STATIONS
1
100% reusable PE material
Safe to maintain
TECHNICAL
5
STRONG small pumping stations are for pumping waste
water, storm water, and drainage water in places
where installing gravity-flow piping is not possible CHARACTERISTICS
or reasonable. From us, even the most demanding
customers will find suitable pumping stations, pumps,
and control cabinets.
6
Aside from STRONG small pumping stations we also
offer large pumping stations, booster pumping stations, INSTALLATION
tanks, septic tanks, etc. of the same brand.
OPERATION 8
MAINTENANCE 9
ACCESSORIES 10
WARRANTY 11
3
IWS SMALL PUMPING STATION
PRODUCT RANGE
A PUMPING STATION
D1
H3
(D1, mm);
• inlet pipe height (H3, mm) and diameter (D2, mm);
• type of water to be pumped (waste water, storm water, etc.);
• pump parameters – flow rate (Q, l/s) and head (H, mVs);
• number of pumps;
• a plastic cover for green areas / cast iron cover for
traffic areas.
4
IWS SMALL PUMPING STATION
TECHNICAL CHARACTERISTICS
STRONG pumping stations are made means pumping stations manufactured it is resistant to mechanical damage
of PE-HD (high-density polyethylene). using PE do not decompose, rust or that may occur when installing or
Nowadays, PE is a common material corrode due to chemical or electrical using the system. This is important for
used for manufacturing pumping sta- reactions, and nothing is released or preventing waste water leakage into
tions, tanks, wells and pressure pipes. dissolved into the environment. The soil or groundwater from getting into
PE is an elastic and durable type of tank cylinder of the pumping station the pumping station. Additionally, the
plastic. Under normal conditions of use is always manufactured with a ring tank cylinder is double-walled, making
PE is a chemically inert plastic, which stiffness of at least SN2 (2 kN/m²), so it absolutely leak-proof.
Cover: PE, with 50 mm Service opening: PE, with Tank cylinder: double-walled PE Auto-coupling
of thermal insulation 50 mm of thermal insulation with ring stiffness SN2 (GG25 with epoxy coating)
5
IWS SMALL PUMPING STATION
INSTALLATION
INSTALLING THE
PUMPING STATION
1. The trench for the pumping station
needs to be with a diameter at least
1.2 meters wider than the diameter of
the pumping station. This is to leave
enough room for compacting the back-
fill around the pumping station.
2. The bottom of the trench is filled
with a 300 mm layer of sand and then
compacted.
3. Refer to the instructions given in
chapter: “Anchoring” when anchoring
the pumping station. min 600 mm
6
IWS SMALL PUMPING STATION
INSTALLATION
REQUIREMENTS FOR THE Sand and gravel mixtures imum level of groundwater reaches
FILLING MATERIAL Sand and gravel mixtures may be used the ground level). That way buoyancy
if the components comply with the is equal to the bulk of the pumping
Sand, gravel, and crushed stone are
above requirements for gravel, crushed station. Small pumping stations have a
suitable filler materials. The filler must
stone, and sand. Sand and gravel mix- protruding base plate wide enough that
be clean, freely flowing, and must not
tures must be compacted as it does not need an additional anchor-
contain ice, snow, clay, organic sub-
instructed below. ing plate. In order to ensure correct
stances, or large or heavy objects that
anchoring, correct backfill materials
may damage the pumping station when
must be used and diligently compacted
falling onto it. The minimum required
ANCHORING according to the instructions given in
packing density is 1,500 kg/m³.
chapter: “Backfilling”.
Surface water buoyancy
Gravel The pumping station must be anchored
Gravel particle size must not be less in order to neutralise the buoyancy
than 3 mm or more than 20 mm. of surface water and to ensure that
the pumping station remains securely
Crushed stone
Crushed stone particle size must not
in place. Anchoring must be done in
such a way that the weight of the !
be less than 3 mm or more pumping station and the soil resting on
than 16 mm. the protruding edges of the anchoring
The pumping station must not be
base plate are at least equal to the
installed on soil with a low load-
Sand buoyancy. Calculated counterweight
bearing capacity. In such cases, the
Particle size must not exceed 3 mm. depends on the weight of the empty
backfill layer must be separated with
pumping station and the maximum
fibare cloth to keep it from mixing
level of the groundwater (the safest
with soil.
bet would be to guess that the max-
BACKFILLING
The trench of the pumping station 100 mm
is filled on all sides by 300 mm thick 300 mm
layers of gravel, crushed stone or sand,
compacting each layer to 95% of the 300 mm
soil’s natural density.
300 mm
In cases of high groundwater level or
otherwise wet and heavy soil (e.g. clay 300 mm
soil), use only gravel or crushed stone
300 mm
as backfill material. Take special care
when compacting near the pumping 300 mm
station’s pipe connections to avoid
leaving any gaps. 300 mm
7
IWS SMALL PUMPING STATION
INSTALLATION
INSTALLATION UNDER
TRAFFIC AREA Cast iron cover
To avoid damages from traffic load on a
Road pavement
pumping station installed under traffic
area, the pumping station must be Reinforced concrete plate
covered by a 150 mm thick reinforced 50 mm thermal
concrete load balancing plate. The plate insulation plate
must extend at least 300 mm beyond
the pumping station in all directions. All
pumping stations under traffic areas Backfill
must have a cast iron cover that is
connected to the service opening with
a telescopic tube. This prevents the
traffic load from reaching the service
opening of the pumping station.
