You are on page 1of 4

CHAPTER 4

VENTILATION AIR SUPPLY AND EXHAUST


(interior room) except through
adjoining rooms
401.0 Scope.
Covered by this chapter are the
requirements for ventilation air supply and shall be permanently unobstructed
air exhaust, makeup air requirements and and shall have a free area of not
evaporative cooling systems. It includes less than 8 percent of the net
also the pressure relationships and occupied area of the interior room
ventilation requirements for general acute or not less than 25 ft² (2.3 m²).
care hospitals are shown in Table 4-5 and [ASHRAE 62. 1:5.1.1]
filter efficiencies for general acute care are
shown in Table 4-6 and Table 4-7. 402.2.2 Control and
Accessibility. Operable wall or
402.0 Ventilation Air. roof openings shall be readily
accessible to building occupants
402.1 General Requirements. whenever the space is occupied.
Ventilation (outdoor) air for occupants [ASHRAE 62. 1:5.1.2]
shall be designed based on all rooms and
occupied spaces listed in Table 4-1 402.3 Mechanical Ventilation.
When the National Building Code
402.1.1 Construction of the Philippines do not allow
Documents. The design natural ventilation, the mechanical
calculations of the ventilation ventilation systems shall be
system requirements shall be designed, constructed, and
clearly shown on the construction installed to provide a method of
documents. supply air and exhaust air. The
mechanical system shall operate
402.2 Natural Ventilation. Instead of a so that all rooms and spaces are
mechanical ventilation system the use of continuously provided with the
natural ventilation systems designed in required ventilation rate while
accordance with this section shall be occupied.
permitted. [ASHRAE 62. 1:5.1]
Exception: An approved 403.0 Ventilation Rates.
engineered natural ventilation system by The design outdoor air intake flow rate for
the Authority Having Jurisdiction need not a ventilation system shall be determined in
meet the requirements of 402.2.1 and accordance with Sections 403.1 through
402.2.2 [ASHRAE 62. 1:5.1] 403.6.

