Technical Proposal for Partial Discharge Detection Equipment

1. Standard
GB/T16927.1 Part One General Definition and Test Requirements, High Voltage Test Technique
GB/T16927.2 Part Two Measurement System, High Voltage Test Technique
GB/T7354 Partial Discharge Measurement
DL/T846.4 Part Four Partial Discharge Detector by Pulse Current Method, Terms of High Voltage
Test Equipment General Technique
GB/T311.1 Part One Definition, Principle and Rules, Insulation Coordination

2. Products List
No Products Name Products Description Q`ty Remarks
JF-A04D Partial Discharge Detector
1 JF-A04D 1pc
(Touch Screen)
2 Digital external calibrator JZF-10N 1pc
3 Input unit 4# 3pcs
4 Partial Discharge Signal Filter Adapter PDLB-1 3pcs
5 Coupling capacitor OWF-100kV/1000pF 3pcs
6 Three-phase frequency doubling power filter LBS-60 1pc
7 The power cable -- 1pc
8 High frequency line -- 1pc
9 Partial discharge signal 8m 3pcs
10 Red, black signal wirings -- 1pc
11 Charger -- 1pc

1. JF-A04D Partial Discharge Detector (Touch Screen)

- 1 -
Main Technical Data:
Model: JF-A04D
Channels: 4 Channel
Capacitance of test product: 6pF--250μF
Measuring range: 0.1pC-10000nC
Display unit: 10.1 inch capacitive touch screen
Measuring sensitivity: 0.01pC
Accuracy: ±5%
With 10.1 inch touch screen, one button automatic calibration, high
Function: voltage test voltage divider ratio can be set, serial communication upload
test data
On low frequency :10kHz、20kHz、40kHz
Amplifier:
On high frequency :80kHz、200kHz、300kHz
6 grades of gross adjustment. Gain difference between grades is 20±1dB,
Amplifier Gain adjusting:
fine adjusting range >20dB
(1) Window width: adjustable, 5 °to 170 °at 50 Hz.
Time window: (2) window position: each window can be rotated 0 °to 170 °
(3) two time windows can be opened separately or simultaneously.
Frequency: 50/60Hz、100Hz、150Hz、200Hz、400Hz
Time base of ellipse scan: Turn: 30º per grade, revolution≥120°
display ways: Ellipse -- Expand -- Line
Display: Digital meter with 3.5 bits LED digital display; precision better
Measuring voltmeter:
than ±5%(with full graduation)
Zero mark : The zero flag is consistent with all ellipse scan frequencies
Power Source: 220V/60Hz
Function: To measure the PD value of tested object

2. JZF-10N Digital External Calibrator

- 2 -
Main Technical Data:
Model: JZF-10N
The ranges to output electric
5pC、10pC、20pC、50pC、100pC、200pC、500pC
charge:
Polarity: Positive and Negative alternative
Repeat frequency: 50、100、200、500、1200Hz
Frequency accuracy: <1%
Pulse rise edge time: <60nS
Pulse fall edge time: >100uS
Injection capacitance: 10pF,100pF
Correction of charge error: Eq≤±5%
Charging adapter: 220VAC input,12VDC output
Size: 150×65×35mm3
Weight: 0.5kg
Function: To correct when PD test,Built in rechargeable lithium battery

3. 4# Input Unit

- 3 -
Main Technical Data

Model: 4#

Resonance capacitance range: 400~1500~6000pF

Sensitivity(pC)(Imbalance circuit): 0.1

Imbalance circuit: 250mA


Allowed current rms value:
Balance circuit: 2A

4 Partial Discharge Signal Filter Adapter


Model: PDLF-1
This adapter is connected between the input unit and the local amplifier for
filtering the high frequency interference components mixed in the local amplifier
signal, which can effectively improve the test effect of the field test and the
signal-to-noise ratio level of the local amplifier.

5. OWF-100kV/1000pF Coupling Capacitor

Main Technical Data:

Model: OWF-100kV/1000pF

Rated Voltage: 100kV

Rated capacitance: 1000pF

- 4 -
Operating Frequency: 60Hz

Allowed running time: 100%UN, IN running 60min; 70% UN, IN continuous running

The tangent value of the high voltage


20℃,0.9─1.1UN ≤0.002
capacitor dielectric loss angle:

withstand value: 1.1UN,1min

Partial Discharge Value: 100%UN ≤ 2pC

Insulating Medium: Oil

Function: To couple high frequency PD signal

6. LBS-100 Three-phase frequency doubling power filter

Model: LBS-100

Rated Capacity: 60kVA

Three phase rated voltage: 800V

Rated Current: 72.17A

Operating Frequency: 100-200Hz

Circuit Number: 3

Attenuation characteristic: 10kHz ~ 100kHz ≥ 40dB , 100kHz ~ 1000kHz ≥ 60dB

Background Noise: At rated voltage Q≤ 5pC

Cooling method: Dry self cooling


- 5 -
7. Service conditions of the whole set of equipment
1. The altitude of the use area shall not exceed 1000m
2. The ambient air temperature ranges from - 25 ℃ to + 45 ℃
3. The relative humidity of ambient air shall not be greater than 80% RH
4. It does not contain chemical corrosive gas and steam
5. No conductive dust and explosion hazard
6. No severe vibration and impact
7. The front end of the power supply entering the system does not pass through the leakage protector
8. The system adopts corona free cable
9. Indoor use

- 6 -