Professional Documents
Culture Documents
OPERATION MANUAL
OF HIBALLAST NF SYSTEM
(HI-CON)
HULL NO 0117616/0117615/0117614
SHIP CLASSFICATION NK
TYPE APPROVED
Page
DOCUMENT NO. HiB-M01010 Rev. No
4 144
RESPONSIBLE PARTY Hyundai Heavy Industries Co., Ltd.
USCG TYPE APPROVED OMSM
Rev.1 / 21. Oct. 2021
PACKAGE REVISION No. & DATE
Rev. Date Reason for Issue Prepared Checked Approved
0 21. July, 2022 First Issue S.H. Ha J.S. Seo G.H. Lee
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Revision Sheet
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
CONTENTS
2. Introduction ................................................................................................................................................................. 2
3. System description....................................................................................................................................................... 7
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
6. Operating instructions................................................................................................................................................ 36
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
1. Button .......................................................................................................................................................................... 9
2. Parameter ................................................................................................................................................................... 11
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
1. Manufacturer’s information
1.1. Supplier
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
2. Introduction
This chapter describes introduction on how to operate the HiBallast NF system and also contains a general
overview and control system of the HiBallast NF.
2.1. Abbreviations
The below table is a list of abbreviations in this manual.
Abbreviations Descriptions
AODD Air Operated Double Diaphragm
AL Alarm
AMS Alarm Monitoring System of a vessel
APT After Peak Tank
BS Existing Ballast System of the vessel
BWP Ballast water Pump
BWTS Ballast Water Treatment System
CC Control Cabinet
CCR Cargo Control Room
DP Deferential Pressure
ECR Engine Control Room
EM Electrolysis Module
EMC Electromagnetic Compatibility
ESD Emergency Shut-down
PSD Process Shut-down
USD Unit Shut-down
EU Electrolysis Unit
FIFRA The Federal Insecticide, Fungicide, and Rodenticide Act
GPS Global Positioning System
GS Gas Separator
GSP General Service Pump
HAZOP Hazard and Operability study
HMI Human-Machine Interface
IAS Integrated Automation System
IMO International Maritime Organization
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Abbreviations Descriptions
IP International Protection
J/B Junction Box
LOP Local Operating Panel
MCC Motor Control Cabinet
MMO Mixed Metal Oxide
MTBF Mean Time Between Failure
NU Neutralizing Unit
PC Personal Computer
PLC Programmable Logic Controller
PMS Power Management System of a vessel
PSU Practical Salinity Unit
RF Rectifier
RH Relative Humidity
SD Shut-Down
SKID The place electrolyzer unit and gas separator installed
SCU System Control Unit
ST Strainer
SWFU Seawater Feeding Unit
TBD To be determined
TRO Total Residual Oxidant
TRC Total Rated Capacity(Total treatment Rated Capacity)
TSU TRO Sensor Unit
USCG United State Coast Guard
WBP, BWP Water Ballast Pump
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The personnel for installation, commissioning, operation and maintenance of the HiBallast NF system
and its equipment must read and understand this manual including the Health and safety section.
Depending on the qualification of the personnel, additional training might be necessary.
The installation of the HiBallast NF system has to be carried out in accordance with local regulations
and accepted code of good practice.
The installation, commissioning, operation and maintenance of the HiBallast NF system may only be
carried out by authorized and trained personnel.
Strictly comply with all relevant rules for accident prevention and local health and safety regulations.
Check all relevant safety procedures before you switch on the HiBallast NF system.
HHI accepts no responsibility for any damage arising from incorrect installation, incorrect use,
incorrect maintenance or own modifications of the HiBallast NF system.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The HiBallast NF system must be installed, operated, maintained, and repaired by persons
who have been sufficiently trained as described in HiBallast NF safety manual (HiB-
M01005).
Make sure all documentation is available, read and understood before start.
Make sure all parts are installed properly according to installation guide before start.
Make sure that all operating parameters are set properly before start.
Make sure that WBP and its related valves are set to be proper position before the HiBallast NF starts.
Make sure not to exceed the certified flow (TRC, Treatment Rated Capacity) in the main stream.
Make sure that all manually operated isolation valves for electrolyzer modules SHALL be OPENED
for ballasting operation. It is strongly recommended to CHECK the status of manual isolation valves,
and be CAREFUL not to operate or energize electrolyzer without water flow. It should be noted that if
the valve is closed, there is no water flow through electrolyzer module.
If the vessel uses a dedicated seawater tank for low salinity of seawater or a salt
tank, please make sure that the dedicated seawater tank should be filled with
normal seawater before entering into a port which is low salinity region.
Please Note :
At low salinity region, pre-charged salt water in the dedicated tank will be used
for salt water source.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
3. System description
The HiBallast NF system is a Ballast Water Treatment System that employs aqueous chlorine which is
produced by seawater electrolysis. Total residual chlorine will be dissolved to the water and then converted to
hypochlorous acid and hypochlorite ion, which have been widely used for disinfection such as prevention of the
marine organisms’ growth and sterilization of drinking water or wastewater. Especially, side-stream (in-direct)
method for electrolysis’ arrangement is hired in order to produce high concentration (but, not more than 1,000
mg/l) of disinfectant, free chlorine and its derivatives from seawater, and then it will be directly injected into the
ballast pipe during ballasting. Generated chlorine and its derivatives will disinfect marine organisms and their
final concentration will meet regulation requirements. The remaining hypochlorite concentration will be
significantly lower than initial doses because the neutralization agent will be injected before de-ballasting in
order to remove any remaining oxidant that might have harmful effect when discharged without neutralization.
The HiBallast NF, Ballast Water Treatment System (hereinafter BWTS), consists of Electrolysis unit,
Neutralization unit and System control unit including Sampling unit. Table 1 summarizes each function of
equipment in the system.
Separately, SEA WATER FEED UNIT which is could be combined in the electrolysis unit considering
installation condition supplies water from source to the electrolysis unit. ELECTROLYSIS UNIT contributes to
produce a disinfectant in the same time. The key role of electrolysis unit is to generate active substances and
inject high concentrate of disinfectant into mainstream of ballast water piping. During this process, hydrogen
gas is also created but it is immediately vented out in order to secure the BWTS during operation.
During de-ballasting, remaining disinfectant which might be harmful to marine environment is reduced by
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
neutralizing agent such as thiosulfate and sulfite. The main purpose of NEUTRALIZATION UNIT is to detoxify
possible residuals, which could be residual chlorine or bromine derivatives measured as TRO (Total Residual
Oxidant) in ballast water.
