INPUT SPECIFICATION : 92
3
96 42
Direct Voltage AC 50 to 300V AC (L - N) 3Ø-4W/1Ø-2W
85 to 520V AC (L - L) 3Ø-3W
Frequency 45.0 Hz to 65.0 Hz
Resolution 0.1 Volt
TERMINAL CONNECTION
Accuracy Class 1.0
DISPLAY AND KEY : 15
20 19 18 17 16 14 13 12 11
Display 4 digit, 1line, 7 seg, 0.8” RED LED D+ D-
Reset
VL1 VL2 VL3 N
Keys SET/ENT, INC, DEC/RST MODBUS
System:
GENERAL SPECIFICATION : Range 3Ph-4W/3Ph-3W/1Ph-2W
CAT III Voltage (L-L) : 85-520V AC Accuracy Class: 1.0
Dimension (mm) 96 (H) x 96 (W) x 42 (D) mm (L-N) : 50-300V AC
Made in India
Panel Cutout 92 (H) x 92 (W) mm www.multispanindia.com
230V AC !
Trip Setting Under Voltage : 85-520V AC 3Ø-3W 50Hz, 4VA
50-300V AC 3Ø-4W/1Ø-2W Relay-1 Relay-2
Over Voltage : 85-550V AC 3Ø-3W NO C NC NO C NC
L N
50-330V AC 3Ø4W/1Ø2W
Under Frequency : 45.0 Hz To 65.0 Hz 1 2 3 4 5 6 7 8 9 10
Over Frequency : 45.0 Hz To 65.0 Hz
Phase Asymmetry : 2-30%
Time Parameter Power ON Delay Time : 0 To 99 Sec.
Trip delay Time : 0 To 999 Sec.
Recovery Time : 0 To 99 Sec.
KEY OPERATION MAINTENANCE
FUNCTION PRESS KEY 1. The equipment should be cleaned regularly to avoid
OPERATOR MODE blockage of ventilating parts.
To enter in parameter setting SET 2. Clean the equipment with a clean soft cloth. Do not use
ENT For 5 sec isopropyl alcohol or any other cleaning agent.
To view individual phase voltage OR 3. Fusible resistor must not be replaced by operator.
2405 4155 2405 All safety related codifications, symbols and instructions that
L1 L2 L3 L1 L2 L3 L1 L2 L3 appear in this operating manual or on the equipment must be
R1 R2 R1 R2 R1 R2 strictly followed to ensure the safety of the operating personnel
as well as the instrument.
2) Voltage L2-N 2) Voltage L2-L3 2) Frequency
If all the equipment is not handled in a manner specified by
2415 4005 505 the manufacturer, it might impair the protection provided by the
equipment.
L1 L2 L3 L1 L2 L3 L1 L2 L3
R1 R2 R1 R2 R1 R2
Read complete instructions prior to installation
3) Voltage L3-N 3) Voltage L3-L1 and operation of the unit.
R1 R2 R1 R2
WARNING GUIDELINES
4) Frequency 4) Frequency
WARNING : Risk of electric shock.
500 500
L1 L2 L3 L1 L2 L3 1) To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
R1 R2 R1 R2
arrangement. Do not touch the terminals while power is
being supplied.
2) To reduce electro magnetic interference, use wire with
MECHANICAL INSTALLATION adequate rating and twists of the same of equal size shall
be made with shortest connection.
1) To install the instrument on a DIN rail, raise the clamp at the
back of the instrument and place it on the rail. Now release 3. Cable used for connection to power source, must have a
the clamp, so the instrument fits on the DIN rail. cross section of 1mm or greater. These wires should have
2) Ensure proper fitting of the instrument by pulling it outwards. insulations capacity made of at least 1.5kV.
3) To remove the instrument raise the clamp to release it from 4) A better anti-noise effect can be expected by using
the DIN rail. standard power supply cable for the instrument.
4) The equipment in its installed state must not come in
close proximity to any heating source, caustic vapors, oil
steam, or other unwanted process byproducts.
5) Do not connect anything to unused terminals.
Page -1
PARAMETER SETTING Password 11 : To Enable / Disable parameter
(Over Voltage, Under Voltage,over
Frequency,Under Frequency,
Asymmetry,Phass loss, Phase
Press SET key
for 5 sec
sequence)
Password 37 : To set Power on delay time, Trip delay
Time,Relay Fault Mode, Reset mode,
network selectiom
pass Password
Relay-1 Settings Press SET key
Press SET
key for 5 sec
11 Enter Password 11
Press SET
key pasS Password
Press key
210 (Under Voltage Value)
SET
(85-520V For 3Ø-3W )
(50-300V For 3Ø-4W/1Ø-2W )
Press SET
key
UF (Under Frequency)
If Over Frequency is Enable
Press SET
key OFR1 (Over Frequency of Relay 1)
If Over
eNBL (Enable/Disable)
Frequency
Press SET
key
is Disable
Press SET
key
550 (Over Frequency Value)
(45.0-65.0 Hz)
as (Asymmetry)
IF 1Ø-2W Press SET
key
Selected Press SET
key If Under Frequency is Enable
If Under
UFR2 (Under Frequency of Relay-2) UVR2 2205 ◘ Under Voltage in Relay 2
L1 L2 L3 UV L1 L2 L3 UV VL2L3(3Ø-3W) or VL2(3Ø-4W)
Frequency Press SET
key
is Disable
R1 R2 R1 R2 Under Voltage Value=220.5V
550 (Under Frequency Value) OfR2 525 ◘ Over Frequency Fault in Relay 2
(45.0-65.0 Hz) L1 L2 L3 OF L1 L2 L3 OF ◘ Over Frequency
Press SET
key IF 3Ø-4W/3Ø-3W Selected
R1 R2 R1 R2 Value=52.5 Hz
(2-30%) = 20 %
L1 L2 L3 PL ◘ L1
PL - Phase loss
R1 R2
Press SET key for save & exit
L1 L2 L3 PS ◘ Phase sequence Fault
Ps R1 R2