Site ID Tower HT District PAT Date


S.N Progress

CDR698 Sunrise CDR 35 DHANUSHA Yes 2021/7/20


1

CDR718 ABC CDR 25 DOLAKHA Yes 2022/7/7


2
3 CDR727 Sunrise CDR 35 DHANUSHA Yes 2021/8/1

4 CDR731 Sunrise CDR 35 DHANUSHA Yes 2021/7/19


Khadka
CDR737 Engineering CDR 25 NUWAKOT Yes 2022/10/18
5 / DipKiran

CDR773 SUNSHINE CDR 25 DHADING Yes 2022/10/20


6

CDR867 ABC CDR 35 BARA Yes 2021/2/25


7
8 CDR909 ABC CDR 35 DHANUSHA Yes 2021/7/18

9 CDR913 Sunshine CDR 35 DHANUSHA Yes 2021/12/11

MWDR773 #N/A MWDR RTT BANKE Yes 2022/11/27


10

CDR1002 DIP Kiran CDR 25 NUWAKOT Yes 2023/1/20

11

MWDR244 #N/A MWDR #N/A BANKE Yes 2022/11/13


12

MWDR351 ABC MWDR 35 DANG Yes 2021/8/21


13

MWDR364 ABC MWDR 25 PYUTHAN Yes 2021/4/3


14
Assure
MWDR456 MWDR 25 SURKHET Yes 2021/12/7
15 Solutions

16 MWDR477 VSV MWDR 25 SALYAN Yes 2022/8/1

MWDR510 VSV MWDR 25 ROLPA Yes 2021/8/19

17
Assure
MWDR527 MWDR 25 KALIKOT Yes 2022/11/21
18 solutions
19 MWDR548 VSV MWDR 25 KALIKOT Yes 2022/11/18

MWDR560 VSV MWDR 25 SALYAN Yes 2022/2/2


20

MWDR567 ABC MWDR 25 DANG Yes 2021/12/15

21

MWDR568 SUNSHINE MWDR 25 DANG Yes 2022/3/18

22
Assure
23 MWDR581 MWDR 25 RUKUM_E Yes 2022/3/23
Solutions
24 MWDR583 ABC MWDR 25 RUKUM_E Yes 2022/3/26

MWDR597 Colt Infra MWDR 35 BARDIYA Yes 2022/6/29

25
26 MWDR600 SUNSHINE MWDR 25 BANKE Yes 2021/11/18
Assure
27 MWDR609 MWDR 25 DAILEKH Yes 2022/8/11
solutions

MWDR614 ABC MWDR 25 RUKUM_E Yes 2022/9/30

28

MWDR624 VSV MWDR 25 JUMLA Yes 2022/11/19


29

MWDR638 Colt Infra MWDR 35 DANG Yes 2022/11/27


30

MWDR641 Colt Infra MWDR 25 ROLPA Yes 2022/6/29


31

MWDR646 SUNSHINE MWDR 25 SALYAN Yes 2021/11/1


32

MWDR648 SUNSHINE MWDR 25 PYUTHAN Yes 2021/11/3


33

MWDR655 VSV MWDR 25 SALYAN Yes 2022/8/2


34

MWDR660 VSV MWDR 25 SURKHET Yes 2022/12/12


35
MWDR664 Colt infra MWDR 25 SALYAN Yes 2022/9/28

36

MWDR666 ABC MWDR 25 PYUTHAN Yes 2022/4/1

37
Heramb/
38 MWDR667 MWDR 25 PYUTHAN Yes 2022/10/22
Colt

KTM435 #N/A CDR RTT KATHMANDU Yes 2022/6/26

39

Khadka
CDR934 CDR 25 KAVRE Yes 2022/10/15
Engineering

40
41 CDR1047 GENESIS CDR 25 SINDHUPALCHOWK Yes 2022/8/24

CDR1028 GENESIS CDR 25 SINDHUPALCHOWK Yes 2022/9/28

42
43 CDR1098 DIP Kiran CDR 25 SINDHULI Yes 2022/9/25
Snag Details
Responsible pers Material requirement
Cable 35sqmm
1. LA value is high.
Shanta
3. TGB-1 busbar missing.
4. EGB to TGB YG cable missing. 45