The SYSTEM CONTROL UNIT of BWTS, an independent control unit of the ship’s IAS (Integrated
Automation System) or operator console, controls the system valves, electrolysis unit, neutralization unit and
monitors the system status. It is connected via hard wiring and/or data communication through ethernet to
communicate data between IAS or console and system.
The SAMPLING UNIT is to facilitate sampling of treated water by using flow measuring and sample
preparation devices, which shall comply with IMO Sampling guidance.
* Note
Please refer to APROVAL DOCUMENT for more information
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The necessary personnel and position for each operation stage are shown in the table below.
NUMBER OF POSITION
OPERATION STAGE PERSONNEL** REMARK
REQUIRED CCR LOCAL
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The HiBallast NF system has basic electrolyzers with the TRC (Treatment Rated Capacity) of 75, 150,
225, 300, 600, 900, 1200, 500, 1000, 1500 and 2000m3/h. The system’s TRC (Treatment Rated Capacity)
can be increased by parallel installation of the basic electrolyzers. The basic models are illustrated as below.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Please refer to CODE BOOK for product structure (Doc. No. : HiB-M01004)
3.10. Materials
Flange,
H2 ventilation piping JIS STPG 370/Sch.20 5K Galvanized
Sleeve welding or full penetration
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Following list of chemicals summarized active substances, relevant and other chemicals which are detected
during Land based testing of IMO Type approval. The DBPs generated are strongly affected by organic
chemical included in the influent water. Other DBPs not listed in below could be generated.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
R10-22-34 HAN
Dichloro-acetonitrile 3018-12-0
S2-13-20-24-25-26-36-39-46 Disinfection by-product
R23/24/25-34-50 HAA
Monochloro-acetic acid 79-11-8
S1/2-23-37-45-61 Disinfection by-product
R35-50
Dichloro-acetic acid 79-43-6
S1/2-26-45-61
R35-50-53
Trichloro-acetic acid 76-03-9
S1/2-26-36/37/39-45-60-61
R23/24/25-35-43-50
Monobromo-acetic acid 79-08-3
S1/2-26-36/37/39-45-61
R34
Dibromo-acetic acid 631-64-1
S2-20-24-25-26-27-39-46
R34
Tribromo-acetic acid 75-96-7
S2-20-24-25-26-27-39-46
Other chemical
R12 By product
Hydrogen 1333-74-0
S2-9-16-33
Neutralizing agent,
Sodium thiosulfate 7772-98-7 NR
Reducing agent
* Note
Please refer to MSDS of reference manual.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
3.11.1. Injection
Please see Installation Guidance (Doc. No. ; HiB-M01006, Ch. 3.9.2 ~3) for more information.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Please see Installation Guidance (Doc. No. : HiB-M01006, Ch. 3.11) for more information.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
≤ 300 300 12
≤ 1200 1200 12
≤ 2000 2000 14
≤ 6000 6000 56
≤ 8000 8000 64
≤ 10000 10000 92
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
* Note
When stop ballasting, water inside electrolysis unit is changed to sea water by flushing sequence
automatically. If the BWTS is stopped by emergency shutdown, the remaining water inside of electrolysis unit is
sea water containing hypochlorite. So if drain is required for maintenance after ESD, manual flushing should be
performed by crew before drain. Please see maintenance manual for more information.
Appendix F Emergency manual operation procedure (Ballasting step 1 to 15) of this manual
HiBallast NF maintenance manual [Doc. No. : HiB-M01002]
If the closed tank is not drained properly according to [appendix C Drain manual
Caution
for closed tank], the blowers can be damaged by overflow from this closed tank.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Please see Installation Guidance (Doc. No. : HiB-M01006, Ch. 3.3.1 ~ 2) for more information.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Hydrogen (hereinafter H2) gas also produced by the electrolyzer during ballasting. HiBallast NF system does
not allow inflow of H2 gas into ballast tanks for safety. This H2 gas is separated by degas system in the
electrolysis unit then diluted and discharged to safety area on deck through vent pipe line. The degas system is
mainly composed of gas separator, vent valve and blower as below configuration. Furthermore there are safety
interlock functions such as H2 gas concentration, blower’s discharge pressure, blower running status monitoring
and auto blower run to prevent unexpected accident.
Auto
vent
Drai
Blowe Blowe
Separat
Separat
The H2 gas separated by separator comes out by internal pressure of separator via two auto vent valves. And
small water which comes out with H2 gas when the vent valve is open flows in the closed separator drain tank.
This drain water containing hypochlorite should be treated properly before discharge. Please see 3.11 and
appendix C for more information.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
HiBallast NF has safety interlock functions for degas system as below table.
Please see 4.7 alarm and safety function for more information.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
4. System control
This chapter shows general drawings for system and major components including required utilities for
HiBallast NF.
* Note
Please refer to APPROVAL DOCUMENT for more information.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Electric power for the system operation is distributed as shown in following Figure 2 & 3. The primary power
for control cabinets, motor control cabinet and rectifiers are supplied through ship’s power distribution system.
In the case of motors of BWTS, the power is supplied via MCC (Motor Control Cabinet).
If the system requires multiple trains to cover large capacity of ballast water, electrolyzer module will be
added to this configuration in parallel. For more details, please see the relevant electrical drawings.
* Note
Please refer to APPROVAL DOCUMENT for more information.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The CC (Control Cabinet) involves duplicated CPUs and multiple I/O(Input/Output) cards in order to control
and monitor all equipment such as valves, pumps and sensors.
The operation can be executed at LOP (Local Operation Panel) installed on the control cabinet and at PC,
installed in ship’s office or CCR (Cargo Control Room). The operator interface, called HMI (Human-Machine
Interface), was designed to facilitate operation by operator(s). For BWTS operation, operator(s) should be
educated with minimum training required for operation and maintenance.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
System is controlled by commercial programmable logic controller (PLC) and operator can manipulate system
via operator interface installed in control cabinet or operator station which will be installed in ship’s office for
cargo control room (CCR). The operator interface was designed to facilitate treatment operation by crews. For
system operation, crews should be educated with required training for operation and maintenance.
The monitored signals are transmitted to system control unit via wiring. The schematic diagram of control
system is as following Figure
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
HiBallast NF has essential control function for operation and treatment performance of the system as
following.
