You are on page 1of 7

Voltage sags:

effects, mitigation
and prediction
Customers all over the world experience problems due to voltage sags.
Computers, industrial control systems, and adjustable-speed drives are
especially notorious for their sensitivity. Tripping of high-power adjustable-
speed drives is probably the main voltage sag problem, The number of trips
depends strongly on the equipment sensitivity. Prediction methods are needed
to quantify this aspect of the quality of the supply. From utility and
manufacturer's data, a customer can assess the compatibility between a piece
of equipment and the electricity supply.

by Math H.J. Bollen

Introduction distance between the fault and the customer.


A voltage sag, or voltage dip, is a reduction The duration of the voltage sag is determined
of the voltage at a customer position with a by the fault-clearing time of the protection.
duration of between one cycle and a few There is unfortunately some confusion about
seconds. Voltage sags are caused by motor how t o characterise the voltage sag. Some
starting, short circuits and fast reclosing of characterise it by the deviation from the
circuit breakers. normal or pre-sag voltage. Others use the
Voltage sags occur in power systems all voltage during the sag. Following the North-
over the world. They are a nuisance for many American practice, I will use the terrri 'sag
industrial and commercial customers; they magnitude' for the voltage during the fault.
are impossible t o prevent; but it is often This convention will make it easier t o
possible t o mitigate the impact on compare sag magnitudes with equipment
equipment. Like other power quality sensitivity.
problems, this one needs co-operation Its magnitude and duration describe the
between the utility, the customer and the voltage sag in sufficient detail for most
manufacturer of the equipment. Before a applications. Based on these t w o parameters,
decision about mitigation can be made, an a scatter plot can be obtained from
assessment of the expected number of sags is monitoring the supply for a certain period.
needed. Such an assessment can be made Fig. 2 shows the results of a North American
through measurements or by using power quality monitoring project. Shown are
stochastic prediction methods. phase-to-neutral voltages at low-voltage
This article discusses some results of customers. (The clustering around durations 1 Voltage sag d u e t o a
voltage sag surveys. Surveys are one way t o of one and four cycles is due t o the short circuit
get an impression of the expected number of
voltage sags as a function of magnitude and
duration. The alternative is t o use stochastic
prediction methods. These lead t o results
much faster and are potentially more
powerful. Afast estimation method is
presented; and some alternative methods are
mentioned. The effects of voltage sags on
various types of equipment are discussed and
some mitigation methods are also
mentioned. Finally, voltage sags are treated
as an aspect of the compatibility aspect
between the supply and the equipment.

0bservat io ns
A typical shape of a sag due t o a short
circuit is shown in Fig. 1 . The voltage during
the sag is determined by the electrical
POWE'R ENGINEERING JOURNAL JUNE 1996 129
2 Scatter plot processing of the measurements.) The 10.5 sags per year of duration longer than
resulting from voltage
monitoring took place at a large number of 100 ms and magnitude less than 70% etc.
sag monitoring at a
number of sites in the sites. Sags are most common in the parts of From such a cumulative table, one can
USA the graph where the dots have coloured it immediately estimate the expected number
black. We can distinguish between sags due of trips for given equipment sensitivity. It is
t o short-circuit faults (durations up to about thus easy t o realise that all equipment more
one second), due t o motor starting (longer sensitive than 70%, 1 OOms is actually not
durations and magnitudes above 80°/0),and suitable for connecting t o this system. In
due t o fast reclosure (longer durations, other words: there is a compatibility problem
magnitudes close t o zero). between this equipment and the supply.
Alternative methods of presenting the
results of a voltaqe saq survey are:
I I
Effects and mitigation
The main reason for the increased interest
distribution or density function of the sag in voltage sags is that modern equipment is
magnitude or duration often not able t o withstand such sags.
a two-dimensional histogram of number Computers, process control equipment and
of sags versus duration and magnitude power electronics equipment are notorious
a table with each entry showing the for their sensitivity. Trip frequencies of once a
number of sags of a given duration and week and more have been reported. Also
magnitude range some more classical pieces of equipment still
a curriulative table with each entry cause problems due t o voltage sags:
showing the number of sags exceeding a
certain duration and magnitude Consumer electronics equipment like
a chart of magnitude versus duration with personal computers, compact disc
lines connecting points with the same players, electronic alarms, video recorders
expected number of sags exceeding that and microwave ovens can reset due t o a
magnitude and duration. short reduction in voltage. The sensitivity
(maximum permissable saq) varies from
Table 1 shows some results of t w o years of 85% during half a cycle u p t o 50% during
voltage sag monitoring in the United 1 s. (A sensitivity of 50%, 1 Oms, means
Kingdom. Each entry in the Table gives the that the equipment will trip if the voltage
number of sags exceeding the given duration is below 50% of its nominal value for 10
and magnitude. There are thus on average ms.) From Table 1 it is easy t o conclude

