You are on page 1of 14

HTJS-V Transformer Tan-Delta Tester

Introduction

The HTJS-V high-voltage dielectric loss test device is a high-precision instrument that
automatically measures the dielectric loss tangent and capacitance of various
high-voltage power equipment on-site in power plants and substations. Due to the use of
frequency conversion technology, it can ensure accurate measurement under strong
electric field interference. The instrument adopts Chinese menu operation, and the
microcomputer automatically completes the whole process of measurement.
The instrument is also suitable for measuring tgδ and capacitance of high-voltage
electrical equipment in workshops, laboratories, and scientific research units; it is more
convenient, simple, and accurate for the loss test of insulating oil.
The instrument can be used to measure the high-voltage electrical equipment that is
not grounded or directly, and can also measure the tgδ of the capacitive voltage
transformer and the capacitance of the main capacitors C1 and C2.
The instrument is equipped with a high-voltage step-up transformer, and has adopted
safety protection measures such as zero-crossing and lightning protection. During the test,
high voltages of different levels of 0.5KV to 10kV are output, and the operation is simple
and safe

Features

. High voltage short circuit protection


· CVT overvoltage protection
· Protection for equipment not well grounded

Parameters
1、High voltage output: 0.5 ~10kV,

Add 500V for each gear, there are 20 gears in total, capacity :

1500VA

2、Accuracy: tgδ: ±(reading*1%+0.06%)

Cx: ±(reading*0.5%+5PF)

3、Resolution: tgδ:0.001% Cx:0.001pF

4、Measuring range: 0.001% < tgδ < 100%

Internal high voltage:3pF~60000pF/10kV60pF~1µF/0.5kV

External high voltage:3pF~1.5µF/10kV 60pF~30µF/0.5kV

5、Power: AC 220V 士 10% 50 士 1Hz

6、Measure method:a.single frequency:45Hz、50Hz、55Hz、 60Hz 、 65Hz

b.Different frequency:45/55Hz、55/65Hz、47.5/52.5Hz Automatic

double frequency conversion

7、Harmonic adaptation: ≤3%

8、Use condition: -15℃-50℃ Humidity<80%

9 、 Diemension: 460(L)×345(W)×345(H)

10、Weight: 35 kg

Details Images
HTJS—V Tan Delta Tester
HTJS—V Weight: 35 kg

HT J S - V

Accessories of a product

CVT nput cable