- TRC control
- TRO control for ballasting and de-ballasting
- Disinfectant injection flow control
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The controller monitors system through signals from instruments. The list of instruments is as below.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This section describes the set value, delay time, and disable function of alarm. Furthermore, the meaning of
time delay is as follows;
1 sec : Immediate response
5 sec : Very quick response
30 sec : Very important & quick action
60 sec : Important & normal response
180/300 sec : Important & late response
600 sec : Important & regulation
The alarms and time delay set values could be different in accordance with actual installation and operation
conditions
The HiBallast NF has ventilation fan interlock function for safety and to comply with the related
requirement of the class rule. In this case, the fan should be run to start BWTS. Below table shows examples of
the fan interlock function.
Description of interlock
Ventilation fan for Criteria of area
(If the ventilation fan is turned off)
Separate BWTS room Safety Alarm and System shut down
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
5. Process overview
This section explains how HiBallast NF system works during ship’s ballasting, de-ballasting and emergency
bypass process.
5.1. Ballasting
The ballast water is pumped in from the sea chest. And The sea water is also to be fed to electrolysis unit
from the water source by the SEA WATER FEED UNIT.
The ballast water flow is monitored by the flowmeter and controlled by a position valve to ensure that the
flow rates do not exceed the specific TRC (Treatment Rated Capacity). If the flow rates exceed TRC, an alarm
will occur.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
5.2. De-ballasting
De-ballasting operation is that treated ballast water is pumped from ballast tanks to discharge overboard. In
de-ballasting process, remaining disinfectant in the ballast tanks and ballast piping is reduced by neutralizing
unit as using an agent such as thiosulfate. Such residuals are measured by TRO (Total Residual Oxidant) sensor
of HiBallast NF and its feedback is also monitored consistently to control the level of TRO in order to achieve
allowable TRO concentration guided by regulation that must be within 0.1 ppm.
During de-ballasting, the ballast water flow is controlled by the position valve to ensure that the flow rates do
not exceed the specific TRC.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The emergency shutdown (ESD) and process shutdown (PSD) are operated only in emergency cases for
ships’ safety. It automatically shuts down the whole system in a pre-determined order as below.
Emergency Shutdown Process Shutdown
All the equipment and valves are turned off and closed The equipment and valves are turned off and closed I a
immediately. Then, emergency dilution air supply pre-set order. Lastly, blowers will be turned off after
valve is opened. 600 seconds.
The ESD and PSD operations always activate an audible and visual alarm. And the event is logged in the
BWTS controller.
The bypass operation (override operation) for emergency is performed by opening main flow control valve
without disturbing ballast water pump operation as shown on the following Figure.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
6. Operating instructions
6.1. General
This section describes for the HiBallast NF system operation how to activate each operation step by step. It
contains ballasting, de-ballasting and emergency operation. Please read and follow the preparations and
conditions carefully as well as any danger or warning notes. Operator can select mode and proceed with system
guidance.
Operational
Limitation
Please check the OPERATIONAL LIMITATIONS described in the certificate before all
operations.
When BWTS control PC is powered on, BWTS CONTROL OVEERVIEW will appear on screen at first as
below.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
7 Alarm acknowledge
10 Alarm reset
11 Operation start
12 Operation stop
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The status of BWTS is described by indication lamp in BWTS CONTROL OVERVIEW as below.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Click button of in order to see the ballast system with BWTS. The following Figure
shows the BWTS piping overview for the HiBallast NF.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Click button of in order to see the ballasting start sequence. The following figure
shows the BALLASTING START SEQUENCE showing the status of ballasting start procedure.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Click button of in order to see the ballasting start sequence. The following figure
shows the BALLASTING START SEQUENCE showing the status of ballasting start procedure.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Click button of in order to see the ballasting PSD sequence. The following figure
shows the BALLASTING PSD SEQUENCE.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Click button of in order to see the deballasting start sequence. The following figure
shows the DEBALLASTING SEQUENCE showing the status of deballasting start procedure.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Click button of in order to see the deballasting stop sequence. The following figure
shows the DEBALLASTING SEQUENCE showing the status of deballasting stop procedure.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Click button of in order to see the deballasting PSD sequence. The following figure
shows the DEBALLASTING PSD SEQUENCE.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
To operate BWTS, adequate login level is required. There are three levels for operation of HiBallast NF,
Monitor, Operator and Supervisor as an Administrator (authorized person). The Monitor level is only for
monitoring and a default when start. The Operator is used normally for operation and the Supervisor only for
alarm and parameter adjustment as an authorized person, respectively.
The following table shows each level and its access authority respectively and below figure depicts a screen
shot of the login window.
1) Access limit
Login level
Items Remark
Operator Supervisor
Password required No Yes
2) Available task
Login level Remark
Task
Operator Supervisor
Monitoring (Status of operation) O O
System operation (Automatic mode) O O
Manual operation O O Logged
Control right transfer O O Logged
Alarm history view O O
Report file extraction O O
Trend view O O
Maintenance mode Alarm,
X O
(Cleaning, Calibration, Maintenance) Logged
Replacement of software and hardware X X
High/Low
ALARM limit & delay adjustment X O
only
Logged(Valve,
Operation PARAMETER adjustment O O TRC, Initial
current. Etc.)
DISABLE(override) function for minor Alarm,
X O
instrument Logged
USER registration X O
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Click button then enter ID and passward on the pop-up window to login.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The sever in LOS has the default control permission to run the BWTS equipments. The control permission
transfer will be achieved by requesting and confirmation of both computers pressing button.
And current control position is displayed on HMI screen.
Click
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
System should be ready condition to activate each operation. Otherwise system will not be operated properly.
Required preparations and pre-conditions are as below.
Below table shows required manual valves status for each operation.
Table 2 List of valves to be checked (Project specific)
STATUS (TO BE)
TAG DESCRIPTION
BALLASTING DE-BALLASTING STRIPPING
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
There are mainly two kinds of system settings. One is the equipments selection and the other one is aprameter
setting. The equipments selection allow operator to use BWTS flexibily considering the condition of vessel or
BWTS. But parameter settings are optimizsed by service engineer during commissioning and onboard test
period and it cannot be adjusted by operator. If change of parameters is required, it should be checked and
confirmed by manufacturer.
The equipments intended to be used for operation should be selected by operator properly in BWTS
OPERATING OVERVIEW. Inappropriate selection could cause malfinction or shut-down of BWTS.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
NOTE
1) In particular case, cross change operation between port and stb’d side could be available for NA pump,
TRO sensor and WBP as a contingency plan.