Table 1 Monitoring results for t h e UK: number of voltage sags exceeding given magnitude
and duration

130 POWER ENGINEERING JOURNAL JUNE 1996


~

that the number of trips will vary from Some manufacturers offer drives with
two per year up to almost 50 per year. For improved 'ride-through'. One o f t h e
household equipment tripping is a problems is that many customers are not
nuisance but seldom a very serious aware of voltage sag problems vvhen they
problem. The problems are more serious buy a drive and go for the (seemingly)
for office equipment. cheaper option. When the drive is
0 Control systems for industrial processes installed and thevoltage sag induced trips
are equally sensitive. Spurious tripping of become apparent, it's often too late for a
continuous processes can cause serious simple solution. As long as there is not
loss of revenue and it can even lead to sufficient customer demand, nor any
dangerous situations. In most industrial standardisation, most manufacturers will
processes therefore the control system is not equip their standard drives with
protected against sags as much as improved 'ride-through'.
possible. 0 AC adjustable-speed drives are often fed
0 Both types of equipment are fed from an from a three-phase non-controlkd
internal DC bus through a single-phase rectifier (six or twelve-pulse diode bridge).
rectifier (e.g. a simple diode bridge). The The voltage a t the DC bus is more or less
rectifier operates as a DC voltage source constant. To protect the diodes against
through a capacitor connected t o the DC large inrush currents, the DC bus is
bus. If the voltage a t the DC bus gets too equipped with under-voltage and over-
low the equipment (often some kind of voltage protection. If the DC voltage
digital electronics or microprocessor) will drops for example below 85% of its
malfunction. The capacitor will keep the nominal value, a trip signal will be
voltage up for some time but often not generated immediately. As the bus
longer than a few cycles. The acceptable capacitor will not keep up the voltage for
sag duration depends, among other much more than a few cycles, it IS clear
things, on the capacitor size in relation to that these drives are very sensitive to
the DC load. voltage sags. Possible solutions are
0 Another thing that both types of installing larger capacitors, and/or using
equipment have in common is that they part of the rotational energy in the motor
are basically low power (the main power inertia to keep up the bus voltage.
is often taken by less-sensitive loads like
fans and monitors). It is therefore not too
difficult to feed them from an
uninterruptable power supply (UPS). A
UPS consists of a rectifier, a DC bus with a
battery block connected to it, and an
invertor (see Fig. 3). If the AC input
voltage drops, the DC voltage is kept up
with power from the battery and the AC
output is not affected. A UPS can ride
through sags and even interruptions up
to several minutes in duration. The cost of
a UPS is low enough to justify its use for
industrial control systems, and for
important office equipment. They are,
however, seldom justifiable for home use.
0 Looking a t the way a computer is fed 0 DC adjustable-speed drives and large AC 3 Simplified structure
through a UPS (AC to DC and DC t o AC in drives are fed from a three-phase of an uninterruptable
the UPS and again AC to DC in the controlled rectifier (either three cliodes power supp'y(ups)
computer), one easily concludes that and three thyristors, or six thyristors). The
there are too many conversions. It should problems become a bit more cornplicated
not be too difficult to manufacture a here. As most faults are single-phase or
computer in which a battery block can be phase-to-phase faults (especially on
inserted. Every laptop computer has this overhead lines), the voltages in the three
provision already. A next step would be t o phases are seldom of the same
think about the feasibility of a DC magnitude. For a non-controlled rectifier,
distribution system for offices and some kind of average of the threlz-phase
eventually even a t home. voltages will determine the resulting DC
0 Many adjustable-speed drives are too bus voltage, and thus whether the drive
large to be fed from a UPS, and they are will trip or not. For a controlled rectifier,
often essential for the production additional problems can occur with the
process. Their sensitivity varies from 85%, firing of the thyristors. This can be
10 ms, up to 50%, 500 ms. If this aggravated as sags are associated with a
equipment needs to ride through a sag, jump in the phase angle of the voltage.
some large energy storage is required, like The firing-angle control will have
the recently proposed superconducting difficulties following this jump. The
magnetic energy storage (SMES) devices. control system can get disturbed which
However, there has not been much can lead to damage to the thyristors. To
evidence as to their feasibility. prevent damage, most drives are
POWER ENGINEERING JOURNAL JUNE 1996 131
nonessential motors faster than essential
motors. This will make more of the supply
available t o re-accelerate the essential
motors.
Some types of discharge lighting take
minutes t o restrike after a severe voltage
sag. The obvious answer here is t o feed
the essential parts of the lighting via a
battery backup.

