SIPROTEC 5

Overcurrent Protection 7SJ8

© Siemens AG 2012. All rights reserved.


Overcurrent or Motor Protection
You need powerful functionality and flexibility?

„Then you should go for SIPROTEC 5!“


Powerful engineering with DIGSI 5

Modular and flexible


Modular hardware communication
Basic module + Different plug-in modules
up to 4 expansion Different protocols
modules Security inside

Flexible functionality
51 67 50 51N 50N 67N 67Ns 79 49 27 59 81 25 32 SIPROTEC 5 Series

© Siemens AG 2012. All rights reserved.


Page 2 2013-09-04 Energy Automation Sector Infrastructure & Cities
SIPROTEC 5 Overcurrent and Motor Protection

Overcurrent Protection Motor Protection


7SJ8 7SK8

© Siemens AG 2012. All rights reserved.


Page 3 2013-09-04 Energy Automation Sector Infrastructure & Cities
Agenda

Devices 7SJ8

Typical applications 7SJ8

Functional improvements 7SJ8

© Siemens AG 2012. All rights reserved.


Page 4 2013-09-04 Energy Automation Sector Infrastructure & Cities
SIPROTEC 5
Overcurrent protection devices

OC protection 7SJ85
(modular IO)

Nov./13
OC protection 7SJ82
(non-modular IO)

OC protection,
7SJ86
as line protection backup
(modular IO)

© Siemens AG 2012. All rights reserved.


Page 5 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection
7SJ85 – Profile

Feeder protection
Multifunctional protection
All network types, all voltage levels
Applications

Multi feeder protection

4 I, 4 U … (x I, x U)
11 BI, 9 BO ... 59 BI, 33 BO …
Up to 5 plug-in modules
Up to 4 expansion modules expandable

Suitable device 7SJ85


Directional OC protection with basic Phasor measurement unit PMU
& advanced functionality Modular software
functions

Protection interface IEC 61850 (Edition 1 and 2)


Device

Ground fault protection for Multiple & redundant communication


comp./isolated networks SIPROTEC 5 standard functions for
U, f, P/Q protection functions control and monitoring
AR, Sync function
© Siemens AG 2012. All rights reserved.
Page 6 2013-09-04 Energy Automation Sector Infrastructure & Cities
SIPROTEC 5
Overcurrent protection devices

OC protection 7SJ85
(modular IO)

Nov./13

OC protection 7SJ82
(non-modular IO)

OC protection,
7SJ86
as line protection backup
(modular IO)

© Siemens AG 2012. All rights reserved.


Page 7 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection
7SJ82 – Profile (scheduled for Oct. 2013)

Feeder protection
Multifunctional protection
All network types, all voltage levels
Applications

4 I, 4 U
11 BI, 9 BO or 23 BI, 16 BO
Up to 2 plug-in modules
non-expandable via 1/6 modules non-expandable

Suitable device 7SJ82


Dir. & Non-Dir. OC protection with Phasor measurement unit PMU
basic & advanced functionality Modular software
functions

Protection interface IEC 61850 (Edition 1 and 2)


Device

Same functionality as 7SJ85


Ground fault protection for Multiple & redundant communication
comp./isolated networks SIPROTEC 5 standard functions for
U, f, P/Q protection functions control and monitoring
AR, Sync function
© Siemens AG 2012. All rights reserved.
Page 8 2013-09-04 Energy Automation Sector Infrastructure & Cities
Differentiation of 7SJ82 and 7SJ85/86

7SJ82 7SJ85/86

HW Modularity Base module not expandable Base module expandable with


with 1/6 expansion modules 1/6 expansion modules
IO limited to 23 BI, 16 BO max. IO e.g.: 75 BI, 40 BO 1)
max. 4 I, 4 V max. 24 analog inputs I or U
max. 2 plug-in modules max. 5 plug-in modules
no keylock-switch option keylock switch option
max. 16 LEDs 32 / 48 / … LEDs
standard and large display standard and large display
without display

Housing flush mounting flush mounting


surface panel mounting
detached operation panel

1) 1/1 x 19’’ device

© Siemens AG 2012. All rights reserved.


Page 9 2013-09-04 Energy Automation Sector Infrastructure & Cities
Differentiation of 7SJ82 and 7SJ85/86

7SJ82 7SJ85/86
integrated port J: integrated port J:
COM specifics
DIGSI 5 DIGSI 5
IEC 61850 Reporting IEC 61850 Reporting
IEC 61850 GOOSE
Application / FW
Identical functionality
the same protection, supervision and
automation functions are applied

© Siemens AG 2012. All rights reserved.