2) For cross change operation, selection button should be changed accordingly in the equipmet selection
on the HMI
3) Furthermore, the related valves located in local side should be also changed accordingly.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The operator cannot have access to change the key parameter settings such as TRO target for operation in
compliance with the regulation. Adjustment of parameter settings are allowed to supervisor level only.
Please see 6.10 for more information about login level.
Click button in order to see SETTINGS.
② Click!
③ Click!
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Note
Below parameters can be different depending on project specific.
- Injection flow
- Main flow(TRC)
- Rectifier current
Please see 4.7 alarm and safety function for more detail information.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
HiBallast NF controller provides diable (bypass) function and it can be used by clicking selection button
in ALARM SETTING in order to operate BWTS without some sensors. This function is available in
supervisor login level. But the items below shall be noted before activate.
Only use this DISABLE selection button in case of malfunction of these sensros.
Safety and normal operation without theses sensor to be ensured by operator.
This selection will generate alarm and the event will be recorded in the controller
② Click!
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The items disabled or unselected by operator are figured out by yellow mark in HMI as below.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
HiBallast NF system provides main ballast valve lineup check function for each operation. If the system
started with incorrect lineup condition, system will give alarm but system is still operational with this alarm.
To prevent intake or discharge of untreated water by system bypass condition, it is recommended to make it
correct (all green lamps). Below figure shows how to use it and an example of this function.
Click!
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
HiBallast NF system has TRC (Treatment Rated Capacity) which is considered as a maximum treatment
capacity of system. The main flow rate should be properly controlled by BWTS controller automatically or
operator using flow control valve in manual. The TRC set value for ballasting can not exceed the rated
(designed) capacity of ballast pump(s), but the main flow for de-ballasting can be adjusted regardless of the
rated capacity of ballast pump.
The main flow is controlled by BWTS controller automatically and BWTS controller allows the operator
to adjust TRC set value in [TRC CONTROL PARAMETER] page for flexible operation at supervisor login
level only. (Please see 6.13.2 and 6.10 for more information)
②Click!
Please note that the intended TRC set value can not exceed the maximum capacity of the system itself.
And if TRC set value is adjusted before start system, default valve position of main flow control valve to be
also changed accordingly.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
CAUTION! If the TRC set value is changed during ballasting, output current of rectifier is also
changed automatically accordingly by controller. But before start BWTS, the initial
current set value of the rectifier is not changed automatically. So user must change the
initial current set value of rectifier properly in accordance with the following tables.
Please see 6.14.2 for more information.
NOTE The initial current is maintained for predifined specific time after start the rectifier in
order to make the system stable at the beginning of operation. So if this value is not set
properly, the system could be shut down by TRO concentration alarms.
HiBallast NF system has following treatment capacities according to the electrolyzer models from 75 to
10000. During commissioning, the initial current could be set considering chlorine demand which are
dependent on function of salinity and temperature of intake water.
* For all cases, the salinity and temperature of feed water to electrolysis unit will be controlled above 15PSU using
dedicated tank or salt tank and 10℃ using heater.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
HiB-75 EM-75 X1 54 54 40 46 51 57 68
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
* This factor is used for the very challenging condition in which the influent water contains high concentration o
f dissolved or particulate organic matters which causes severe chlorine decay during or after treatment.
The main flow can be controlled by operator in manual using a flow control valve placed in main ballast
pipe line. It is recommended to control this valve gradually to avoid alarm or system shut down, even
though the current of rectifier will be changed automatically to maintian proper TRO concentration of
ballast water. The expected abnormal conditions which could be caused by dramatic flow change are as
below.
Please see 오류! 참조 원본을 찾을 수 없습니다. [HiBallast NF standard alarm list] for more
inforamtion
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
6.14.4. Main flow reduction operation for low temperature of feed water (Ballasting)
Feed water for electrolysis unit will be heated when low temperature is detected by sensor, if the vessel has heat
exchanger for heating the feed water. But, if the vessel has no heater or installed heater is malfunction, TRO
concentration counld be lower than low alarm set value.
In that case, it is recommended to reduce main flow up to 80% of TRC for ballasting. Further reduction might
be required depending on actual temperature of feed water and ballast water quality.
6.14.5. Main flow reduction operation for rectifier current alarm (Ballasting)
Rectifier of HiBallast NF provide current for electrolysis reaction in order to generate the required disinfectant
which can be measured as TRO (as chlorine) during ballasting operation. Normally, it can provide sufficient
current for normal ballasting operation. However, in the case that the feed water to electrolyzer and/or ballast
water contains very high organic content, the capacity of current supplied by the installed rectifier, may be
insufficient to support the TRO in the proper range of ballasting operation. In that case, a CURRENT HIGH or
HIGH HIGH alarm of rectifier is to be annunciated. (Refer to HiB-G0301)
In that case, it is recommended to reduce main flow up to 80% of TRC for ballasting. Further reduction might
be required depending on actual feed water and ballast water quality.
6.14.6. Main flow reduction operation for partial fail of electrolyzer train (Ballasting, multi train type
only)
In case of partial fail of electrolyzer train(s) by defective of electrolyzer module or connected rectifier,
ballasting operation is possible with reduced TRC and isolation of the defective electrolyzer train(s) by closing
electrolyzer outlet manual valve(s). In this case, TRC should be adjusted accordingly considering available
treatment capacity of eletrolyzer train(s). Below table shows an example of the partial operation of HiB-6000 in
case of one train fail.
HiB-6000 (2000 x 3)
Full operation Partial operation (one trian fail)
No. of working electrolyzer 3 x 2000 No. of working electrolyzer 2 x 2000
train(s) train(s)
No. of working rectifier(s) 3 x 100D No. of working rectifier(s) 2 x 100D
TRC 6000 TRC 4000
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
6.14.7. Main flow reduction operation for partial fail of electrolyzer module in train (Ballasting)
One train of electrolyzer can be connected with multiple rectifiers. When a part of electrolyzer modules or
one of rectifier is fail, treatment capacity of the electrolyzer train can be reduced by disable of the defective
module and rectifier. Below table shows an examples of the treatment capacity reduction of train.
HiB-2000 (EM500 x 4)
Full treatment capacity Reduced treatment capacity (one module fail)
No. of working electrolyzer 4 x M500 No. of working electrolyzer 2 x M500
modules module(s)
No. of working rectifiers 2 x 50D No. of working rectifier 1 x 50D
Treatment capacity of train 2000 ㎥/h Treatment capacity of train 1000 ㎥/h
If the TRO concentration in ballast water is high due to clean water and short voyage, ballast water
could not be neutralized until less than 0.1 mg/L then system will be shutdown by too high TRO alarm
during de-ballasting. In that case, main flow reduction is recommended to ensure neutralization of
discharge water for normal operation.