In a large production process there are many


pieces of equipment that are sensitive t o
voltage sags. It is not always easy t o find the
piece of equipment that actually causes the
production process t o stop.

Prediction methods
The results of monitoring the supply for a
certain period can be used t o estimate the
expected number of sags of various duration
and magnitude. Such information can be
used t o assess how often a certain piece of
equipment will trip due t o voltage sags. This
will help in deciding about the purchase of
equipment, Voltage sag monitoring is a very
useful tool. It is especially suitable t o obtain
an 'average quality of supply' for a certain
country or area.
Its use for a single site has some
limitations, however. Voltage sag monitoring
for one site can take a long time, especially if
one is interested in less-frequent sags. As
shown in Fig. 4, the number of voltage sags
differs considerably through the year. This
implies that a monitoring period of a t least
one year is required, even for very frequent
sags. There are ways t o correct for seasonal
and other variations: they require additional
information and some assumptions. From a
monitoring study, it is also difficult t o obtain
information on the effect of system changes.
Stochastic prediction methods do not have
these limitations. They form an important
4 Variation of equipped with protection that trips the addition t o voltage sag monitoring. These
frequency of voltage drive if anything suspicious occurs, like prediction methods are based on techniques
sags through the year;
results from a large unbalance or under-voltage. This also used for power system reliability analysis.
North American survey protection determines the sensitivity of A very simple prediction method is based
the drive t o voltage sags. on the voltage divider equivalent circuit. The
5 Radial distribution The electricallyheld contactor drops out basics of the method are best explained for
network with fault three-phase faults. Single-phase and phase-
position (F), position of
when the voltage magnitude gets below
sensitive load (L), and about 60% for more than a few cycles. to-phase faults can be treated similarly,
point-of-common- This problem can be mitigated by using a although some complications can occur.
coupling (PCC) battery source for the contactor, by To calculate the sag magnitude for a fault
supplying essential motors through circuit somewhere within a radial distribution
breakers, or by using a contactor with system, one must find the point of common
automatic reclosure, coupling (PCC) between the fault and the
Synchronous motors and induction load, as shown in Fig. 5. Fig. 6 shows the
motors stall when the voltage gets too voltage divider model, whereZ, is the source
low for too long. Especially for induction impedance a t the PCC; Z,is the impedance
motors the strength of the supply has a between the PCC and the fault (including any
considerable influence on what is fault impedance). For three-phase faults only
acceptable. Even without stalling the positive sequence impedances are needed.
motor, a voltage sag can cause problems For single-phase faults one needs t o use the
when the speed or torque requirements sum of positive, negative and zero-sqeuence
of the process are no longer met. In impedances. The sag magnitude (Yo)a t the
practice it is not so much the actual load position equals the voltage (%) a t the
stalling of he motors that causes the PCC if we neglect all load currents:
problems, but their tripping by under-
voltage relays. Loss of the production Vsag =
L2

process can be avoided by tripping z, + z2


~

(1)

132 POWER ENGINEERING JOURNAL JUNE 1996


We see that the sag becomes deeper for
faults closer t o the PCC (smallerz,) and for a
weaker supply (IargerZ,) Fig. 7 shows the
influence of the distance t o the fault and the
source strength on the sag magnitude for a
PCC at 1 1 kV.
Assume that there is a 'critical voltage'
below which the equipment will trip, and
above which it will not trip. Eqn. 1 can now
be used t o estimate the expected number of
equipment trips. For a given sag we have t o
consider all fault positions for which

