under a floor?
What is the maximum temperature difference between makeup and and exhaust air for a
Type I hood?
� heat
� vapor
� smoke (correct answer)
� odors
Type B double-wall connectors are being used to connect a Category I natural draft
65,000 BTU water heater and 187,500 BTU natural draft furnace, to a 30 feet tall
Type B double-wall common vent. What size common vent is required?
� 4
� 3
� 6 (correct answer)
� 5
� Mechanical systems
� Duct Work
� Venting of Mechanical systems
� None of the above (correct answer)
Attic access openings shall be a minimum of _______ or large enough for the removal
of the equipment.
� 20 x 30 (correct answer)
� 24 x 30
� 30 x 36
� 22 x 30
The door for a HVAC unit in a meeting room shall be 36" wide and how tall?
A 66" high attic space containing an appliance, shall be provided with a passageway
not more than ___ feet in length measured along the centerline of the passageway
from the opening to the appliance.
� 30
� 22
� 24
� 20 (correct answer)
A 14" round sheet metal duct being installed in a single dwelling unit shall be at
least ______ inch thick.
� .0175
� .0236
� .0187
� .0157 (correct answer)
Dryer exhaust ducts for clothes dryers shall be equipped with ______.
Piping for other than dry gas conditions shall be sloped not less than ____ inch in
15 feet to prevent traps.
� 3/16
� 1/8
� 1/4 (correct answer)
� 1/2
Vents shall terminate not less than ___ feet in vertical height above the highest
connected appliance flue collar.
� 3
� 5 (correct answer)
� 4
� 8
Which of the following will the inspector not allow of a Type I grease hood?
I. Terminated 42� above the roof.
II. Terminated 12� from the adjoining grade.
� I only
� II only
� Both I and II
� Neither I or II (correct answer)
� Attic
� Storage
� Crawlspace
� none of the above (correct answer)
A room containing a 25,000 BTU/h furnace and an 11,000 Btu/h water heater that
draws all combustion air through a mechanical air supply system, shall have
combustion air supplied from the outdoors at a rate not less than ____ cubic feet
per minute.
� 8.9
� 9
� 12.6 (correct answer)
� 18
Two naturally vented appliances using an 18 foot high Type B double-wall 16" common
vent are allowed to have a combined input rating of ______, when stated in
thousands of BTU/H.
� 1690
� 2147
� 1910
� 1510 (correct answer)
Copper tubing shall be joined by brazing with filler metals having a melting point
of not less than ____ degrees (F).
A room containing a 25,000 BTU/h furnace and an 11,000 Btu/h water heater that
communicates to the outdoors using two permanent vertical ducts, and all air from
the outdoors comes from the ventilated attic, shall have openings with a minimum
net free area of ____ square inches.
� 9 (correct answer)
� 7
� 12
� 18
The transition duct for a domestic clothes dryer can be which of the following?
Feedback: 504.6.3--- the transition ducts---plastic ducts are usually not listed
for dryers
Single-wall metal connectors are being used to connect a Category I natural draft
80,000 BTU water heater and 200,000 BTU fan forced furnace, to a 10 feet tall
masonry chimney. What is the minimum internal area of the masonry chimney flue in
square inches?
� 63
� 38 (correct answer)
� 28
� 50
� 12
� 10
� 8
� 15 (correct answer)
The region within an occupied space between planes 3 and 72" above the floor and
more tan 2' from the walls of the space or from fixed air-conditioning equipment is
known as ____________.
Connectors shall connect to a chimney flue at a point not less than ___ inches
above the lowest portion of the interior of the chimney flue.
� 18
� 12 (correct answer)
� 14
� 24
A 24 in. x 12 in. metal louver shall be assumed to have a net free area of ______
square inches.
� 288
� 144
� 72
� 216 (correct answer)
A Type ___ vent shall be used as a common vent for an oil-burning and gas
appliance.
� B or L
� B
� B-W
� L (correct answer)
Any appliance in which the products of Combustion Air at the point of entrance to
the flue has a temperature greater than 2000 degrees F is know as a(n)
__________________________.
� 30
� 25
� 10 (correct answer)
� 6
A rooftop unit is installed _______' from the edge of a roof with a 3/12 pitch, a
guard which is a maximum of 42� high must be installed to keep people working on
the unit for falling off the roof.
� 5'
� 12'
� 10' (correct answer)
� 3'
Any appliance in which the products of Combustion Air at the point of entrance to
the flue has a temperature more than 1000 F and less than 2000 degrees F is know as
a(n) __________________.
� 25 (correct answer)
� 22
� 20
� 30
Hydronic piping systems shall be tested hydrostatically at one and one half times
the maximum system design pressure, but not less than ___ psi.
� 80
� 125
� 90
� 100 (correct answer)
A room that contains a 25,000 Btu/h gas furnace and depends solely on indoor
combustion air must contain at least _____ cubic feet.
In a dry cleaning plant with a Type II system all of the following conditions must
apply in the dry cleaning and drying rooms except.
� A hazardous chemical alarm is installed when the PPM of toxicity gets above a
predetermined level. (correct answer)
� Compliance with DOL 29 CFR Part 1910.1000
� Mechanical ventilation must be designed to exhaust 1 cfm/ft2 air per minute
� Ventilation system shall operate automatically when the dry cleaning
equipment is in operation
A 125,000 BTU Category I natural draft furnace is being installed in the basement
of a 2,400 sq./ft. house. The installer is using a single-wall metal connector with
a rise of 2 feet and a lateral run of 5 feet, to a Type B double-wall gas vent that
has a total height of 20 feet. The vent size would be __ inches, and the connector
___ inches.
� Toilet Rooms
� Surgical Rooms
� Storage Rooms
� Garages (correct answer)
A commercial hood which removes steam and heat and not grease laden vapors is a
______________________ hood.
� Type IV
� Type I
� Type II (correct answer)
� Type III
� 9 (correct answer)
� 6
� 12
� No Reduction Allowed
The total amount of air needed for ventilation as well as fuel combustion is known
as ______________.
An exhaust outlet for a commercial heavy duty cooking appliance shall serve not
more than ________ of hood.
� 10'
� 15'
� 12' (correct answer)
� unlimited
The appliances, equipment and systems regulated by this code shall not be located
in a(n) _______________.
� stairwell
� kitchen
� repair garage
� elevator shaft (correct answer)
� 0"
� 3" (correct answer)
� 8"
� 6"
A system that continues to operate during a fire will utilize a ________ fire
damper.
� high-heat
� positive-pressure
� static
� dynamic (correct answer)
Space within a dwelling unit utilized for living, sleeping, eating, cooking bathing
purposes is known as ______________________________.
When testing a Type I hood all of the following shall be inspected and tested
except?