Please see 오류! 참조 원본을 찾을 수 없습니다. [HiBallast NF standard alarm list] and 오류! 참조
원본을 찾을 수 없습니다. [Main flow contol (TRC)] for more inforamtion
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Ballast water is pumped then flow to the ballast tank(s). It is important to activate BWTS to control valve(s)
before the ballast pump start.
Low salinity The dedicated seawater tank should be filled with salt water before entering into a port where
low salinity region is. At low salinity region, pre-charged salt water in the dedicated tank will
be used as salt water source.
APT When using GSP for APT intake, low pressure operation is required.
ballasting In case that the vessel has separate APT ballasting operation mode using GSP and there is no
orifice at the GSP discharge, it should be considered to reduce APT ballast line pressure below
4bar to get EU injection. In this case, to reduce pressure of the APT ballast line, following
methods are recommended.
But, the first one is recommended because second one still has a risk of high pressure when
the system was shut down and flow control valve was closed.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
In order to run BWTS, following shall be checked & confirmed on the control monitor before start of
ballasting. Confirmation on the control monitor is necessary to go to the next step of BWTS operation.
Make sure that TRO sensor reagent is enough for whole ballast operation.
(Preparing reagent kit, refer to MAINTENANCE MANUAL)
Make sure that electrolysis skid is ready for start.
Make sure that seawater feeding line is ready for start.
Make sure that the system is ready for ballasting.
Make sure that ballast system valves line up for ballasting. (See 6.12)
Make sure that the ready OK for ballasting.
Table 5 System ready check list for the ballasting (System Ready Condition)
NO CHECK ITEMS CHECK POINT
1) Check first whether the vessel is located at low salinity region (<15PSU)
or not.
Low salinity 2) The low salinity region shall be predefined at the Window in HMI on
1
(< 15PSU) operation PC.
3) If the vessel is located at low salinity region, the low salinity unit will be
utilized properly and automatically.
Check TRO sensor is ready and reagent is enough. (Reagent kit shall be
2 TRO
replaced every 3 month, refer to MAINTENANCE MANUAL)
Check that the manual valves are correct position in the electrolysis unit.
3 Electrolysis unit
Check that the drain valves are CLOSE.
Check the OPEN status of valves of selected strainer & pump.
4 Seawater feed unit (Local & Manual)
Check the CLOSE status of valves. (Local & Manual)
1) Control cabinet ready
5 System ready status 2) Motor control cabinet ready
3) Rectifier ready
Ballast system valve
6 Check ballast system valves line-up for ballasting. (See 6.12)
line-up
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The HiBallast NF system has a special function for low salinity region detection by using Ship’s GPS
data. The GPS interface comply with applicable parts of International Standard IEC 61162.
The following drawing shows a schematic how to cope with low salinity issues on the electrolysis.
The ‘P1’ and ‘R1’ show the position and radius of low salinity region, respectively. The vessel ‘A1’
receives current position data through GPS (Global Positioning System) and the HiBallast NF system
recognizes automatically whether the vessel is approached with the low salinity region or not. Once the
vessel approaches within low salinity region, the HiBallast NF notifies an alarm to the operator.
The low salinity region, less than 15 PSU, is also available to be predefined by operator, which is
consisted of the latitudinal and longitudinal data of the vessel’s location and the radius of the region as
shown on the below Figure.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Click button in order to start the low salinity area management function.
② ③
④
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The required minimum salinity of feed water for the electrolyzer is 15PSU to produce chlorine during
ballasting. And salt water can be supplied from dedicated ballast tank(s) or additional salt tank in low salinity
area. Ship’s crews will recognize the low salinity area by alarm as described in 6.15.3 and preparations for
filling dedicated tank before going into low salinity region or filling salt tank before ballasting and making salt
water feeding line-up should be performed adequately by crews. But it would be available to provide auto low
salinity operation mode by supplier as an optional function. Please see below guideline when use dedicated tank
or additional salt tank.
Vs = Fi x Tb
To protect the system, dedicated tank level is interfaced with BWTS main controller. Please press the
use button on the BWTS OPERATING OVERVIEW to activate interlock function of the tank level.
And to avoid unnecessary alarms, please deactivate the interlock function by pressing the button.
Selection button
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
NOTE Please check the line-up of the manual valves for the SEA WATER FEED
UNIT suction pipe line before use.
If the vessel uses a dedicated seawater tank for low salinity, please make sure
that the dedicated seawater tank should be filled with normal seawater
before entering into a port of low salinity region.
At low salinity region, pre-charged salt water in the dedicated tank will be
used.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Once the salt tank unit is in operation, fresh water or sea water supplied from vessel through the remote valve
(BT-1751) is mixed with pre-charged salt in the tank (V-175). And saturated salt water will overflow to the salt
water tank of the unit. Then produced high concentration salt water is injected into the seawater feed pump
suction line by salt water feed pump (P-175). And injection flow is automatically controlled by BWTS
controller using control valves, level switches and salinity sensors to meet required salinity concentration of
feed water for electrolysis unit. Below figure & table show typical configuration of the salt tank unit and
function of the component.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The salt tank unit is composed of two tanks. One is for salt to be filled before use and the other one is
for mixed salt water which will be overflowed from salt tank when use.
Below table shows function of main equipment of the salt tank unit.
Component Function
Salt tank (V-175) Salt storage
Feed pump (P-175) Salt water supply
On/off control valves
Water supply for salt tank
(BT-1751)
Flow control valves
Salt water injection flow control
(FCV-1751)
Salinity sensor (CT-1751) Salinity concentration monitoring
NOTE If the vessel uses a salt tank unit for low salinity operation, please make sure
that the salt tank should be filled with salt fully before starting ballasting.
Sufficient water for salt tank unit should be supplied (project specific)
Max. supply water for salt tank is 20m3/h
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The required minimum salinity of feed water for the electrolyzer is 15PSU to produce chlorine during
ballasting. And salt water can be supplied from dedicated ballast tank(s) or additional salt tank in low salinity
area. Ship’s crews will recognize the low salinity area by alarm as described in 6.15.3 and preparations for
filling dedicated tank before going into low salinity region or filling salt tank before ballasting and making salt
water feeding line-up should be performed adequately by crews. But it would be available to provide auto low
salinity operation mode by supplier as an optional function.
