30 9.52 / 3/8” 15.88 / 5/8”

CEILING DUCTED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.0 FDBN10CV1 RN10FV1 9,000 20 10 6.35 / 1/4” 9.52 / 3/8”
1.5 FDBN15CV1 RN15FV1 12,000 20 10 6.35 / 1/4” 12.70 / 1/2”
2.0 FDBN20CV1 RN20CV1 18,000 30 15 6.35 / 1/4” 12.70 / 1/2”
2.5 FDBN25CV1 RN25CV1 21,000 30 15 6.35 / 1/4” 15.88 / 5/8”
2.8 FDMN30CV1 RN28CV1 28,000 45 25 9.52 / 3/8” 15.88 / 5/8”
3.0 FDMN30CV1 RN30CV1 30,000 45 25 9.52 / 3/8” 15.88 / 5/8”
3.5 FDMN40CV1 RN35DV1 36,000 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FDMN40CV1 RN40DY1 42,000 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FDMN50CV1 RN50DY1 47,000 50 30 9.52 / 3/8” 15.88 / 5/8”
6.0 FDMN60CV1 RN61DY1 55,000 35 15 9.52 / 3/8” 19.05 / 3/4”
\ D’Info NO. CS 20-02 28 April 2020
No. CS 20-01

R410A SINGLE SPLIT NON INVERTER


CEILING EXPOSED
COOLING CAPACITY. at MAX. PIPE MAX. PIPE SIZE (mm / in)
HP FCU CU
19°CWB (btu/hr) LENGTH (m) ELEVATION (m) LIQUID GAS
1.5 FHN15CBV1 RN15FV1 12,500 20 10 6.35 / 1/4” 12.70 / 1/2”
2.0 FHN20CBV1 RN20CV1 18,000 30 15 6.35 / 1/4” 12.70 / 1/2”
2.5 FHN25CBV1 RN25CV1 21,000 30 15 6.35 / 1/4” 15.88 / 5/8”
2.8 FHN30CBV1 RN28CV1 27,000 45 25 9.52 / 3/8” 15.88 / 5/8”
3.0 FHN30CBV1 RN30CV1 29,000 45 25 9.52 / 3/8” 15.88 / 5/8”
3.5 FHN35CBV1 RN35DV1 35,000 50 30 9.52 / 3/8” 15.88 / 5/8”
4.0 FHN40CBV1 RN40DY1 41,000 50 30 9.52 / 3/8” 15.88 / 5/8”
5.0 FHN50CBV1 RN50DY1 44,500 50 30 9.52 / 3/8” 15.88 / 5/8”
6.0 FHN62CV1 RN61DY1 55,000 35 15 9.52 / 3/8” 19.05 / 3/4”