Page 10 2013-09-04 Energy Automation Sector Infrastructure & Cities
SIPROTEC 5
Overcurrent protection devices

OC protection 7SJ85
(modular IO)

Nov./13
OC protection 7SJ82
(non-modular IO)

OC protection,
7SJ86
as line protection backup
(modular IO)

© Siemens AG 2012. All rights reserved.


Page 11 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection, as line protection backup
7SJ86 – Profile

Directional overcurrent protection


as backup line protection
transmission networks
Applications

4 I, 4 U … (x I, x U)
11 BI, 9 BO ... 23 BI, 25 BO …
max. 5 plug-in modules
max. 4 expansion modules (1/6) expandable

Suitable device 7SJ86


Directional OC protection, Phasor measurement unit PMU
configurable as emergency function Modular software
Same(Edition
functionality
functions

67N for high resistive gnd. faults IEC 61850 1 and 2)


Device

(same functions as in 7SA/7SL) Multiple as 7SJ82/85


& redundant communication
85/67N teleprotection schemes SIPROTEC 5 standard functions for
AR, Sync function control and monitoring

© Siemens AG 2012. All rights reserved.


Page 12 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection
Predefined HW variants

For each 7SJ8 device type several standard HW variants are predefined:

7SJ82
U1: 1/3 19’’, 4 I, 11 BI, 9 BO
U2: 1/3 19’’, 4 I, 23 BI, 16 BO
U3: 1/3 19’’, 4 I, 4 U, 11 BI, 9 BO
U4: 1/3 19’’, 4 I, 4 U, 23 BI, 16 BO

Fast configuration of your HW


© Siemens AG 2012. All rights reserved.
Page 13 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection
Predefined HW variants

For each 7SJ8 device type several standard HW variants are predefined:

7SJ85
S1: 1/3 19’’, 4 I, 4 U, 11 BI, 9 BO
S2: 1/2 19’’, 4 I, 4 U, 17 BI, 16 BO
S3: 1/2 19’’, 4 I, 4 U, 27 BI, 17 BO
S4: 2/3 19’’, 4 I, 4 U, 43 BI, 25 BO
S5: 5/6 19’’, 4 I, 4 U, 59 BI, 33 BO

7SJ86
L1: 1/3 19’’, 4 I, 4 U, 11 BI, 9 BO
L2: 1/2 19’’, 4 I, 4 U, 17 BI, 16 BO
L3: 1/2 19’’, 4 I, 4 U, 23 BI, 25 BO

Fast configuration of your HW


© Siemens AG 2012. All rights reserved.
Page 14 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection
Online-Configurator - Define your device

Define your own device according to your requirements!


Modify the standard variant by adding or changing modules according to
the required number of currents & voltage inputs and binary IOs.
Example 7SJ85:

Possible
expansion modules

© Siemens AG 2012. All rights reserved.


Page 15 2013-09-04 Energy Automation Sector Infrastructure & Cities
Agenda

General and device overview 7SJ8

Typical application 7SJ8

Functional improvements 7SJ8

© Siemens AG 2012. All rights reserved.


Page 16 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection 7SJ85
Protection of multiple feeders

Protection of three feeders with only


requirement
Customer

one device
Flexible (expandable) hardware

OC protection device 7SJ85


Siemens
solution

Hardware:
Standard Variant S1 + 1 x expansion
module IO203 -> 12 I, 4 U

3 function groups “U/I 3-phase”, each Reduced investment:


connected to one 3-phase current One device instead of three
Simplified parameterization:
functions

Benefits
measuring point
Device

51, 51N (OC protection, phases & Set one function and copy it
ground) per function group Shortened commissioning
Up to 7 feeders in one device

new solution (due to expandable hardware)


© Siemens AG 2012. All rights reserved.
Page 17 2013-09-04 Energy Automation Sector Infrastructure & Cities
Application template:
protection of multiple feeders
Feeder 1

Feeder 2

Feeder 3

© Siemens AG 2012. All rights reserved.


Page 18 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection 7SJ82, 7SJ85
Dir. Comparison of a line supplied from two sides

Directional OC protection of a line


requirement
Customer

supplied from two sides without time


grading
Supervised protection data
communication via optical fiber
Integrated protection data interface 7SJ82 7SJ82 7SJ82 7SJ82
67 PDI PDI 67 67 PDI PDI 67
Hardware: Std.Var S1: 4 I, 4 U
Siemens
solution

PDI PDI
App.Temp. “Dir. OC grounded” Communication Communication
Communication: 1 plug-in module
(2 x FO): protection data & station com.

1 function group “U/I 3-phase”, Fast fault clearing


connected to CTs and VTs, incl. fct. 67 Reduced investment (1 module)
functions

Benefits
1 FG “Prot. Data Communication” (PDI) Adaptable to com. infrastructure
Device

Exchange of dir. information over the Secure communication


PDI for release (or blocking) the 67N
Supervision of PDI link

new solution (due to PDI option)


© Siemens AG 2012. All rights reserved.
Page 19 2013-09-04 Energy Automation Sector Infrastructure & Cities
Application template:
Dir. Comparison for a line supplied from two sides
Line

© Siemens AG 2012. All rights reserved.