The operator is able to start BWTS remotely in BWTS CONTROL OVERVIEW for ballasting and monitor
start sequence in BALLASTING START SEQUENCE.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
NOTE If the pump(s) is not run in 60s from ballast pump run request, the system will be stop
automatically. Please see 오류! 참조 원본을 찾을 수 없습니다. HiBallast NF
STANDARD ALARM LIST for more information
The initial current is maintained for predifined specific time after start the rectifier in
order to make the system stable at the beginning of operation. So if this value is not set
properly, the system could be shut down by TRO concentration alarms. Please see 6.14.2
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The operator is able to stop BWTS remotely in BWTS CONTROL OVERVIEW and monitor stop sequence
in BALLASTING STOP SEQUENCE.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
NOTE
1) After rectifier is turned off, the seawater feeding pump will remove the residual hypochlorite acid in the
electrolysis unit pipe for setting time, and remaining H2 gas in gas separator is also removed by blower
for specfic time at the end of stop procedure. So it takes a few minutes until BWTS stop completely.
2) After stop ballasting operation, some remaining H2 gas in electrolysis unit can be exhausted from gas
separator. The blowers will be run automatically if H2 gas is detected by gas sensor placed in gas vent
pipe line, even though the system is not in ballasting operation.
3) The running time for seawatr feed pump and blowers can be checked in OTHER CONTROL
PARAMETERS (See 6.13.2). This setting time cannot be adjusted by operator. If new set value is
required for operation, it to be checked and confirmed by service engineer.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
BWTS shall be started before de-ballasting. And the related valves to be prepared in advance.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Before starting BWTS for de-ballasting, followings shall be checked. (System Ready Condition)
1) Please do not overfilling the NA tank. If the tank is filled with NA more than 100% level, NA
consumption in the operation report could be incorrect. It is recommended to fill the tank no more than
95%.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The operator is able to start BWTS remotely in BWTS CONTROL OVERVIEW for ballasting and monitor
start sequence in BALLASTING START SEQUENCE.
NOTE If the pump(s) is not run in 60s from ballast pump run request, the system will be stop
automatically. Please see 오류! 참조 원본을 찾을 수 없습니다. HiBallast NF standard
alarm list for more information.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
NOTE
1) N.A pump start specific time before start the pump with initial N.A pump stroke to ensure that ballast
water is treated before discharge.
2) Adquate pre-injection time and pump stroke is applied by commissioing engineer before delivery.
These set value can be checked in NEUTRAL CONTROL PARAMETERS (See 6.13.2). These set
value can be adjusted in supervisor mode. If new set value is required for operation, it is recommended
to be checked and confirmed by maker engineer.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The operator is able to stop BWTS remotely in BWTS CONTROL OVERVIEW and monitor stop sequence
in BALLASTING STOP SEQUENCE.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
In case that BWTS controller is able to control some of VRCS valves by signal interface, BWTS provides
circulation mode to prevent discharge of ballast water when TRO measured by sensor is more than 0.1mg/L
during deballasting. But, if there is no circulation mode, main flow control valve will be closed automatically
when TRO is above 0.1mg/L during deballasting.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
CAUTION! Driving (motive) water of the eductor is untreated and thus contains organisms. As a
result the discharge water may not meet the discharge standard if sampled at discharge.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Before starting BWTS for stripping, followings shall be checked. (System Ready Condition)
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The operator is able to start BWTS remotely in BWTS CONTROL OVERVIEW for stripping and monitor
start sequence in STRIPPING START SEQUENCE.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
NOTE
1) N.A pump start specific time before start the pump with initial N.A pump stroke to ensure that ballast
water is treated before discharge.
2) Adquate pre-injection time and pump stroke is applied by commissioing engineer before delivery.
These set value can be checked in NEUTRAL CONTROL PARAMETERS (See 6.13.2). These set
value can be adjusted in supervisor mode. If new set value is required for operation, it is recommended
to be checked and confirmed by maker engineer.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The operator is able to stop BWTS remotely in BWTS CONTROL OVERVIEW and monitor stop sequence
in STRIPPING STOP SEQUENCE.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
When an emergency case occurs, the system can be shut down by operator. Once the ESD operation starts, the
output of rectifier and all pumps will be shut off immediately and all valves will be closed according to
predefined sequence as well.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
BWTS can be bypassed by opening flow control valve in manual in emergency case. This system bypass
operation shall be used in emergency only for vessel’s safety. Please note that all event and alarm including
system bypass are logged in BWTS controller for 2(two) years in compliance with regulation.
On/off valve 1) Use portable compressed air Press or turn manual open switch of solenoid valve
2) Rotate the drive shaft
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
In case of critical sensor fail, auto operation is not possible. In that case, ballast water can be treated by full
manual operation.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The status and parameters of each rectifier can be monitored by just clicking button in BWTS
PIPING OVERVIEW. The following figure shows a screen shot of pop up window for the rectifier monitoring.
Actual output current and voltage, temperature for internal of enclosure and switching power device
Status monitoring: E-STOP, RUN/STOP, READY/ERROR, OVER CURRENT ALARM, and so on.
Click!
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
NOTE
1) If the rectifier is not changed to normal condition after ESD caused by alarms, please click
button.
2) Remote mode to be selected for auto operation. Otherwise please check selection switch on the rectifier
front control panel at the local as below.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The operator is able to start TRO sensor in manual using start button for operation or test.
Click!
NOTE
1) This TRO sensro start button is available only for DPD type.
2) To stop TRO sensor, click start button again.
3) If operator does not stop the TRO sensor after use, TRO sensor will keep running until the TRO reagent
bottle is empty.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Remote manual operation mode is provided for all equipment such as pumps and valves. Users are able to
change to manual mode by clicking MIMIC and manual button to control them in manual regardless of
operation condition as below picture.
Click!
NOTE
1) Once the equipment operation mode is changed to manual mode, it will not be turned back to auto
mode automatically.
2) All equipment operation mode are cahnged to auto mode when operator click BWTS operation start or
stop button.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
7.4. Alarms
HiBallast NF makes visible and audible alarms to give operators warning when an abnormal condition is
detected by controller to protect the system from damages and crews from unexpected accident during operation
or standby. These alarms are triggered by pre-set values or pre-defined condition. Please see 오류! 참조 원본
을 찾을 수 없습니다. HiBallast NF standard alarm list for more information.