OPERATION
8
IWS SMALL PUMPING STATION
MAINTENANCE
We recommend doing the following prevent the pumps from possibly 4. Clean the float switches and the level
maintenance at least once per year. becoming unusable in the future. sensor from sediments. Visually
Contact a company providing pump inspect the condition of the pumps’
1. Lift the pump together with the
maintenance services. power cables.
auto-coupling by the lifting chain,
then wash the pumps with a 2. Clean the inner walls and the bottom 5. After completing the maintenance
pressure jet and assess their of the pumping station from works above, lower the pumps with
condition. Maintain the pumps sediments using a pressure jet. The the auto-couplings back down by the
according to the manufacturer’s cleaning interval may be shorter or lifting chains and then check their
instructions (technical passport). If longer depending on the sediments functioning in operating conditions.
the pumps are working below their collecting in the pumping station.
intended productivity or emit noises
3. Clean the inside of the non-return
that were not there when the pumps
valves from the collected debris and
were in order, we recommend trying
sediments. To do so, close the ball
to eliminate the faults in order to
valves and open the cover of the
non-return valve.
SAFETY
1. The employer of the pumping 4. It is strictly prohibited to perform 7. If the pump has a plug connection,
station’s maintenance personnel any works inside the pumping its earthed power outlet must be
must instruct the maintenance station alone! installed above water level. The
employees about electrical hazards power cable of no-plug pumps
5. Close all inlets to the pumping
and toxic exhaust gases and must must be connected by a qualified
station for the duration of
provide them with necessary specialist.
maintenance works!
protective equipment.
8. No damage claims are accepted if
6. Before commissioning the pumping
2. Switch off the pumps at the control safety requirements are ignored.
station, properly qualified personnel
cabinet before starting maintenance
must verify that all applicable safety
of the pumping station!
regulations are fulfilled. The
3. The pumping station must be earthing, neutral line and the
ventilated for at least 5 minutes equipotential connections must
before entering the pumping station. comply with regulations for
electrical installations and must be
inspected by qualified personnel.
9
IWS SMALL PUMPING STATION
ACCESSORIES
ALARM DEVICE
As an accessory to small pumping The level sensor is adjusted to a If the water level rises and reaches the
stations, we offer a wireless alarm suitable height where it will check the level sensor, the tank full alarm will
device such as TankCheck TC-412. level of the water in the pumping activate and the red “FULL” indicator
The wireless water level sensor station and transmit the data to the lamp on the control panel will start
Tank-Check TC412 has two parts: control panel. On the control panel the flashing and the control panel will
green “OK” indicator lamp is on as long sound an alarm.
1. a transmitter installed on the inner as the water level in the pumping
wall of the service opening with a When emptying the pumping station,
station has not yet reached the set
sensor monitoring the water level in the be sure to check the level sensor and,
sensor level.
pumping station; if necessary, remove from it any
impurities that may affect its work.
2. a control panel installed at a suitable
location in the building.
Control panel
Transmitter
10
IWS SMALL PUMPING STATION
WARRANTY
Innovative Water Systems assumes 2. Validity terms of the warranty 3. The warranty does not include:
responsibility for the equipment’s 2.1. The warranty is valid only if the 3.1. Training for installation, mainte-
properties and for elimination of regulations in force and the installation nance and use of the equipment.
shortcomings that become apparent and operation manuals required to be 3.2. Repairs of transport damage and
during the equipment’s use. The followed upon installation, use and other mechanical damage (caused by
warranty terms stem from the maintenance of the equipment are vandalism, lightning, fire, etc.).
legislation of the Republic of Estonia, followed. The warranty will be valid if
The warranty does not cover short-
and the warranty is first and foremost the equipment has been maintained
comings caused by insufficient
based on the manufacturers’ warran- regularly and used according to the
maintenance, incorrect installation and
ties as long as they do not conflict with instructions of the manufacturer.
repairs, or normal wear. The warranty
the laws of the Republic of Estonia. The 2.2. If the identification of a fault
is also void if the equipment has been
warranty includes shortcomings of requires that the equipment be dug
modified.
manufacturing, materials or design of out, this must be done in the presence
the equipment and its individual of the representative of the
elements. manufacturer.
2.3. The warranty does not include
1. General warranty terms
damage caused to third parties
1.1. The warranty is valid for 2 years
because of a faulty product; it also
i.e. 24 months provided that the
does not include loss of revenue or any
product is used as intended.
other similar loss.
1.2. The warranty period starts from
2.4. In case of a fault becoming
the date of delivery of the product.
apparent, the equipment shall be
repaired, not replaced as a whole.
11