402.2.1 Location and Size of 403.1 Zone Calculations. Zone


Openings. parameters shall be determined in
Spaces provided with natural accordance with Sections 403.1.1 through
ventilation shall have a minimum 403.1.3. [ASHRAE 62. 1:6.2.2]
permanent wall opening of 4% of
the net occupied area and shall be 403.1.1 Breathing Zone Outdoor
within twenty-five (25) feet (7,620 Airflow. The design outdoor
mm) of the operable wall or roof airflow required in the breathing
openings to the outdoors, zone for an occupied space or
Openings that are covered with spaces in a zone, i.e., the
louvers or otherwise obstructed, breathing zone outdoor airflow,
the wall opening are shall be shall be determined in accordance
based on the free unobstructed with Equation 4-1. [ASHRAE 62.
wall opening area. For naturally 1:6.2.2.1] [PSAVRE 2010 Section
ventilated spaces without direct 4.3]
wall openings to the outdoors
Vbz=RpPz+RaAz (Equation 4-1)
the outdoor air intake flow (Vot) shall be
determined in accordance with Equation
4.3. [ASHRAE 62.1:6.2.3]
WHERE: Vot=Voz (Equation 4-4)
Az= zone floor area: the net
occupiable floor area of the 403.3 100% Outdoor Air Systems.
zone ft.2 (m2). When one air handler supplies only
Pz= zone population: The largest outdoor air to one or more zones, the
number of people expected to
outdoor air intake flow (Vot) shall be
occupy the zone during typical
usage. If the number of people
determined in accordance with
expected to occupy the zone Equation 4-4.
fluctuates, shall be z permitted
to be estimated based on Vot=Ʃall zonesVoz (Equation 4-4)
averaging approaches
described in Section 403.5.2. If 403.4 Multiple Zone Re-circulating
cannot be accurately predicted Systems. When one air handler
during design, it shall be supplies a mixture of outdoor air and
estimated based on the zone re-circulated return air to more than
floor area and the default
one zone, the outdoor air intake flow
occupant density listed in Table
4-1 [Refer to 2010 PSAVRE
(Vot) shall be determined in
Table 4.3.2]. accordance with Sections 403.4.1
Rp= outdoor airflow rate required through 403.4.4 [ASHRAE 62.1:6.2.5]
per person as determined from
Table 4-1. = outdoor airflow rate 403.4.1 Primary Outdoor Air
required per unit area Fraction. When Table 4-3 is
Ra= Outdoor airflow rate required used to determine system
per unit area as determined ventilation efficiency, the zone
from Table 4-1 [ASHRAE primary outdoor air fraction (Z p)
1:6.2.2.1] [Refer to 2010 shall be determined in
PSAVRE Table 4.3.2].
accordance with Equation 4-5.
403.1.2 Zone Air Distribution
[ASHRAE 62.1:6.2.5.1]
Effectiveness. The zone air
distribution effectiveness ( ) Zp=Voz/Vpz (Equation 4-5)
shall be determined using Table
4-2 [ASHRAE 62.1:6.2.2.2] Vpz is the primary airflow to the
zone from the air handler,
403.1.3 Zone Outdoor Airflow. including outdoor air and re-
The required zone outdoor airflow circulated return air. [ASHRAE
shall be determined in accordance 62.1:6.2.5.1]
with Equation 4-2. [ASHRAE 62.
1:6.2.2.3] [The zone outdoor 403.4.2 System Ventilation
airflow is that amount of outside air Efficiency. The system
that must be provided to the zone ventilation efficiency (Ev) shall
through the supply air distribution be determined using Table 4-3
system]
or Appendix A of ASHRAE 62.1.
Voz=Vbz / Ez (Equation 4-2)
[ASHRAE 62.1:6.2.5.2]
[PSAVRE 2010 Section 4.3]
403.2 Single Zone Systems. When one
air handler supplies a mixture of outdoor 403.4.3 Uncorrected Outdoor
air and recirculated air to only one zone, Air Intake. The design
uncorrected outdoor air intake duration or the ventilation rate
(Vou) shall be determined in will be varied or uninterrupted
accordance with Equation 4-6. for a short period of time, the
Vou=D Ʃall zones RpPz + Ʃall design shall be permitted to be
zones RpAz based on the average
(Equation 46) conditions over a time period
The occupant diversity, D, shall be determined by Equation 4-9.
permitted to be used to account for [ASHRAE 62.1:6.2.6.2]:
variations in occupancy within the
zones served by the system. T=3v/Vbz (4-9) IP (Equation 4-9)
The occupancy diversity is defined
WHERE:
as:
T= averaging time period, (min)
D=Ps/Ʃall zonesPz (Equation 4-7) V= the volume of the zone for
whichever aging is being
Where the system population (Ps) applied, ft.3 (m3).
is the total population in the area Vbz= the breathing zone outdoor
served by the system. Alternative airflow calculated using
methods shall be permitted to be Equation 4-1 and the design
used to account for population value of the zone population P,
diversity when calculating Vou, cfm (L/s).
provided that the resulting value is
no less than that determined by 403.6 Dynamic Reset. The system
Equation 46. [ASHRAE
shall be permitted to be designed to
62.2:6.2.5.3] [PSAVRE 2010
Section 4.3] vary design outdoor air intake flow
(Vot), or the space or zone airflow as
403.4.4 Outdoor Air Intake. The operating conditions change.
design outdoor air intake flow (Vot)
shall be determined in accordance 403.7 Exhaust Ventilation. Exhaust
with Equation 48. [ASHRAE airflow shall be provided in accordance
62.1:6.2.5.4] [PSAVRE 2010 with the requirements in Table 4-4.
Section 4.3] Exhaust makeup air shall be permitted
to be any combination of outdoor air,
Vot=V/ouEv (Equation 4-8) re-circulated air, and transfer air.
403.5 Design for Varying Operating
404.0 Make-up Air.
Conditions.
Makeup air requirements shall be
based on the amount of exhaust
403.5.1 Variable Load
airflow. Pre-cooling of make-up air
Conditions. Ventilation
shall be allowed.
systems shall be designed to be
capable of providing the
405.0 Evaporative Cooling Systems.
required ventilation rates in the
Evaporative cooling systems shall not
breathing zone whenever the
be used for make-up air cooling and
zones served by the system are
shall comply with the provisions of this
occupied, including all full and
chapter.
part load conditions. [ASHRAE
62.1:6.2.6.1]
Evaporative cooling systems shall be
provided without side air as specified
403.5.2 Short-term
for cooling systems in this code.
Conditions. If it is known that
peak occupancy will be of short
Air ducts and fire dampers that are a least six (6) inches (152mm)
portion of an evaporative cooling above the adjoining ground
system shall comply with this code. level.
405.1 Location. Evaporative
cooling systems shall be 406.0 Example: Determine the
installed so as to minimize the outdoor air rate required for a single
probability of damage form an zone AC unit serving an interior
external source. 2000ft.2 meeting/conference room with
a design occupancy of 100 people.
405.2 Access, Inspection, and The system supplies and returns air
Repair. Evaporative coolers from the ceiling.
shall be accessible for
inspection service and the Per Table 4-2, the zone air distribution
replacement without removing effectiveness in 1.0 since the system
permanent construction. supplies cooling only from the ceiling.
Using the rates from Table 4-1 for a
405.3 Installation. An meeting/conference room, the
evaporative cooler supported by minimum system outdoor air rate is
the building structure shall be calculated to be:
installed on a substantial level
base and be secured directly or V= (RpRz+RaAz)/Ez
indirectly to the building = (5×100+0.06×2,000)/1.0
structure suitable means to = 620 cfm
prevent displacement of the
cooler. 407.0 Referenced Publications. The
documents or portions of this chapter
Modifications made to the have been reproduced from the
supporting framework of Mechanical Code 2007 and Tables
buildings as a result of the from the ASHRAE 60.2 publications.
installation shall be in
accordance with the
requirement of the National
Building Code. Openings in
exterior walls shall be flashed in
an approved manner in
accordance with the
requirements of the Building
Code.

An evaporative cooler
supported directly by the ground
shall be isolated from the
ground by the level concrete
slab extending not less than
three (3) inches (76mm) above
the adjoining ground level.

An evaporative cooler
supported on an above ground
platform shall be elevated at

You might also like