When the alarm occurs, HMI displays alarm indicator on top side of HMI as below.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The Alarm display shows 100 lines of latest alarm and arrange the events occurred in chronological order.
The alarm display consists of the time when the event occurred, tag name, description of the tag, the value at the
event, alarm status. The row of the alarm un-acknowledged will be indicated as red text and the space of the row
will be filled with green when operator presses the “ACK” button. The alarm summary page will display only
the list of the tag with alarm condition, and space of rows will be filled as white on the list if the alarm cleared.
If a state is unchecked in “Alarm Event Filter”, alarm lists with the state in the list will not be shown.
Click!
See 6.13.2 & 6.13.3 for more information about alarm setting.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
The trend view function can be activated by clicking button on the top of MIMIC.
Please see appendix A for more information.
The trend display consists of two modes; history trend and live trend. The live trend displays history data
(from current time to past time as long as the time range) and current live data. The history trend displays the
recent 10 days trend data. Operator is able to select time interval between 30 seconds and 1 hour.
When trend window is clicked, the trend legend is appeared. Operator can only see specific data by disabling
the eye symbol on the trend legend.
The following figure shows a screen shot of trend. It is useful to show process data and provides operators
with a way to write value.
With this function, you can:
monitor constant values as well as tag values
use real time data from tags or use historical data from log files
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
It is not possible to delete the log data and BWTS operation data should be available on board for 24 month
in compliance with regulation. All operation, event and alarm are logged in control station automatically.
The control systems will generate the report file as EXCEL format after finishing major operations of
BWMS such as Ballasting and Deballasting and store the file in the each operating station. The operating
station has enough capacity to save total 24 months of the report files.
Check the log data on ‘GENERAL’ tab of ‘SELECT REPORT VIEW’ and click
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
NOTE Do not use it for port survey submission because it may be different from actual value
due to system integration, configuration and operation characteristics.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Alarm/event and audit trail history during operation of BWMS is stored as Excel file with daily basis in
These log data include manual operation of equipment, alarm activation and normalization, Start/stop of
operation, manual override/bypass and parameter change. The operator is able to extract the data file to the
external storage. The ROS and LOS have enough capacity to save total 24 months of the history data file.
Check the log data on ‘ALARM/AUDIT’ tab of ‘SELECT REPORT VIEW’ and click
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Alarm
Event
Remark
Please see Appendix B to see meaning of the tag names of alarm
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Remark
Please see Appendix C to see meaning of the tag names of audit trail
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
In the event that the control and monitoring equipment is replaced, the data recorded prior to
replacement should be available onboard for minimum 24 month in compliance with regulation.
The control system provides maintenance/calibration status select function. Operator is able to select the
maintenance or calibration operation on HMI screen. To carry out any maintenance or calibration work, BWTS
should be changed to maintenance or calibration mode in compliance with regulation [USCG 46 CFR §
Maintenance mode
【 END
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
It requires drain and filling the drain tank with NA when required. It’s available to be
carried out during operation if necessary.
(If an uncertified NA solution is used, it may cause performance degradation in the
system)
Safety Strictly comply with all relevant rules for accident prevention and local health and
safety regulations. Wear your Personal Protective Equipment.
Do not inhale liquid. Protect your skin and wear safety gears. Ordinary glass or
plastic is sufficient. Keep away from incompatibles such as oxidizing agents, acid,
and alkalis. Keep container tightly closed. Keep container in a cool area.
*Refer the Material Safety Data Sheet (MSDS) for more information.
Purpose To drain neutralized water from the Drain Tank and ensure that drain water from
vent pipe is neutralized before next drain work.
Frequency
When LS-1141 high alarm is activated. Refer to Sec. 오류! 참조 원본을 찾을 수
3 Make sure that the tank is empty and close drain valve.
Validity date of The validity date of product is NOT specified, but it is recommended to check
1
product (NA) any external damages of the package.
Purchase of product If additional purchase is required, please contact to HHI Global Network or
1
(NA) bwts@hhi.co.kr before leaving the current port.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
1. Button
TAG_NAME DESCRIPTION
MP_AIT1121(2/3)_ST AIT-1121(2/3) CALIBRATION MODE START COMMAND
MP_AIT1121(2/3)_SP AIT-1121(2/3) CALIBRATION MODE STOP COMMAND
MP_REPAIR_ST MAINTENANCE MODE START COMMAND
MP_REPAIR_SP MAINTENANCE MODE STOP COMMAND
MF_TE1111 TE-1111 DISABLE COMMAND
MF_PT1721 PT-1721 DISABLE COMMAND
MF_LIT1311 LIT-1311 DISABLE COMMAND
MF_CT1111 CT-1111 DISABLE COMMAND
MF_B117_BP BLOWER GAS OPERATION DISABLE COMMAND
MF_APT APT MODE SELECTION COMMAND FOR LOW SALINITY
MF_IMO IMO & USCG MODE SELECTION COMMAND (0 : IMO, 1 : USCG)
MP_SOUNDOFF BUZZER STOP COMMAND
MP_ESTOP EMERGENCY STOP COMMAND
MP_RESET ALARM RESET COMMAND
MP_(DEVICE)_OP DEVICE OPEN COMMAND
MP_(DEVICE)_CL DEVICE CLOSE COMMAND
MP_(DEVICE)_ST DEVICE START COMMAND
MP_(DEVICE)_SP DEVICE STOP COMMAND
MP_( DEVICE)_A DEVICE AUTO MODE COMMAND
MP_( DEVICE)_M DEVICE MANUAL MODE COMMAND
MP_BAL_ST_S(P/A) STBD(PORT/APT) BALLASTING START COMMAND
MP_BAL_SP_S(P/A) STBD(PORT/APT) BALLASTING STOP COMMAND
MP_DEBAL_ST_S(P/A) STBD(PORT/APT) DEBALLASTING START COMMAND
MP_DEBAL_SP_S(P/A) STBD(PORT/APT) DEBALLASTING STOP COMMAND
MP_STRIP_ST_S(P) STBD(PORT) BALLASTING START COMMAND
MP_STRIP_SP_S(P) STBD(PORT) BALLASTING STOP COMMAND
MP_RH_ELEC_PART_RESET PARTIAL ELECTROLYZER RUNNING HOUR INITIALIZING
MP_RH_ELEC_FULL_RESET FULL ELECTROLYZER RUNNING HOUR INITIALIZING
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Remark
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
Above tag name and descriptions are for reference. Please note that actual tag name and description
could be different in accordance with the project. So it is recommended to contact maker if unknown tag
name is shown on the logged data. Please see 1 Manufacturer’s information for more information.