Page 20 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection 7SJ82, 7SJ85
Ground fault protection for transient & static faults

Dir. protection against static ground


requirement
Customer

faults in a resonant-grounded network


Dir. detection of transient ground faults
in a resonant-grounded network

Function for transient and static earth


Siemens
solution

faults
4th CT input as sensitive input
App.Temp. “Dir. OC comp./isol. network”

1 function group “U/I 3-phase”, Reduced investment: one device


connected to phase CTs, cable-type CT instead of 7SJ62 and 7SN60
functions

Benefits
and broken delta voltage Reduced engineering
Device

67Ns function, with two elements: Higher sensitivity and stability of


one “Watt-metric” element transient function compared to
one “Transient”*) element 7SN60
*) with V3, scheduled for April 2013

new solution (due to transient GF element)


© Siemens AG 2012. All rights reserved.
Page 21 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection 7SJ82, 7SJ85
Restricted ground fault prot. (low impedance)
IA
Restricted earth fault protection for a
requirement
Customer

transformer winding, as 7UT8 backup IB A


Low impedance principle required
IC B

C
7SJ82
all transformer backup protection 3I0“ = IA + IB + IC
Siemens

87N T 51
solution

functions in one 7SJ8 device


3I0‘ = ISP
Hardware: Std.Var S1: 4 I, 4 U ISP 51N
App.Temp. “OC protection” + 87N T

1 function group “U/I 3-phase” Reduced investment


connected to phase CTs, incl. 87N T Reduced engineering
functions

Benefits
1 function group “U/I 1-phase” High sensitivity
Device

connected to the transformer star point


FG “U/I 1-phase” connected to FG “U/I
3-phase”

new solution (due to new 87N T function)


© Siemens AG 2012. All rights reserved.
Page 22 2013-09-04 Energy Automation Sector Infrastructure & Cities
Application template:
Restricted ground fault protection (low impedance)

© Siemens AG 2012. All rights reserved.


Page 23 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection 7SJ85
Protection of capacitor banks

Capacitor banks in different designs


requirement
Customer

(e.g. different no. of filter circuits)


should be protected with one device

Capacitor
All required functions in one 7SJ85
Siemens
solution

Hardware: Std.Var S1 + IO203: 12 I, 4U

Filter
Application temp. “Capacitor bank in H
configuration”

1 function group “Capacitor bank” with All functions in one device ->
all required interfaces reduced investment
functions

Benefits
Specific functions for the cap. bank: Optimal tailoring of HW and
Device

- 59C Peak overvoltage protection functionality to the specific cap.


- 60C Current unbalance protection Bank
Measurement up to the 50th harmonic Very high sensitivity of the
Autom. Compensation of oper. unbal. unbalance measurement
new solution (due to new functions and SIP5 HW flexibility)
© Siemens AG 2012. All rights reserved.
Page 24 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection 7SJ86
Backup protection for Line protection devices

Directional emergency OC protection of


requirement
Customer

a line, as 7SA8 backup


backup protection by a redundant 7SA8 7SA8
PDI Communication
device 21 PDI PDI 21
85/67N 85/67N
Emergency Mode
Hardware: Std.Var L1: 4 I, 4 U 7SJ86 7SJ86
51 PDI PDI 51
Siemens

Communication: 1 plug-in module


solution

85/67N 85/67N
(2*FO): protection data & station com.

1 function group “Line”, incl. fct. 67, Optimal fault clearing


67N (same fct. as in 7SA) Reduced training and engineering
functions

Benefits
Activation of 67 and 67N only in case of cost through harmonized
Device

7SA emergency functionality in 7SA8 and 7SJ86


85/67N teleprotection schemes (FG Line, 67N, 85/67N)
available if required (via PDI) Reduced engineering through
integrated teleprotection function
optimized solution for line protection backup
© Siemens AG 2012. All rights reserved.
Page 25 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection 7SJ8x
Phasor measurement unit (PMU)

Dynamic ‚Wide Area Monitoring‘


requirement
Customer

Blackout prevention via over-regional


control operation

Phasor measurement available in each


SIPROTEC 5 device
Siemens
solution

Data transmission to regional data


concentrators (e.g. SIGUARD PDP)
according C37.118

Phasor determination of local currents Increased grid quality and stability


and voltages with 1% TVE*) Increased system availability
functions

Benefits
GPS time synchronization Future save investment in new
Device

Ethernet module: Protocol setting = relay device technology


SYNC/PMU

*) total vector error

Increased system availability


© Siemens AG 2012. All rights reserved.
Page 26 2013-09-04 Energy Automation Sector Infrastructure & Cities
Agenda

Devices 7SJ8

Typical applications 7SJ8

Functional improvements 7SJ8

© Siemens AG 2012. All rights reserved.