Let Z,= Yxz, with zthe feeder impedance


per kilometre, and 'LJ!the distance between
the fault and the PCC. Assume further that
theXIR ratios of Z, and Z,are equal. We
can then calculate the 'critical distance' Zcnl
as:

Any short circuit at a distance less than the


critical distance from the PCC leads t o
tripping of the equipment. Fig. 8 shows the
critical distance for a PCC at 1 1 kV, with
short-circuit powers of IO,30 and 100 MVA.
We see that the critical distance, and thus the
expected number of sags, increases very distance between fault and PCC
quickly for increasing critical voltage. The
critical distance also increases for decreasing
short-circuit power of the source.
Table 2 gives critical distance for various distance is t o some degree compensated for, 6 Voltage divider
voltage levels and short-circuit powers. The as lower voltage lines attribute more faults model Of a sag
critical distance increases considerably for and longer fault-clearing times. 7 Sag magnitude as a
higher voltage levels: from less than 1 km for TO estimate the expected number of sags function ofthedistance
400 V, up t o hundreds of kilometres for 400 at a certain load position, the critical distance between the fault and
kV. As the short-circuit current is of the same has t o be calculated for every possible PCC. the PCC. for threevalues
of the short-circuit
order of magnitude for all voltage levels, the What results from this exercise is the so-
power at the PCC
critical distance will be roughly proportional called exposed area. Every fault within this
t o the voltage. This increase in critical exposed area will lead t o tripping of

8 Critical distance
against critical voltage
at 11 kV

POWER ENGINEERING JOURNAL JUNE 1996 133


Table 2 Critical distance for various voltage levels and short-circuit powers

equipment. The expected number of sags contribution of a feeder t o the number of


can simply be obtained by adding the sags with a voltage magnitude less than V , is
expected number of faults within the proportional t o W(1 - U). As this holds for all
exposed area, The latter can be obtained feeders, the total number of sags will also
from failure statistics. show this relation. Fig. 9 compares this
For three-phase faults the above method theoretical relation with the results of voltage
can be used easily. For single-phase and sag monitoring. The monitoring results
p hase-to- p hase fau Its some com pl icat ions clearly confirm the simple approximation.
occur:
More accurate prediction methods
The critical voltage used is the voltage in In some cases the above method is not
the faulted phase a t the PCC. Due t o the suitable. This happens, for example, when
transformer connections, this is not the the system is strongly meshed or when the
voltage a t the load terminals. expected number of sags of various durations
0 Single-phase and phase-to-phase faults and magnitudes is sought. Other methods
cause different voltage magnitude in have t o be used then:
different phases. The behaviour of three
phase equipment due t o these is often A straightforward method is t o calculate
hard t o assess. magnitude and duration of the voltage
sag for many possible faults. After taking
For each voltage level one needs t o the failure rate for each fault into
determine which voltage a t the PCC will account, the expected number of sags as
cause the sensitive equipment (at a lower a function of magnitude and duration can
9 Number of voltage voltage level) to trip. be calculated. The method from the
sags below a certain The method is presented here for radial previous section can then be used t o
voltage, as a function of svstems. It has been applied successfullv t o estimate the area within which faults have
that voltage: some non-radial systems too. For meshed t o be studied.
comparison between
monitoring results and
systems like the 400 kV grid it certainly has its To take second-order events (like failure of
theoretical limitations. the protection) into account, detailed
approximation From eqn. 3 we can conclude that the stochastic models are needed.
In systems with large motor
concentrations it is necessary t o take the
shape of the voltage sag into account. It is
then no longer enough t o characterise
the sag through magnitude and duration
only.

