Professional Documents
Culture Documents
Pre-Programmed Important Notes: (NYC Abort – Does not comply with UL864)
Applications Specific operation of the NYC Abort is as follows:
Pressing the Abort switch does the following:
Releasing the Abort switch starts the 90-second Investigate Timer. When the
Investigative Timer expires, the following occurs:
Subsequently pressing/releasing the abort switch repeats the process (silencing the
NACs, activating the bell, starting the 90 second investigation timer, etc.) until the
Release Timer expires and the RAC(s) activate.
Pressing/releasing the Abort switch while the Investigation Timer counts down has no
effect (i.e., it will not reset the timer).
Note: All other abort switch modes are discussed in “Programming Abort Switch Operation” in Chapter 4
of this manual.
1-7