The minimum cement content for compacted concrete of pavers shall not be less than 380 Kg / cum.
The cement used in the manufacture of high quality pre-cast concrete paving blocks shall be
conforming to IS 12269 (53 grade ordinary Portland cement) or IS 8112(43 grade ordinary Portland
cement).
The maximum water cement ratio for pavers concrete shall not be more than 0.40
The fine and coarse aggregates shall consist of naturally occurring crushed or uncrushed materials,
which apart from the grading requirements comply with IS 383-1970. The fine aggregates used shall
contain a minimum of 25% natural silicon sand. Lime stone aggregates shall not be used. Aggregates
shall contain no more than 3% by weight of clay & shall be free from deleterious salt sand
contaminants. Zone iv sand shall not be acceptable. Course aggregate shall be 10 mm and below.
The pigment shall be used only on wearing and top surface and through out the paver block. The
pigment used shall not be more than 10% of weight of cement used in the wearing course layer.
However, use of pigment shall in no way alter the required strength of the paver block.Pigment used
for colouring paver blocks shall have durable colour. It shall not contain matters detrimental to
concrete. The pigment shall not contain Zinc compound. Lead pigment shall not be used.
The compressive strength requirement of concrete paver block shall be minimum 47.2 MPa (N /
sqmm) for 28 days (Testing as per IS;15658) after applying the correction factor as per IS-15658;
2006. No lower tolerance limit in compressive strength shall be allowed.
Compressive Strength
Abrasion Resistance
Maximum 2.0 mm
Water Absorption
Maximum 5.80%
Mix Calculation: –
4. Calculation of water: –
400 X 0.4 = 160 kg Which is less than 186 kg (As per Table No. 4, IS: 10262)
Hence o.k.
5. Calculation for C.A. & F.A.: – As per IS : 10262 , Cl. No. 3.5.1
Where
V = absolute volume of fresh concrete, which is equal to gross volume (m3) minus the volume of
entrapped air ,
(fa) , (ca) = total mass of fine aggregate and coarse aggregate (kg) per m3 of
Sfa , Sca = specific gravities of saturated surface dry fine aggregate and Coarse aggregate
respectively.
As per Table No. 3 , IS-10262, for 20mm maximum size entrapped air is 2% .
=> Fa = 660.2 kg
20mm = 701 kg .
10mm = 467 kg .
Cement = 400 kg
Water = 160 kg
Recron 3S = 900 gm
Source:
https://law.resource.org/pub/in/bis/S03/is.15658.2006.pdf
प्रति,
मा. मुख्याधिकारी
लोणावळा नगरपरिषद,पुणे.
विषय : लोणावळा नगरपरिषद हद्दीतील आरक्षण क्र. ६६ आशीर्वाद हॉस्पिटल समोरील
शॉपिंग कॉम्प्लेक्स विकसित करणे.
२) इस्कॉन कन्स्ट्रक्शन यांनी Strutform Consultant यांना २३/०९/२१ रोजी सादर केलेले
बिल
३) लोनप मख्
ु याधिकारी यांना २३/०९/२१ रोजी सादर केलेले पत्र
४)लोनप मख्
ु याधिकारी यांना ११/१०/२१ रोजी सादर केलेले पत्र
सन्मानीय महोदय,
उपरोक्त विषय आणि संदर्भास अनुसरून आम्ही आपणास हे पत्र कळवित आहोत, की
सदर कामाच्या प्रथम दे यकाची गेले तीन महिने सातत्याने पाठपुरवठा करीत आहोत त्या
संदर्भात आम्ही आपणास वेळोवेळी पत्र दिली तसेच दि १५/११/२०२१ रोजी समक्ष भेटू न बील
अदा करणेबाबत विनंती के ली होती, आपण शहर अभियंता यांना बोलवून दे यक अदा
करण्यासंबंधी आवश्यक कार्यवाही करण्याच्या सूचना दिल्या होत्या. तरी अद्याप आमचे बिल
रे कॉर्ड झाले नाही. सल्लागाराकडून बिल मंजूर करणेबाबत शिफारस होऊनही अद्याप देयक अदा होत
नाही. निविदा शर्तीनुसार महिन्यात १ देयक अदा करावयास हवे असते. सल्लागारांकडू न देयक तपासणी करून
आले तरी दे यक अदा करण्यासाठी विलंब करण्यात होत आहे . तरी याबाबत आपण योग्य
ती कार्यवाही करावी. या विलंबामळ
ु े आमचे मोठे नक
ु सान तर होतच आहे परं तु त्याचा
कामाच्या प्रगतीवर दे खील याचा विपरीत परिणाम होत आहे .
सबब बील तातडीने अदा करण्यात यावे हि विनंती.
आपला विश्वासू