Equipment compatibility
Voltage sags have t o be treated in the light
of the compatibility between equipment and
supply. Before connecting a piece of
equipment t o the electricity supply, the
equipment’s compatibility t o that supply
should be checked. To do this it is required t o
know the performance of the supply, and the
sensitivity of the equipment. The (voltage sag
aspect of the) performance of the supply can
be quantified, as shown in Table 1 . If the
equipment sensitivity is known, the customer
can estimate the expected number of
equipment trips. He can then decide t o install
a UPS, t o ask the equipment manufacturer
for improved ride-through, t o ask the utility
for improved power quality, or simply t o
accept the situation.
134 POWER ENGINEERING JOURNAL JUNE 1996
It is often hard for a customer t o obtain the Applications, 1993, 29, pp.397-40.3
required information from the equipment 4 CONRAD, L.E. (Chair):'Proposed Chapter 9 for
manufacturer or from the utility. Often predicting voltage sags (dips) in revision to
neither the manufacturer nor the utility has IEEE Std 493, the Gold Book', /€E€
the information available. There are, Transactionson lndustry Applications, 1 994,
30,pp.805-821
however, tools available and under
5 IEEE PI346 Working Group (Chair: \/.
development t o assess the performance of Wagner): 'Electrical power system
the supply and the sensitivity of equipment. compatibility with industrial process
Apart from the lack of knowledge there is a equipment - Part 1 : Voltage sags', IEEE
certain amount of fear that somebody will be Industrialand Commercial Power Systems
blamed for the problems. Poor power quality Technical Conference, May 1994, Irvine, CA,
is, however, nobody's fault. It is simply a USA, pp.261-266
consequence of various technical and 6 DORR, D.S.: 'Point of utilization of power
economic develop ment s . Power q uaIity quality study results', lfff Transactionson
problems like voltage sags call for close co- Industry Applications, 1995,31, pp.658-666
7 BOLLEN, M.H.J.:'Method for reliability
operation between utility, manufacturer and analysis of industrial distribution systems', /€E
customer. Proceedings C, 1993, 140, pp.497-502
8 BOLLEN, M.H.J.:'Fast assessment m'ethodsfor
Further reading voltage sags in distribution systems', IEEE
1 KEY, T.S.: 'Diagnosing power-quality related Industry Applications Society Annu&
computer problems', I€€€ Transactions on Meeting, October 1995, Orlando, FL, USA.
Industry Applications, 1979, 15, pp.381-393
2 WAGNER, V.E. eta/.:'Powerqualityand
factory automation', I€€€ Transactionson 0 IEE: 1996
Industry Applications, 1990, 26, pp.620-626 ~~

3 McGRANAGHAN, M.F., MUELLER, D.R., and The author is with Manchester Centre for Electrical
SAMOTYJ, M.J.: 'Voltage sags in industrial Energy, UMIST, PO Box 88, Manchester IM60 1QD,
power systems', IEEE Transactionson lndustry UK. He is an IEE Member.

Ferroresonance -
mystery, mythology
and magic!
The subject of ferroresonance in electric small business units with power factor
power systems was addressed at a discussion correcting capacitors. The unfortunate
meeting enticingly titled: 'Warning! circumstances could be triggered by the
ferroresonance can damage your plant!' at combination of light loading and network
Savoy Place recently. The level of interest in conditions (fault location with unusual
the subject was demonstrated by the large si ng Ie- p hase con d it io ns).
audience (93 compressed into the Faraday Doug Ellis (Eastern Electricity) showed that
Room) who had turned out despite bitterly it was possible t o have ferroresonant circuits
cold weather and several centimetres of containing a wide range of capacitance due
snow in the home counties. t o lengths of underground cable- from
Ferroresonance is the name given t o 40 m t o over 1000 m . When considering a
resonance in which the resonant circuit simple pole-mounted transformer in series
consists of a capacitance and a nonlinear with a length of underground cable,
i ron-cored inductance driven into satu ration. ferroresonance was demonstrated t o be one
It is usually a series resonant circuit. The of t w o stable states where the overvoltage is
subject had gained some mystique from tales at the same frequency as the energising
of strange noises emanating from power voltage. Other stable states could, however,
transformers accompanied by excessive exist with ferroresonance at subharnionic
voltages and currents. All these phenomena ferroresonant frequencies. In his
are true, and five expert speakers presentation entitled 'Living with
de-mystified the subject. ferroresonance on 1 1 kV rural distribution
Eurlng John Rye (Consultant) opened the systems', Doug considered the effect of load
discussion with the very apt title 'Tales of the resistance, the calculation of ferroresonant
unexpected'. This featured a number of voltage and critical damping resistance, the
practical instances where ferroresonance has role of surge arresters, limits for cable lengths
occurred in his 40 years' experience in the and transformer design. On this last point,
ESI. His concluding example showed that it is material and assembly costs have t o be
quite possible to have ferroresonant balanced against capitalised losses and rate
conditions in urban networks which have of return on investment t o determine the
POWER ENGINEERING JOURNAL JUNE 1996 135

You might also like