2. LA=35
Shanta
3. Phase L3 not in supply

1. LA earthing value High.


Shanta 20
2. TGB1- TGB2 yg cable not available
1. TGB to EGB no y/g cable.
Shanta 45
2. No la cable

Shanta
6. NEA cable should route properly.
1. LA value high
2. Earth PIT construction not done. Shanta

1. TGB1 to TGB2 is not connected, TGB2 is not connected to pit,


2. EGB to equipment pit is not connected,
Shanta
3. LA cable is not installed,
45
Shanta 45
3. Cable tray and equipment base is touched with ground.
L2 phase missing Shanta
1. 2nd Phase Voltage Missing.
2. TGB-EGB Not Connected.
3. LA Cable not Available.
4. Earthing value not measure due to absence of Meggor. Manoj NA
1.NO TGB-EGB Earthing Cable connection
2.Shelte Light Stolen
3. Shelter light cabe is kept on back of shelter, need in front
4. No La Earthing Cable Shanta
5. No TGB1 & TGB2 Earthing Connection
6. LA earthing value high 65 ohm.
7. Aviation lam not light up 35
1. Equipment earth resistace is high i.e. 8.5Ohm.
2. ACPDB SPD missing.
4. Only single phase supply, no supply in two phase. Manoj
1. Printed labelmissing in CPRI, RRU power & load cable.
2. EQ & LA Cable are not of standard size.
3. Cable clamp need to add in each sector.
4. LA value seem higher than threshold(5.6Ohm). no issue site 45
1. Earthing value higher than threshold, 11.62ohm.
2. LA value higher than threshold, 11.91ohm
3. LA & earth cable are not running parellel and neatly in cable ladder.
Manoj
1. One pcs solar panel broken.
2. 11pcs earthing strip not connected to solar foundation base.
3. One set support base need at horiziontal ladder. no issue site
1. YG cable for EQ/LA from TGB to EGB is missing.
2. 4pcs solar panel broken. Manoj 35
1. High EQ & LA Value( EQ=16.29Ohm; LA=17.87OhM).
2. LA Cable missing.
3. TGB1-TGB2 earthing cable missing.
4. TGB2-EGB earthing cable not of standard size.(i.e. 25mm sq.)
Manoj 35
1. LA value high(29.4Ohm).
2. EQ is high(12.16Ohm).
3. B20 is not working due to shortage of E4 card(E2 card is used instead). no issue site
2. LA value high(29.4Ohm) Manoj
1. LA value=32.6ohm.
2. EQ value=12.4ohm

11. ODU not earth to TGB at both end. Manoj

7. YG cable not routed properly(all).

14. LA earth value high, 28Ohm. Manoj


1. No earthing of LA.
2. Higher value of LA
3. Ladder lid jammed, must be opened
5. Horizontal ladder must be repaired..
7. Feet of the vertical ladder does not support along the ground.

9. Aviation power cable must be replaced. Manoj


1. LA & EQ value hgh. Manoj
1. Earthing value of EQ & LA high. Manoj
1. LA earth resistance high 10.15ohm.
2. LA earthing cable not present.
3. Eq earthing cable not present
4. NEA meter base is not stable need to fix
5. NEA meter MCB not instelled.
6. Ground busbar(EGB,TGB) not present. Manoj 45
1. Lighteing Arrester Earthing cable not found. Manoj
Solar structure grounding not done. Manoj
1. Earthing value high 47.5.5Ohm.
2. LA value high. 75Ohm
3. EGB plate not installed with insulated and not connected 35mm sq. cable
with earthing pit(EGB to pit)
4. Aviation lamp not installed.
5. LA cable missing.
6. AC 4 core armoured cable (copper) not connected to ACDB to meter box. Manoj 35

2. 36 pcs of solar foundation nut missing.