Page 27 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent & Motor protection 7SJ8x, 7SK8x
Unified functions

Get busy with one function only once


requirement
Customer

Same behavior of one function in 25 50BF 79


different devices

A system where one and the same


function is applicable in different devices
Siemens
solution

7SJ8 7SA8 7SD8 6MD8

Most of your protection and supervision Less clarification efforts


function are fully identically, no matter in Less engineering effort
functions

which device they are applied

Benefits
Less chances for wrong function
Device

Examples are: 25, 27, 46, 50HS, 51, settings


50BF, 59, 59N, 67, 67Ns, 81, FL, …

Maximized user friendliness


© Siemens AG 2012. All rights reserved.
Page 28 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent & Motor protection 7SJ8x, 7SK8x
Basic & Advanced overcurrent protection functions

basic type: advanced type:


Reduce complexity for protection function
requirement
Customer

settings
Reduce the probability of setting
functions wrong

For the standard OC application (80%


Siemens
solution

case) the basic function is used


For more complex applications the
advanced function will be used

For each function 51, 51N, 67 and 67N Avoiding wrong parameterization
an “basic” and “advanced” function type Reducing engineering and testing
functions

exist efforts

Benefits
Device

Maximized user friendliness & minimized functional complexity


© Siemens AG 2012. All rights reserved.
Page 29 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection 7SJ8x
”True RMS” measurement precise up to 50th harmonic

Detect and evaluate signals up to 50th


requirement
Customer

harmonic, for protection and operational


measured values
OC and Thermal overload protection for
7SJ8
a capacitor bank
Sampling frequency of 8 kHz 49 51
30th harm: 1%, 50th harm: 3 %
Siemens
solution

(with 33% harmonic in relation to Cap. Bank

fundamental, 50Hz)

All OC protection functions can be correct detection and evaluation of


configured to operate either with the high harmonics
functions

“fundamental” or the “True RMS” value. optimal OC- and Overload

Benefits
Device

Other function which are related to protection for a capacitor bank


thermal conditions (e.g. Thermal
overload) also use True RMS values.

Strongly improved True RMS measurement


© Siemens AG 2012. All rights reserved.
Page 30 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent & Motor protection 7SJ8x, 7SK8x
“Watt-metric ground fault protection (67Ns)”

Ground fault function for resonant-


requirement
Customer

grounded networks
Save distinction between faulty and non-
faulty for all levels of ground fault rest
currents
Use of one dir. characteristic for low-
ohmic faults with reduced dir. sensitivity
Siemens
solution

Use of another dir. characteristic for


high-ohmic faults with max. dir.
sensitivity

The 67Ns function allows to configure 2 Improved stability in case of


watt-metric stages with independent dir.- low-ohmic faults
functions

characteristics Maximum sensitivity in case of

Benefits
Device

The high-set stages bocks the low-set high-ohmic faults


stage (via add. logic)

Improved stability and sensitivity


© Siemens AG 2012. All rights reserved.
Page 31 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent & Motor protection 7SJ8x, 7SK8x
“Watt-metric ground fault protection (67Ns)”

Ground fault function for resonant-


requirement
Customer

grounded networks
Maximum stability (no over-functioning)
after the fault extinction

Detection of the decaying zero


sequence system signals, after the fault
Siemens
solution

extinction
Blocking of possibly affected ground
faults stages

The 67Ns function offers a detection of Improved stability during the


the fault extinction (decaying U0 & 3I0) decaying of the zero-sequence
functions

The 67Ns stages provide a blocking system after the fault extinction

Benefits
Device

option in case of the fault extinction


detection

Improved stability
© Siemens AG 2012. All rights reserved.
Page 32 2013-09-04 Energy Automation Sector Infrastructure & Cities
Overcurrent protection 7SJ8x
Improved inrush stabilization

Stable at inrush currents (switching ON


requirement
Customer

of a transformer)
Stable at sympathetic inrush currents
(switching ON of a parallel transformer) IMP1

Method 1: I2,Harm/I1,Harm > 15%


Inrush detection function blocks the Method 2: CWA Flat area evaluation
Siemens
solution

overcurrent protection
New is the one out of two decision of
two different inrush algorithms

Inrush detection function with two Avoiding of false trip in the case of
different measuring principles an inrush or sympathetic inrush if
functions

Second harmonic evaluation with 2nd harmonics are quite low

Benefits
Device

the cross block option Increased system availability


Curve waveform analysis (CWA)

Increased stability at inrush currents


© Siemens AG 2012. All rights reserved.