2. Parameter
TAG_NAME DESCRIPTION
TD_ALARM TAG ALARM DELAY TIME VALUE
MS_ALARM TAG ALARM SET VALUE
ControlRight Control Position (0 : LOS, 1 : ROS)
MS_WBP_SP BALLAST PUMP STOP WAITING TIME
MS_TRO_WAIT TRO SENSOR START WAITING TIME
MS_SWP_ST S.W.F.P START WAITING TIME
MS_SWP_SP S.W.F.P STOP WAITNG TIME
MS_NU_PRE N/U PUMP PRE-RUN TIME
MS_TRO_SAMPLING TRO BOOST UNIT START WAITING TIME
MS_BLR_SP BLOWER SAFTY RUN TIME
MS_BLR_PRE BLOWER PRE-RUN TIME
MS_BLR_GAS BLOWER AUTO GAS RUN TIME
MS_F1(2/3)21_DP NO.1(2/3) AUTO BACKFLUSING DP. SET
MS_TE_NOR TE-1111 RECOVERY LIMIT
MS_CT_NOR CT-1111 RECOVERY LIMIT
MS_DTRO_HH_IMO IMO TRO TOO HIGH FOR DEBAL.
MS_DTRO_HI_IMO IMO TRO HIGH FOR DEBAL.
MS_DTRO_HH_USCG USCG TRO TOO HIGH FOR DEBAL.
MS_DTRO_HI_USCG USCG TRO HIGH FOR DEBAL.
MS_NU_TRG_IMO IMO TRO TARGET VALUE FOR DEBAL.
MS_NU_DB_IMO IMO TRO DEADBAND FOR DEBAL.
MS_NU_TRG_USCG USCG TRO TARGET VALUE FOR DEBAL.
MS_NU_TRG_IMO USCG TRO DEADBAND FOR DEBAL.
MS_AP_LO AFTER PEAK TANK LOW ALARM SET VALUE
MS_AP_LL AFTER PEAK TANK TOO LOW ALARM SET VALUE
MS_DP1(2/3)21_HH NO.1 FITLER DP. TOO HIGH ALARM SET VALUE
MS_DP1(2/3)21_HI NO.1 FITLER DP. HIGH ALARM SET VALUE
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Operation Manual HiB-M01010
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
Necessary Conditions
Check TRO reagent and replacement time (life time)
Buffer : 1bottle/year or 320hrs, Indicator : 1bottle/3month or 80hrs
All remote valves and instruments are operational.
BALLASTING START
- EU injection
- TRO sampling
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
7 Open XV-1731 or 1732 in sea water feed If low temp. of the feed water is expected,
unit using manual button. please open XV-1732(heater inlet) and close
XV-1731(heater bypass). The temp. of the feed
water can be checked by temp. sensor in EU
after start SWFP See below step no. 14.
8 Open EU injection flow control valve(s) Only open the valves in the direction operator
(FCV-1121/2121/3121) want to use.
- Initial open : 35%
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
9 Sea water feed pump start in manual Only start one pump (A or B).
(P-171A or P-171B)
10 Check disc. Pressure of sea water feed pump If disc. pressure of the pump is too low, it is
and DP of strainer (PT-1721) recommended to check mechanical seal, air
- Normal disc. pressure : 3 ~ 5.5 bar vent and manual valves in suction line.
11 Check the differential pressure between If DP of the strainer is higher than 0.7 bar,
strainer inlet and outlet. strainer cleaning to be done before operation or
- Normal range : <0.7 bar other side can be used by changing manual
valve and SWFP.
12 Check the level switch is on (green) in EU.
13 Check the temp. & salinity of the feed water. If temp. is low, heater in sea water feed unit to
(TE-1111/CIT-1111) be used. See above no. 8.
- Normal range If salinity is low, salt tank or dedicated sea
Temp. : >10℃ water tank to be used.
Salinity : 15PSU (Min. 13PSU)
14 Check injection flow and adjust if required Adjust injection flow control valve to get set
(FCV-X131) value.
- Normal range : see TRO SET in
SETTING parameters.
15 Start ballast pump(s) Only start the ballast pump in the direction
operator want to use.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
Ex)
HiB-6000 with 100D x 2set and 50D x 2set
Required total current : 1225A (0.74 CLF)
① : Press MANUAL button - 100D : 1225*(100/300) = 408A
② : Press RUN button - 50D : 1225*(50/300) = 204A
③ : Input the current and press CMD button
17 Start TRO sensor (AIT-X51) Green : Running
Grey : Stop(standby)
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
19 Check TRO value and adjust rectifier current It takes time to show actual TRO concentration
if required during operation. due to traveling time of side stream and
- Normal range : 5.5 ~ 10 mg/L(ppm) sampling line. (abt. 5 ~ 10 min.)
- Target : 8 mg/L(ppm) Please adjust rectifier current 10 min. after
rectifier start accordingly as below.
Ar = (TROt/TROp) x Ap
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
BALLASTING STOP
Caution!
Please make sure that the TRO sensor is stop.
Otherwise, TRO reagent (buffer and indicator)
will be consumed continuously.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
Necessary Conditions
Check TRO reagent and replacement time (life time)
Buffer : 1bottle/year or 320hrs, Indicator : 1bottle/3month or 80hrs
Check NA tank level (>50%, full filling is recommended)
All remote valves and instruments are operational.
DEBALLASTING START
- TRO sanpling
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
8 Start ballast pump(s) Only start the ballast pump in the direction
(60s after start NA pump) operator want to use.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
11 Check TRO value and adjust NA pump It takes time to show actual TRO concentration
capa. if required due to traveling time of NA injection and
- Normal range : < 0.1 mg/L(ppm) sampling line. (abt. 5 ~ 10 min.)
Please adjust NA pump capa. 10 min. after start
accordingly.
Caution!
If TRO is above 0.1 ppm due to high TRO
in ballast water even though the NA pump
is running with full capacity (100%), main
flow reduction operation is required.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
DEBALLASTING STOP
Caution!
Please make sure that the TRO sensor is stop.
Otherwise, TRO reagent (buffer and indicator)
will be consumed continuously.
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.
HiBallast NF System Doc. No.
Emergency Manual Operation Procedure HBD-001453-5.0
This publication or any part there of may not be reproduced or transmitted by any process or means without prior
written permission of Hyundai Heavy Industries Co., Ltd.