3. Aviation lamp cable missing. Manoj
1. TGB1-TGB2 YG cable missing.
2. LA cable missing
3. Aviation Lamp not Present at Site Manoj 45
1. EQ & LA value high.
2. No 50mm YG cable from LA to LA pit & TGB to EGB.
3. Jumper cable bending radius & diameter is very less.
4. Cable ties, cable clamps are not properly used and cut no issue site 35
.
2. LA value high.
3. Aviation lamp power no connection. Manoj
1. LA value high.
2. EQ value high( EQ YG cable not connected to pit)
3. Meter box to MCB power cable should be changed to new one. Manoj 35
1. AC phase & neutral short circuited.
2. AC SPD burnt.
3. Service not tested. Manoj

2. High earthing value of LA.


3. IP55 meter box stands are not concreted need base casting of snags. Manoj
1. LA Cable(35mm2) is not installed.
2. Equipment Cable(35mm2) is not installed.
3. LA Earthing value is 50ohm(High)
4. ACDB Door Broken.
5. SPD Missing in ACDB.
6. AC cable duct pipe should be buried. Manoj 35

3. TGB1, TGB2 & YG cable from TGB to EGB not found.


4. Copper stripfrom pit to EGB not buried.

12. LA rod, TGB1 plate & TGB2 plate not installed.


17. EQ & LA value high. Manoj 35
1. High LA value=35.1 Ohm.
2. High EQ value=22.2 Ohm. Manoj

21. NEA power connection from pole to submeter not routed properly, extra
cable left hanging,
Shanta NA
27. Earthing not measured/no megger (no subcon on site),

1. No TGB1 & TGB2


2. EGB missing
3. LA Cable missing
Shanta
4. TGB to EGB Cable missing
5. ACPDB to EGB Y/G cable missing
6. EGB to IGB Y/G cable missing 35
1. TGB1, TGB2 & EGB not connected.
Shanta 35
2. LA value high

3. ACPDB to halogen lamp cable should be routed through duct pipe.


no issue site
7. LA value high 94.5 ohm

LA Value High Shanta


685
Material requirement Remarks Remarks
Cable 50sqmm Busbar Other Rectification timeline

1 SPD SPD done

Grounding value

45

power problem

earthing PIT

45
to be solved on mutual understanding
power problem

NA power problem

35 BULK HeadBulkhead and AWL problem

SPD SPD and Power problem

45 grounding value

grounding value

35

35 grounding value

grounding value
grounding value

grounding value

grounding value

35 AWL cable
grounding value
grounding value

45 3 Power problem, Grounding value


35
cw

35 Need to check with Subcon

AWL cableAWL cable

45 AWL

35 Grounding value

AWL cableGrounding value

Grounding value

SPD

Grounding value
35 SPD CW

35 3 LA rod Grounding value


Grounding value

NA Grounding value

35 3
Grounding value

Grounding value
Grounding value
575
on timeline
Site ID Snags Responsible Person

1. Phase1 & phase2 voltage overhigh>320V; need rectification.


EDR940 2. Neutral grounding voltage high 298, need rectification.
3. Due to high voltage rectifier modules are not working properly. Saurav
EDR653 EQ & LA earthing value high Saurav
1. ACDB grounding required with connector and routed properly.
2. EGB busbar should be fixed.
3. TGB-EGB LA & EG need routing & proper connection at EGB.
EDR719
4. NEA second phase L2 missin.
5. AWL not working.
6. LA value high. Saurav

EDR840 4. EQ & LA YG cable not installed on site.


5. LT panel & main meter box not fixed permanently with GI channel. Saurav
1. Entry door does not lock due to landslide near door.
EDR902 Saurav
2. LA & EQ earthing pit cover does not fixed properly.
WDR450 1. EQ & LA earthing vlue is too high. Sudip

FWDR378 3. Aviation lamp and power cable is not installed.


4. Lighting arrister rod is missing.
Manoj
WDR173 1. Earthing value high(both EQ & LA) Afzal
1. R-phase missing, need to rectify ASAP.
EDR842 Saurav
2. LT power able hanging on tree, need to add three pole for rectification ASAP.
requirement Remarks Remarks timeline
Cable 35sqmm Cable 50sqmm Busbar Other

Apr-week 2
power problem
grounding value Apr-week 2

Apr-week 2

grounding value

Apr-week 3
45 45

CW Apr-week 2
Grounding value Apr-week 3

Apr-week 3

AWL, LA rod
Grounding value Apr-week 3
Apr-week 3